EnviroTank Details & Certification
Report No 285/4102208-2
Page 3 of 5
EXAMINATION AND TEST
Model reference: PG13 Nominal size (NS): 15 Class: 1
CLAUSE ASSESSMENT
3. ASSESSMENT OF TEST RIG
Refer to BSI Test Report No 285/4075353 - Test Rig. Pass
4. TEST AND ASSESSMENTS
Testing was carried out on a test rig approved in accordance
with clause 3. Pass
Testing was witnessed by BSI Product Services. Pass
The nominal size of the separator was NS15. Pass
4.2 Test fluids
The water used was declared by the manufacturer to be
drinking water. Pass
The initial temperature of the water was 10.9 °C. Pass
The final temperature of the water was 11.2 °C. Pass
The pH of the water was 7.42. Pass
The light liquid was fuel oil, having a density of 0.85 ± 0.015
g/cm3 at a temperature of 12°C. Pass
The temperature of the light liquid was 6.2 °C. Pass
4.3 Test procedure for nominal size and class
TE (mins) = 20.96
VK (l) = 4716
-1
Qw (ls ) = 15
The manufacturer's value for VK was checked by review of
manufacturer's drawing number 2755 dated 4 January 2000
and appropriate calculations. Samples taken during the test
were dispatched in accordance with Appendix A of the
Specification. Pass
The samples taken during the test were treated and dispatched
in accordance with Appendix A of the Specification. Pass