Attached to the e-mail Multiple Housing Type 3 - Retirement & Special Needs (Aged Care Facility (Traffic Report Part 2 & Noise Assessment Report) - MCU18/0019.
Aged Care Facility, Noosaville
Figure 8 First Floor Facades Requiring 6.38 mm Laminated Glass (shown in red),
13.76 mm Laminated Glass (shown in yellow)
4.3 Car Park and Light Vehicle Noise
The carpark is underneath the building and not exposed to nearby residences.
Given the generally low vehicle numbers / rates of movements that would be
expected in an aged care facility, and the main pick up / drop off point is on the
Goodchap Street frontage, noise from carparks is not expected to be a cause of
nuisance.
4.4 Service Vehicles and Area
The service vehicle area is cut into the Site, and as such is partially obscured from
view from surrounding residences. The landscaped area is higher than the
pavement level, which will be effective in reducing most noise from the area.
Due to low ambient noise levels, however, it is recommended that the following
protocols be adhered to:
• Waste should not be disposed of outside between 6 pm and 7 am, and
• Service vehicles should not attend the site before 7 am or after 6 pm.
4.5 Mechanical Plant
Mechanical plant specifications are not yet available. However, given the area has
relatively low background noise levels, particularly at night-time, it is envisaged
that the plant rooms will require significant noise attenuation to achieve the
regulatory noise levels under the EPAct 1994. It is likely that a minimum level of
treatment would require noise attenuating grilled air inlets, but it is possible that
the plant rooms will need to be enclosed at ground level with any air inlet / exhaust
requirements satisfied with attenuated ducting to above the roofline. This will need
to be comprehensively assessed during the detailed design stage of the project.
5 Conclusion and Summary of Recommendations
RoadPro Acoustic was engaged by Knowles Group to assess potential effects of
environmental noise onto and emitted by a proposed aged care facility proposed
for construction on Goodchap St, Noosaville.
Existing road traffic noise levels were measured and used to validate a 3-
dimensional road traffic noise model for the site. External road traffic noise levels
were calculated, and minimum glazing requirements to satisfy the internal noise
levels in AS 2107 were determined in accordance with AS 3671.
1121R1-R0 13 December 2017 Page 9 of 10
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Noise Assessment Report.pdfRelated documentApplication case desk ↗
About this file
- File size
- 3.3 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.