                STRUCTURAL STEEL
                                                                                                                                S12       CONCRETE ENCASED STEELWORK SHALL HAVE A MINIMUM OF 50mm OF COVER CONCRETE                                                                               M7       GROUT FOR CORE FILLING SHALL BE STRENGTH GRADE S20. THE GROUT SHALL HAVE A MAXIMUM
                THE CONSTRUCTION CATEGORY HAS BEEN DETERMINED IN ACCORDANCE WITH AS 5131 AND THE
                                                                                                                                          REINFORCED WITH W5 WIRE AT 150 CRS. OR FGW41 FABRIC UNLESS NOTED OTHERWISE.                                                                                      AGGREGATE SIZE OF 10mm, A MAXIMUM SLUMP OF 230mm +/-25mm AND A MINIMUM CEMENT
                FOLLOWING PARAMETERS:
                                                                                                                                                                                                                                                                                                           CONTENT OF 300kg/m³.
                    IMPORTANCE LEVEL          - 2
                    SERVICE CATEGORY          - SC1                                                                             S14       THE POSITION AND DETAIL OF ANY SPLICES REQUIRED OTHER THAN THOSE SHOWN ON THE
                                                                                                                                          DRAWINGS SHALL BE APPROVED BY THE ENGINEER.                                                                                                             M8       ADDITIVES SHALL NOT BE ADDED TO THE GROUT OR MORTAR WITHOUT THE SPECIFIC PERMISSION
                    FABRICATION CATEGORY      - FC1
                                                                                                                                                                                                                                                                                                           OF THE ENGINEER.
                    CONSTRUCTION CATEGORY     - CC2
                                                                                                                                S15       FULL CONTACT BEARING SURFACES, WHERE SPECIFIED, SHALL COMPLY WITH CLAUSE 14.4.4.2 OF
                                                                                                                                          AS4100.                                                                                                                                                 M9       PROVIDE CLEANOUT BLOCKS AT THE BASE OF ALL REINFORCED CORES.
     S1         ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS4100 STEEL STRUCTURES
                CODE AND THE REFERENCED STANDARDS THEREIN.
                                                                                                                                S16       THE ENDS OF ALL TUBULAR MEMBERS SHALL BE SEALED WITH 5mm MINIMUM PLATES AND                                                                             M10      ALL MORTAR DAGS AND PROTRUSIONS INTO THE BLOCK OR BRICK CORES SHALL BE REMOVED
                                                                                                                                          CONTINUOUS FILLET WELDS UNLESS NOTED OTHERWISE.                                                                                                                  PRIOR TO THE PLACEMENT OF ANY CONCRETE. LOOSE MATERIAL AND DEBRIS SHALL ALSO BE
     S2         THE CONTRACTOR SHALL SUBMIT STRUCTURAL STEEL SHOP DRAWINGS FOR REVIEW BY THE
                                                                                                                                                                                                                                                                                                           REMOVED FROM THE MASONRY CORES.
                ENGINEER AND ARCHITECT, BEFORE FABRICATION COMMENCES.
                                                                                                                                S17       CLADDING TRIMMING MEMBERS FOR VALLEYS, EDGES, MECHANICAL AND HYDRAULIC
                                                                                                                                          PENETRATIONS ARE NOT NECESSARILY SHOWN. REFER PURLIN MANUFACTURER FOR DETAILS.                                                                          M11      FULLY BED SOLID UNITS, FACE BED HOLLOW UNITS AND FULLY FILL VERTICAL JOINTS. NO RAKING
     S3         THE STEEL MEMBERS SHOWN ON THE STRUCTURAL DRAWINGS ARE THOSE REQUIRED FOR THE
                                                                                                                                                                                                                                                                                                           OF MORTAR JOINTS IS PERMITTED.
                COMPLETED STRUCTURE ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ANY
                NECESSARY TEMPORARY CONNECTIONS, SUPPORTS AND BRACING TO MAINTAIN THE STABILITY AND                             S18       SUPPORT RODS FOR CEILINGS, SERVICES, ETC, WHICH ARE SUSPENDED FROM PURLINS SHALL BE
                                                                                                                                          CONNECTED TO PURLIN WEBS ONLY. NO HOLES SHALL BE DRILLED THROUGH PURLIN FLANGES.                                                                        M12      GROUTING SHALL NOT COMMENCE UNTIL THE MORTAR JOINTS HAVE GAINED SUFFICIENT STRENGTH
                SAFETY OF THE STEELWORK THROUGHOUT THE CONSTRUCTION PERIOD.
                                                                                                                                                                                                                                                                                                           TO RESIST BLOWOUT AND CORES HAVE BEEN CLEANED OUT.
     S4         THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATION FOR                                  S19       UNLESS NOTED OTHERWISE ALL STEELWORK (INCLUDING FIXINGS) SHALL BE HOT DIP
                                                                                                                                          GALVANISED OR PAINTED (INCLUDING CLEANING & PREPARATION) BASED ON THEIR LEVEL OF                                                                        M13      GROUT SHALL BE COMPACTED BY VIBRATOR OR BY RODDING WITH A ROD NOT LESS THAN 24mm
                ADDITIONAL STEELWORK, CLEATS AND BOLTS NOT SHOWN ON THE STRUCTURAL DRAWINGS.
                                                                                                                                          EXPOSURE (ATMOSPHERIC CORROSIVITY CATERGORY) IN ACCORDANCE WITH AS/NZS 2312 AND                                                                                  DIAMETER.
     S5         UNLESS NOTED OTHERWISE, ALL STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING:                                              THE REFERENCED STANDARDS THERE IN.
                                                                                                                                                                                                                                                                                                  M14      ALL CORES SHALL BE FILLED WITH GROUT, UNLESS NOTED OTHERWISE.
                                          ELEMENT                               STEEL GRADE                                     S20       REGARDLESS OF THE PROTECTIVE COATING SYSTEM ADOPTED, SOME ONGOING MAINTENANCE IS
                                                                                                                                          TO BE EXPECTED THROUGHOUT THE DESIGN LIFE OF EXPOSED STEELWORK, PARTICULARLY IN                                                                         M15      REINFORCEMENT SHALL BE PLACED ACCURATELY AND TIED SECURELY BEFORE PLACEMENT OF
                       HOT ROLLED SECTIONS                                       300 PLUS                                                 COASTAL ENVIRONMENTS.                                                                                                                                            GROUT.
                       WELDED SECTIONS (WB, WC)                                  300 PLUS                                       S21                                                                                                                                                               M16      UNLESS NOTED OTHERWISE VERTICAL CONTROL JOINTS SHALL BE PROVIDED IN BLOCKWORK AT
                                                                                                                                          NON-DESTRUCTIVE WELD TESTING, WHERE SPECIFIED, SHALL BE CARRIED OUT BY SUITABLY
                       CHS UP TO AND INCLUDING 168 DIA.                             C250                                                  QUALIFIED PERSONNEL IN ACCORDANCE WITH CLAUSE 7.4 OF AS1554.1 USING APPROPRIATE                                                                                  8.0m CRS. AND AT 4.0m FROM CORNERS, AND IN BRICKWORK AT 5.0m CRS. AND AT 2m TO 4.5m FROM
                                                                                                                                          RADIOGRAPHIC, ULTRASONIC, MAGNETIC PARTICLE OR DYE PENETRATION TECHNIQUES. THE                                                                                   CORNERS. CONTRACTOR TO CO-ORDINATE LOCATIONS WITH ARCHITECT. JOINTS TO BE 10mm WIDE.
                       CHS GREATER THAN 168 DIA, SHS AND RHS                        C350                                                  RESULTS SHALL BE PROMPTLY FORWARDED TO THE ENGINEER FOR REVIEW PRIOR TO ERECTION                                                                                 JOINTS TO BE CONSTRUCTED IN ACCORDANCE WITH CEMENT CONCRETE & AGGREGATES AUSTRALIA
                                                                                                                                          OF THE STEELWORK.                                                                                                                                                TECHNICAL NOTE TN61.
                       FLOOR PLATES                                                   250
                       MERCHANT BAR - ROUNDS, SQUARES                            300 PLUS                                       S22       ALL COATED SURFACES DAMAGED BY SITE WELDS OR CUTTING SHALL BE THOROUGHLY CLEANED,                                                                       M17      NO HOLES OR CHASES SHALL BE CUT INTO BLOCKWORK/BRICKWORK WITHOUT PRIOR APPROVAL OF
                       AND FLATS                                                                                                          PREPARED AND PAINTED IN ACCORDANCE WITH AS2312.                                                                                                                  THE ENGINEER.

                                                                                                                                                                                                                                                                                                  M18      ALL WALL INTERSECTIONS SHALL BE OF BONDED CONSTRUCTION OR TIED WITH MEDIUM DUTY TIES
                                                                                                                                                                                                                                                                                                           AT 400mm MAXIMUM CRS.
     S6         UNLESS NOTED OTHERWISE, ALL WELDS SHALL BE 6mm CONTINUOUS FILLET WHERE POSSIBLE,
                OTHERWISE ADOPT CPBW. ALL WELDS SHALL BE CATERGORY GP U.N.O. ALL WELDS SHALL BE FROM
                                                                                                                                                                                                                                                                                                  M19      IN CAVITY/BRICK VENEER WALLS PROVIDE MEDIUM DUTY GALVANISED WALL TIES AT 600 CENTRES
                E43XX/W40X ELECTRODES OR ALTERNATIVES GIVING A NOMINAL TENSILE STRENGTH OF WELD
                METAL fuw OF 430MPa OR GREATER.                                                                                           MASONRY BLOCK & BRICKWORK                                                                                                                                        VERTICALLY AND HORIZONTALLY AND AT 300 AVERAGE CENTRES ADJACENT TO OPENINGS. TIES TO
                                                                                                                                                                                                                                                                                                           BE EMBEDDED A MINIMUM OF 50mm INTO THE MORTAR JOINTS. STAINLESS STEEL TIES SHALL BE
                                                                                                                                M1        ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS3700 MASONRY CODE AND                                                                                USED IN LOCATIONS LESS THAN 1km FROM THE COAST.
     S7         ALL CLEATS AND GUSSET PLATES SHALL BE 10mm THICK, UNLESS NOTED OTHERWISE.
                                                                                                                                          THE REFERENCED STANDARDS THEREIN.
     S8         ALL BOLTS SHALL BE M20 8.8/S UNLESS NOTED OTHERWISE. BOLT HOLES SHALL BE 2mm GREATER
                THAN SPECIFIED BOLT SIZE UNLESS NOTED OTHERWISE.                                                                M2       MINIMUMDURABILITY
                                                                                                                                        MINIMUM  DURABILITYREQUIREMENTS.
                                                                                                                                                            REQUIREMENTS.
                                                                                                                                          LOCATION                                       SALT ATTACK                        MORTAR               DURABILITY CLASS OF
     S9         BOLT DESIGNATIONS SHALL CONFORM TO THE FOLLOWING:                                                                                                                        RESISTANCE GRADE                   CLASS                WALL TIES AND BUILT
                                                                                                                                                                                         OF MASONRY UNITS                                        IN COMPONENTS
                       DESIGNATION           AUST. STANDARD     INSTALLATION METHOD
                                                                                                                                          INTERIOR MASONRY                               GENERAL PURPOSE                           M3                             R3

                           4.6/S             AS 1111           SNUG TIGHT                                                                 EXTERIOR MASONRY                                     GENERAL                             M3                             R3
                                                                                                                                          GREATER THAN 1 km FROM COAST                         PURPOSE
                           8.8/S             AS/NZS 1252       SNUG TIGHT
                                                                                                                                          EXTERIOR MASONRY                                     EXPOSURE                            M4                             R4
                           8.8/TB            AS/NZS 1252       FULLY TENSIONED (SOME SLIP ALLOWED)                                        UP TO 1 km FROM COAST

                           8.8/TF            AS/NZS 1252       FULLY TENSIONED WITH NO SLIP.                                    M3        ALL MASONRY BLOCKS SHALL HAVE A MINIMUM UNCONFINED COMPRESSIVE STRENGTH OF 15MPa.
                                                               CONTACT SURFACES TO BE FREE FROM
                                                               APPLIED FINISHES                                                 M4        ALL LOAD-BEARING BRICKS SHALL HAVE A MINIMUM UNCONFINED COMPRESSIVE STRENGTH OF
                                                                                                                                          20MPa.
 S10            LOAD INDICATING WASHERS SHALL BE USED TO VERIFY TIGHTENING OF BOLTS IN TF AND TB
                CONNECTIONS.                                                                                                    M5        CLAY BRICKS SHALL EXHIBIT A MAXIMUM 5 YEAR EXPANSION OF 1.0mm/m. THE BRICK SUPPLIER
                                                                                                                                          SHALL PROVIDE A RECENT TEST CERTIFICATE CONFIRMING THE EXPANSION.
 S11            WASHERS SHALL BE INSTALLED UNDER BOTH BOLT HEAD AND NUT AT ALL SLOTTED BOLT HOLE
                LOCATIONS.                                                                                                      M6        MORTAR SHALL BE CLASS M3 OR M4 IN ACCORDANCE WITH NOTE M2 ABOVE. REFER TO AS3700 FOR
                                                                                                                                          COMPLYING MIX PROPORTIONS. SAND SHALL BE CLEAN WELL GRADED AND FREE OF SILT AND CLAY.
 S12            CONCRETE ENCASED AND FIRE SPRAYED STEELWORK SHALL NOT BE PAINTED.                                                         NO "BRICKIES LOAM" ALLOWED.




C1        ##.##.####    REVISION NAME                                                                                                                                                            BRISBANE
                                                                                 DESIGNED:         APPROVED:
                                                                                                                                                                                            T: 07 3852 4333    CONSULTANTS:                                                                       PROJECT: PROPOSED RESIDENTIAL DEVELOPMENT                                          PROJECT NUMBER
                                                                                                                                                                                                               CONSULTANTS NAME                                                                                                                                                          S24-###
                                                                                                                                                   WE S TE R A
                                                                                                                                                                                              GOLD COAST
                                                                                 DRAWN:
                                                                                                                                                                                            T: 07 5571 1599                                                                                       LOCATION: PROJECT LOCATION
                                                                                                                                                                                          SUNSHINE COAST
                                                                                                                                                                                                                                                                                                                                                                                      SHEET NUMBER
                                                                                 CHECKED:
                                                                                                                                                   PART NE RS                               T: 07 5391 3777
                                                                                                                                                                                           NORTHERN NSW
                                                                                                                                                                                                              USE FIGURED DIMENSIONS ONLY. DO NOT SCALE, IF A DISCREPANCY ARISES CHECK WITH THE
                                                                                                                                                                                                              PROJECT ENGINEER AND/OR SUPERVISING AUTHORITY. DO NOT WORK FROM REDUCED SCALE
                                                                                                                                                                                                                                                                                                  TITLE:       CONSTRUCTION NOTES - SHEET 4
                                                                                                                                                                                                                                                                                                                                                                                           1.3
                                                                                                                                                                                                                                                                                                                                                                                            .
                                                                                 DATE:                                                STRUCTURAL+CIVIL+ENVIRONMENTAL ENGINEERS                                DRAWINGS (A1-A3 SIZE PAPER). COPYRIGHT OF ALL DRAWINGS & WORKS EXECUTED FROM
                                                                                                                                                                                            T: 02 6674 8047   THEM IS VESTED IN WESTERA PARTNERS AND USE OF THERE FORE WITHOUT PERMISSION IS
                                                                                                                                                                                         CENTRAL VICTORIA
                                                                                                                                                                                                                                                                                                               CLIENT NAME                                                                          ##
                                                                                                                                                                                                              STRICTLY PROHIBITED! IT IS THE BUILDERS RESPONSIBILITY TO ENSURE ALL WORKS ARE
                                                                                 PAGE SIZE:   A3   For and on behalf of                www.westerapartners.com.au   ABN 52 097 417 975
                                                                                                                                                                                                              CARRIED OUT WITHCARE AND DUE DILIGENCE TO COMPLY WITH THE CONTRACT DOCUMENTS.       CLIENT:                                                                            REVISION
No.        DATE         REVISIONS                                   DRN   ENG                      WESTERA PARTNERS PTY. LTD.                                                               T: 03 5441 0922
Log in to download the original file

RFI - S25-054 Revised Concept Issue 18.06.2025 updated.pdf · 34.6 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.