Catchpole Building Services: iPumpsets / Boosters Fire Hose Reels compliance~assess~table~perigian Applicable Commercial precinct [Fire hydrants are required as the building is Greater than 50 2 Sprinkler booster and pumps et required as the carpar! equires sprinkler protection. Residential precinct ooster assembly is required as the fire compartment exceeds| 2000 m? and there will be more than two external fir ydrants serving the building. he sprinkler system will require pumps and_booste! assembly. Applicable Commercial precinct s the floor area exceeds 500 m? Fire hose reel/s will be equired on each store ithin 4 metres of exits. Residential precinct The carpark area and the external areas of the podium andfThe BCA gives a concessio! alconies etc of the unit blocks will require hose reelfffor hose reel coverage not tof e required within SOU’s. he laundries and th common areas and common itchens will require hose} eel coverage. ire Hydrants Applicable s the floor area exceeds 500 m? Commercial precinct The fire mains and the fire hydrant system needs to b separate from that of the residential precinct as it is a separat Mark CATCHPOLE