Catchpole Building Services:
Smoke Hazard Management
Fire and Smoke Alarms
compliance~assess~table~perigian
Applicable
Applicable emporal tones are th
urrent requirement unde
S 1670.
Commercial precinct The building is to be fitted with smoke detection and ala
system in accordance with Specification E2.2a as it is
uilding in excess of two storeys in rise with class 5 and class
6 parts.
he sprinkler system requires a Building Occupant Warnin
System (BOWS) in accordance with AS 2118.1 criteria to AS
1670 tonal requirements.
Smoke detection and alarm System is required in accordanc
ith Specification E2.2a
Residential precinct
Smoke alarms are required to be installed in accordance wit!
S 3786 and clause 3.7.2 of the BCA Volume 2.
Class 1 buildings
triums
ort. Fire Extinguishers
ire Control Centres
Mark CATCHPOLE
Not applicable
Applicable Install appropriate fire extinguishers.
Commercial precinct
ire extinguishers should be
located adjacent fire hose|
eels and area of identifie
isk. Refer Clause E1.6 of the}
CA.
Required in accordance with Table E1.6
Fire extinguisher coverage is required outside the Class 3§Some specific workplace|
SOU areas which includes the common Kitchens , laundries{fsafety criteria will dictate fire}
land the associated class 7a carpark xtinguishers to be installed
o AS 2444.
Residential precinct
N/A ot required as the building is less than 25 m effective heigh
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
20517 App P.pdf [As Published]Related documentApplication case desk ↗
About this file
- File size
- 9.0 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.