Geotechnical Report Dec 2013 Revision 1

Attached to the e-mail REC13/0146 - Response to Information Request - Email 2.

of 45

Page text shows just the words. Original shows the document exactly as it was published.

GEOTECHNICAL INVESTIGATION


Proposed Subdivision,
55 Lake MacDonald Drive,
Cooroy




Report For Kalkev Pty Ltd
c/- Callaghan & Toth Consulting Engineers
Report No. 13008-001-Rev1
2 December 2013




          Tectonic Geotechnical Pty Ltd
           PO Box 899 Buderim Qld 4556
        Mobile: 0437 755 750 / 0437 756 711
              www.tectonicgeo.com.au
               A.B.N. 83 165 727 828
Log in to download the original file

Geotechnical Report Dec 2013 Revision 1.pdf · 3.3 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

Full text of the other 44 pages

Page 2

                              55 LAKE MACDONALD DRIVE, COOROY




Document Review
   Document No.           Revision         Prepared By           Reviewed By             Date Issued

           001                    0        Darryn Quinn          Ashley Davey          5 November 2013

           001                    1        Darryn Quinn          Ashley Davey          2 December 2013




Report Distribution
   Revision             Method of Delivery                                 Issued To

       0                      Electronic                  Mr Lex Toth ([email protected])

       1                      Electronic                  Mr Lex Toth ([email protected])




Prepared By:                                              Reviewed By:




Darryn Quinn RPEQ 7602                                    Ashley Davey RPEQ 8159
Principal Geotechnical Engineer                           Principal Geotechnical Engineer




2 December 2013
Report No. 137632019-001-R-Rev0                      i

Page 3

                              55 LAKE MACDONALD DRIVE, COOROY




Executive Summary
This report details the results of a geotechnical investigation carried out for a proposed 31 lot residential
subdivision at 55 Lake MacDonald Drive, Cooroy. The geotechnical investigation was undertaken by
Tectonic Geotechnical Pty Ltd (Tectonic) for Kalkev Pty Ltd, at the request of Callaghan & Toth Consulting
Engineers (C&T). The geotechnical investigation comprised excavation/drilling of test pits and boreholes,
and subsequent laboratory testing. This report summarises the results of the investigation and provides
recommendations regarding site preparation, earthworks, and pavement design parameters.

The proposed development will comprise the subdivision of existing Lot 136 on MCH978 into 32 new
residential allotments. Construction has commenced on the initial four lots fronting Lake MacDonald Drive.
The next stage comprises three lots fronting Wilgee Court. This current investigation addresses site
conditions on Stages 3 and 4 of the development.

The site investigation comprised excavation of thirteen test pits across the site to depths of up to 2.2m below
ground level (BGL). Representative soil samples were obtained from the test pits and forwarded to a
geotechnical testing laboratory for soil classification analysis. An additional two hand auger boreholes and
dynamic cone penetrometer (DCP) tests were undertaken in the western drainage gully.

The subsurface conditions encountered in the test pits generally comprised about 0.2m of loose to medium
dense silty sand topsoil over about 0.1m to 0.2m of loose to medium silty sand (similar material as the topsoil
but no vegetation), then loose to medium dense clayey sand (clay fines of low to medium plasticity) over high
plasticity, stiff, sandy/silty clay.

The main exception to the above profile was test pit TP8, which was located within the drainage gully near
the western boundary of the site. TP8 was positioned on the outer edge of the proposed pavement, and
encountered wet, very loose silty sand and sand over stiff clay. The boreholes located in the drainage gully
encountered very loose silty sand topsoil over soft saturated silty clay to about 0.5m BGL, then firm silty clay
to about 0.8m BGL, then stiff (or stiffer) silty clay.

Groundwater was encountered in two test pits during the investigation, being TP8 at 0.3m BGL and TP10 at
1.4m BGL.

Topsoil stripping depths are expected to be in the order of 150mm to 200mm across the site. If earthworks
are conducted during or following wet weather, the silty sand is expected to lose significant strength upon
wetting up. Deeper stripping to remove the 100mm to 150mm thick silty sand layer below the topsoil may be
required.

Following topsoil stripping, we expect that the exposed subgrade will comprise the silty sand layer or
underlying clayey sand. A preliminary CBRE of 10% may be adopted for the clayey sand. For sandy clay
subgrades, a presumptive CBR of 5% may be adopted, provided appropriate drainage measures are
included in the design. If silty clay subgrade is exposed, CBR values less than 3% may be possible, in which
case, additional overexcavation and replacement may be required.

At the location of test pit TP8, the wet, very loose silty sand and sand must be removed prior to filling. The
exposed silty clay may also be wet and should be treated by oveexcavation and replacement, or be tyned
and dried.

Excavations to the depths of the test pits (generally 1.5m BGL, and TP10 at 2.2m BGL) are expected to be
within the limits of medium to large excavators and dozers.




2 December 2013
Report No. 137632019-001-R-Rev0                        ii

Page 4

                                              55 LAKE MACDONALD DRIVE, COOROY




Table of Contents
        INTRODUCTION........................................................................................................................................................ 1

        PROPOSED DEVELOPMENT................................................................................................................................... 1

        SITE DESCRIPTION.................................................................................................................................................. 1

        METHOD OF INVESTIGATION................................................................................................................................. 6

        4.1         Fieldwork ...................................................................................................................................................... 6

        4.2         Laboratory Testing........................................................................................................................................ 6

        INVESTIGATION FINDINGS ..................................................................................................................................... 7

        5.1         Regional Geology ......................................................................................................................................... 7

        5.2         Subsurface Conditions.................................................................................................................................. 7

        5.3         Laboratory Test Results................................................................................................................................ 9

        ENGINEERING ASSESSMENT .............................................................................................................................. 10

        6.1         Earthworks.................................................................................................................................................. 10

        6.1.1            Site Preparation and Traffickability........................................................................................................ 10

        6.1.2            Excavations........................................................................................................................................... 11

        6.1.3            Filling..................................................................................................................................................... 11

        6.2         Pipelines ..................................................................................................................................................... 12

        6.3         Pavement Design Parameters .................................................................................................................... 12

        LIMITATIONS .......................................................................................................................................................... 13



TABLES
Table 1: Summary of Laboratory Results ............................................................................................................................ 9


TEXT FIGURES
Text Figure 1: Image showing ground surface contours (courtesy Sunshine Coast Council [SCC] My Maps).................... 2

Text Figure 2: Construction works on Lots 1 to 4 fronting Lake Macdonald Drive............................................................... 3

Text Figure 3: Stage 3, Area of Lots 16, 18, 19, 28, 29 (approx.) ....................................................................................... 3

Text Figure 4: Location of test pit TP8 ................................................................................................................................ 4

Text Figure 5: Stage 4 – Lots 13 to 15 (approx.)................................................................................................................. 4

Text Figure 6: DCP hammer/rod at HA1 ............................................................................................................................. 5

Text Figure 7: DCP hammer/rod at HA2 ............................................................................................................................. 5

Text Figure 8: Test pit TP2.................................................................................................................................................. 7

Text Figure 9: Test pit TP8.................................................................................................................................................. 8

Text Figure 10: Spoil from test pit TP12.............................................................................................................................. 8


2 December 2013
Report No. 137632019-001-R-Rev0                                                          iii

Page 5

                               55 LAKE MACDONALD DRIVE, COOROY




FIGURES
Figure 1: Site Plan



APPENDICES
APPENDIX A
Proposed Subdivision Layout (Callaghan & Toth Drawing No. 1225-30)
APPENDIX B
Test Pit & Borehole Reports and Explanatory Notes

APPENDIX C
Laboratory Test Certificates
APPENDIX D
Report Limitations




2 December 2013
Report No. 137632019-001-R-Rev0                     iv

Page 6

                             55 LAKE MACDONALD DRIVE, COOROY


        INTRODUCTION
This report details the results of a geotechnical investigation carried out for a proposed 31 lot residential
subdivision at 55 Lake MacDonald Drive, Cooroy. The geotechnical investigation was undertaken by Tectonic
Geotechnical Pty Ltd (Tectonic) for Kalkev Pty Ltd, at the request of Callaghan & Toth Consulting Engineers
(C&T).

The geotechnical investigation comprised excavation of test pits, drilling of boreholes and subsequent
laboratory testing. This report summarises the results of the investigation, and provides recommendations
regarding:

    Preliminary stripping depths for road and allotment fills (based on test pits and general site observations);

    Preliminary pavement design parameters (i.e. CBR values based on laboratory testing, field testing, and
     presumptive values based on subgrade types);

    Traffickability of excavator working in the gully (to clear vegetation and for placement of rock spalls and
     geotextile); and

    Sewer and stormwater pipe laying conditions (i.e. excavatability; foundation suitability).



        PROPOSED DEVELOPMENT
The proposed development will comprise the subdivision of existing Lot 136 on MCH978 into 32 new
residential allotments, as shown on C&T Drawing No. 1225-30 (attached in Appendix A). The subdivision
comprises four Stages. Stage 1 consists of four lots (Lots 1 to 4) currently under construction, and Stage 2
consists of three lots (Lots 5 to 7) fronting Wilgee Court. This site investigation encompasses two stages,
designated as Stage 3 (located over the western half of the site) and Stage 4 (located over the eastern half of
the site). Stage 3 comprises16 new lots (proposed Lots 16 to 31), and Stage 4 comprises nine lots (proposed
Lots 8 to 16). The two Stages are separated by proposed park land over an existing drainage gully line.

Access to the Stage 3 allotments will be from a new road off Blue Wren Place. Access to Stage 4 will be via a
new road, Masonry Street, entering the subdivision from the north. Proposed Lots 5 to 7 will be accessed by
new driveways off Wilgee Court. Those driveways cross an existing table drain adjacent Wilgee Court.

The sewer line and manholes have been installed in Stage 4 in the eastern side of the stage (i.e. near the
central drainage gully).

It is proposed to raise the ground levels for the new lots about 500mm above the Q100 Inundation line, which is
shown on the C&T drawing in Appendix A. That results in required filling of about 600mm across proposed
Lots 16, 18, 19, and 28 to 31 in Stage 3, and Lots 13 to 15 in Stage 4. Filling in the order of about 1m height
may be required for the new access road into Stage 3.

We also understand that the proposed works may include rehabilitation of the existing drainage gullies, which
may also serve as stormwater detention basins. Those works comprise regrading of the invert of the existing
drainage gully, placement of an approximate 300mm thick layer of rock spalls, jute matting, topsoil and mulch.
The exact scope of rehabilitation works had not been finalised at the time of this investigation.

        SITE DESCRIPTION
The proposed development site is a 60ha parcel of land described as Lot 136 on MCH978 (No. 55 Lake
MacDonald Drive, Cooroy). The site has limited road frontage along Lake MacDonald Drive along the
southern boundary, and Wilgee Court on the eastern boundary. The remainder of the site is bounded by
existing residential subdivisions or rural lots along the northern, eastern and western sides.

Stage 4 comprises gently sloping ground (less than 5º) to the south-west towards the drainage gully that
traverses the site in a south to north direction. Stage 3 consists of a gently sloping northerly trending ridge
(about 5º to 7º), with gullies located on the eastern and western sides.




2 December 2013
Report N0. 13008-001-Rev1                               1

Page 7

                             55 LAKE MACDONALD DRIVE, COOROY


The site is mostly well grassed, with some isolated stands of trees around the site. The drainage gully is more
densely vegetated with long grasses and trees along the banks.

The drainage gully commences as a roadside table drain adjacent Wilgee Court along the eastern side of the
site, heading south, and then running adjacent to Lake MacDonald Drive, before heading in a northly direction
through the centre of the site.

Existing water and sewer lines also run through the middle of the site in a similar alignment to the drainage
gully.


                                      Drainage gullies




                                               Water & sewer
                                               easement




                            Blue Wren Place
Text Figure 1: Image showing ground surface contours (courtesy Sunshine Coast Council [SCC] My Maps)

General site conditions are shown on Figure 1 (presented at the end of this report), and Text Figures 2 to 7
below.




2 December 2013
Report N0. 13008-001-Rev1                                2

Page 8

                                 55 LAKE MACDONALD DRIVE, COOROY




    Text Figure 2 Construction works on Lots 1 to 4 fronting Lake Macdonald Drive




                                                                                    Lots 28/29

                                     Lots 18/19
Lot 16




    Text Figure 3: Stage 3, Area of Lots 16, 18, 19, 28, 29 (approx.)




    2 December 2013
    Report N0. 13008-001-Rev1                              3

Page 9

                             55 LAKE MACDONALD DRIVE, COOROY




                                                       Approximate location of TP8




Text Figure 4: Location of test pit TP8




              Lot 13
                                                         Lots 14/15




Text Figure 5: Stage 4 – Lots 13 to 15 (approx.)




2 December 2013
Report N0. 13008-001-Rev1                          4

Page 10

                            55 LAKE MACDONALD DRIVE, COOROY




Text Figure 6: DCP hammer/rod at HA1




Text Figure 7: DCP hammer/rod at HA2




2 December 2013
Report N0. 13008-001-Rev1                  5

Page 11

                             55 LAKE MACDONALD DRIVE, COOROY


        METHOD OF INVESTIGATION
4.1      Fieldwork
The subsurface investigation comprised excavation of thirteen test pits (designated TP1 to TP13) to depths of
up to 2.2 m below ground level (BGL) across the site using either a Komatsu PC220 (22 tonne) excavator or a
Komatsu PC78MR (8 tonne) excavator. The smaller excavator was used for the test pits on the eastern side
of the site (Stage 3) due to access difficulties in getting the larger excavator across the drainage gully.

Test pits TP1 to TP6 were located within proposed residential allotments. Test pits TP7 to TP9, TP12 and
TP13 were located in proposed road areas. Test pit TP10 was located in where a sewer manhole is
proposed, and test pit TP11 was excavated to assess the material near the central drainage gully for
accessibility. No deeper test pits were excavated in Stage 3, as the sewer line had been installed.

Test pits TP1 to TP4, TP7, TP8, TP12 and TP13 were located within Stage 4, with test pits TP5, TP6, TP9 to
TP11 being located in Stage 3.

Pocket penetrometer (PP) testing was carried out on the sidewalls of the test pits to gain an indication of soil
strength/consistency. Disturbed samples were taken from the test pits for laboratory soil classification testing.

In addition to the above, two hand augered boreholes (HA1 and HA2) were drilled within the western drainage
gully to depths of 1.0m BGL. Dynamic cone penetrometer (DCP) tests were carried out adjacent to the
boreholes, and also at the location of TP8 to assess the strength/consistency of the soil types within the gully
area. The hand augers were located near the widest part of the drainage gully, where it was expected that the
greatest accumulation of sediments may occur.

Test pit and borehole locations were positioned on site using offsets from the road centreline and boundary
survey pegs. Test co-ordinates were obtained using a hand held GPS with an accuracy of ±5m, and are
provided on the test pit and borehole logs.

The fieldwork was carried out in the presence of an experienced geotechnical engineer from Tectonic on 17
October 2013 (test pits) and 28 November 2013 (hand augered boreholes). Reports of test pits and boreholes
(with DCP test results), along with explanatory notes are presented in Appendix B. Test pit and borehole
locations are shown in Figure 1, and also on C&T layout drawing in Appendix A.

4.2       Laboratory Testing
Selected soil samples were dispatched to Geotech (SC) Pty Ltd, a NATA accredited geotechnical testing
laboratory located in Kawana, for geotechnical testing. Laboratory testing was undertaken in accordance with
Australian Standard AS1289 Method for Testing Soils for Engineering Purposes and comprised:

       Atterberg Limits (liquid limit, plastic limit, plasticity index, linear shrinkage) and Fines Content analyses
        for soil classification purposes; and
       Soaked CBR (single point) for pavement design purposes.

A summary of the laboratory testing results is presented in Section 5.3, and the laboratory test certificates are
attached in Appendix C.




2 December 2013
Report N0. 13008-001-Rev1                               6

Page 12

                              55 LAKE MACDONALD DRIVE, COOROY


        INVESTIGATION FINDINGS
5.1      Regional Geology
The 1:100,000 Gympie Special Geological Map (Sheet 9445 and Part 9545) indicates that the site is underlain
by the Early to Middle Triassic-aged Kin Kin Beds formation comprising arenite, argillite, phyllite.

5.2       Subsurface Conditions
The subsurface conditions encountered in the test pits located in the proposed residential areas (TP1 to TP6)
generally comprised about 0.2m of loose to medium dense silty sand topsoil over about 0.1m to 0.2m of loose
to medium silty sand (similar material as the topsoil but no vegetation), then loose to medium dense clayey
sand. High plasticity, sandy/silty clay was encountered below the clayey sand in all test pits except TP3. Test
pit TP1 did not encountered the clayey sand layer (silty sand directly overlies clay).




                                                                           Topsoil
                                                                           Silty Sand

                                                                           Clayey Sand

                                                                           Sandy Clay




Text Figure 8: Test pit TP2

The test pits located in the proposed pavement areas (TP7, TP9, TP12 and TP13) encountered similar profiles
as TP1 to TP6. Test pit TP8, which was located at the edge of the drainage gully, encountered 0.3m of very
loose, grey/dark grey, moist silty sand with a high organic content over wet, very loose sand, then stiff sandy
clay at 0.5m depth. Some large logs were encountered in test pit TP12, and some smaller logs were found in
TP13.




2 December 2013
Report N0. 13008-001-Rev1                             7

Page 13

                              55 LAKE MACDONALD DRIVE, COOROY




                                                                                            Wet, very loose sand



                                                                                            Silty clay




Text Figure 9: Test pit TP8




                                                                Logs within topsoil layer




Text Figure 10: Spoil from test pit TP12

Hand auger boreholes HA1 and HA2 encountered wet, very loose silty sand topsoil to about 0.1m to 0.2m
depth BGL over wet, soft silty clay, becoming firm at about 0.5m BGL, and stiff (or stiffer) at about 0.8m BGL.

At test pit TP8, stiff clay (PP=100kPa) was encountered at about 0.5m BGL, which is where the DCP test
indicated 1 to 2 blows per 100mm penetration. Similar results were noted for the DCP tests at HA1 and HA2,


2 December 2013
Report N0. 13008-001-Rev1                              8

Page 14

                                  55 LAKE MACDONALD DRIVE, COOROY


where DCP blows >1 per 100mm were also recorded at depths of about 0.5m BGL. Therefore, at HA1 and
HA2, the silty clay may actually be stiff from 0.5m BGL (DCP testing in wet silty clay can give low values that
underestimate the strength of the material).

Groundwater seepage was only encountered in test pits TP8 at a depth of 0.3m BGL and at TP10 at a depth
of 1.4m BGL during the investigation. Groundwater was present in boreholes HA1 and HA2 at about 0.2m
BGL. It should be noted that groundwater seepage may occur from more permeable horizons within the soil
following periods of prolonged or heavy rainfall.

Refer to detailed test pit reports and explanatory notes attached in Appendix B.

5.3        Laboratory Test Results
The results of the laboratory testing are presented below in Table 1.
Table 1: Summary of Laboratory Results
 Test Pit No.                                      TP1                  TP2          TP7                 TP9

 Depth (m)                                       0.2-0.3               0.3-0.5      0.3-0.7            0.3-0.5

 Percent fines (%)                                  46                   46

 Liquid Limit (%)                                   23                   29

 Plastic Limit (%)                                  17                   16

 Plasticity index (%)                                6                   13

 Linear Shrinkage (%)                               4.5                 10.0

 CBR (%)                                                                             17.0                19.0

 Field Moisture Content (%)                                                           9.5                18.1

 Optimum Moisture Content (%)                                                        12.7                16.5
Fines Content is the % of clay/silt fraction in the soil profile

The above laboratory test results indicate that the soil tested from TP1 is silty sand, with low liquid limit silt. .
The sample tested from TP2 is clayey sand, with low plasticity clay.




2 December 2013
Report N0. 13008-001-Rev1                                          9

Page 15

                              55 LAKE MACDONALD DRIVE, COOROY


        ENGINEERING ASSESSMENT
6.1      Earthworks
Advice provided to Tectonic by the client indicates that earthworks will comprise the placement of up to
approximately 0.6m of fill across the lower lying areas of the site to raise the ground levels about 0.5m above
the Q100 inundation level.

Filling in excess of 0.6m is expected in the area of the proposed new road into Stage 3, where the ground
level drops about 0.5m towards the drainage gully (e.g. location of test pit TP8).

Excavations to depths of up to about 2.5m are expected for the sewer line on Stage 4.

Excavations in the drainage gully areas as stripping and clearing is proposed, together with placement of rock
spalls, topsoil and muclh.

Additional earthworks may occur at future residential areas to prepare level ground for slab-on-ground
construction.

6.1.1        Site Preparation and Traffickability
The general soil profile comprised about 0.2m of grey silty sand topsoil over about 0.2m of loose to medium
dense grey silty sand (similar material to the topsoil, but lacking roots). Underlying the silty sand is loose to
medium dense clayey sand, then high plasticity sandy/silty clay. At test pit TP1, TP8 and TP11, the clayey
sand layer was not encountered.

Stripping depths to remove the surface vegetation layer are expected to be typically about 0.2m deep. Deeper
stripping is expected in the area of the draining gullies. Two test pits excavated in or close to the drainage
gullies (TP8 and TP11) indicated yup to about 0.4m to 0.5m of stripping may be required in those areas.

The subgrade materials exposed after site stripping are expected to comprise predominantly grey, loose to
medium dense silty sand. Whilst in a dry condition (as experienced at the time of the investigation), the silty
sand forms a suitable subgrade for pavement construction and/or further filling. However, this material will be
subject to significant strength loss from repetitive vehicle loading (particularly from rubber tyred plant) or if they
become wet. If earthworks are undertaken during or following wet periods the grey silty sand may need to be
overexcavated and replaced with a suitable fill material.

If the silty sands are to be overexcavated, the exposed material is expected to comprise loose to medium
dense clayey sand. Laboratory tests indicated CBR values of 17% and 19% for that material, with field
moisture contents either just below the optimum moisture content (OMC) at test pit TP7, or at OMC at test pit
TP9. Some moisture conditioning (addition of water or drying) is to be expected prior to placement of
pavement materials.

In future residential areas, the potential subgrade materials are expected to be of suitable strength to allow for
adequate compaction of future fill to be carried out (provided silty sands are not wet).

At test pit TP8, the soil profile comprised very loose, high organic silty sand over wet, very loose sand, then
high plasticity silty clay. The very loose silty sand and sand are not considered suitable for subgrade platforms
and will be required to be excavated. Following removal of the silty sand and sand, it is expected that the
exposed silty clay will be wet, and will require conditioning (tyned, dried and recompacted) prior to placement
of fill.

At test pit TP12, and to a lesser extent at TP13, large logs were found in the topsoil layer, to a depth of about
0.4m BGL. This material must be fully removed prior to placement of fill.

Due to the potential for poor traffickability across the site during and after wet periods, placement of a
minimum 150 mm thick granular working platform may be required, particularly along haul roads and any
laydown areas.

After stripping of topsoil, the natural subgrade should be ‘proof rolled’ using a minimum 10 tonne drum roller in
order to identify any ‘soft spots’. Treatment of any ‘soft spots’ may involve excavation and replacement with



2 December 2013
Report N0. 13008-001-Rev1                                10

Page 16

                              55 LAKE MACDONALD DRIVE, COOROY


select fill or tyning, appropriate moisture adjustment and compaction. Proof rolling should be carried out in the
presence of an experienced geotechnical engineer.

The site should be graded to shed surface water runoff away from earthworks and/or construction areas. .
Appropriate erosion and sediment control measures must be installed prior to commencement of earthworks
at this site.

In addition to the above assessments, a “proof” roll was conducted using the 8 tonne excavator across the
gully area between Stages 3 and 4, near the existing concrete culvert. This area was assessed for
traffickability as it appeared to be wet and soft ground. The excavator was able to traverse this area with no
difficulties. It is expected that this area would become softer and more difficult to access following wet
weather. Although the surface conditions were dry and hard at the time of the investigation, tyre ruts about
200mm deep were noted in the area between the gully and test pit TP5 on the eastern side of the drainage
gully.

6.1.2        Excavations
Excavations for future services are expected to be in loose to medium dense clayey sand and stiff (or stiffer)
sandy/silty clays. Test pit TP10 was located in an area of a future sewer manhole, with an invert level
approximately 2.5m BGL. The subsurface profile comprised medium dense silty/clayey sand over stiff sandy
clay to 2.2m BGL (maximum depth reach of excavator). Some groundwater seepage was noted at a depth of
1.4m BGL.

Excavations in the silty/clayey sand and sandy clay materials are expected to be achievable using typical
earthmoving plant (e.g. medium to large excavators, dozers). Rock was not encountered in any of the other
test pits, which were excavated to depths of up to 1.5m BGL.

Unsurcharged excavation batters could be temporarily formed no steeper than 1V:2H in the natural soils. The
presence of groundwater seepage may necessitate flatter batters.

The above recommendations do not supersede any existing safety regulations or legislation applicable to
excavations (e.g. limits on personnel entry into trenches).

Groundwater seepage was noted to be slow, and is expected to be removable by grading excavations to a low
point and pumping water from a sump.

6.1.3        Drainage Gullies
We understand that the drainage gullies may be rehabilitated by stripping and re-grading the existing ground
surface, followed by placement of rock spalls, and erosion protection measures (jute matting, topsoil, and
mulch).

Following striping of surface vegetation, the exposed material is expected to comprise silty clay. Where this
material was noted to be wet (e.g. test pit TP8, boreholes HA1 and HA2), a significant reduction is strength
was observed (e.g. soft to firm). At test pit TP11 (located within the central gully), the silty clay underlying the
topsoil was noted to be moist and stiff. The 7 tonne excavator was also able to traverse the area adjacent to
the central drainage gully.

At boreholes HA1 and HA2, the silty clay was described as firm at about 0.5m BGL, then stiff (or stiffer) below
0.8m BGL (based on DCP test results). As discussed in Section 5.2, at HA1 and HA2, the silty clay may
actually be stiff from 0.5m BGL.

Based on the above results, it appears that stiff (or stiffer) clays are present at depths within 0.8m BGL. It is
expected that stiff (or stiffer) silty clay will form a suitable foundation for the placement of rock spalls. If time
and subsurface conditions permit, it is possible that the upper soft to firm clay recorded in HA1 and HA2 to a
depth of 0.8m BGL, could be dried, tyned and re-compacted. This will reduce the volume of material to be
stripped to provide a suitable foundation for placement of rock spalls. To achieve this, the drain will need to be
cleaned out and re-graded to maintain flow towards the outlets, to allow for the clay to dry out so that tyning
and compaction may be undertaken.




2 December 2013
Report N0. 13008-001-Rev1                               11

Page 17

                              55 LAKE MACDONALD DRIVE, COOROY


The presence of deeper deposits of alluvial materials within the drainage gullies should not be discounted.
However, our assessment of the site topography and the subsurface conditions in the test pits and boreholes
indicates that there is a low risk of deep alluvial deposits accumulating within the gullies.

6.1.4        Filling
The proposed earthworks include filling of about 0.6m depth across the proposed Lots 16, 18, 19, and 28 to 31
in Stage 3, and Lots 13 to 15 in Stage 4.

Future fill located within residential areas, pavement areas, or within the gully, should be compacted at
moisture contents within the range of ±2% of optimum moisture content for Standard Compaction.
Confirmatory compaction testing must be carried out at regular intervals. A minimum of two tests per vertical
lift is recommended where structural fill heights are to exceed 300 mm. Further details for control and testing
of fill are given in Australian Standard AS 3798-2007 Guidelines on Earthworks for Commercial and
Residential Developments. Fill should be placed in 250 mm thick (loose thickness) layers and be compacted
by repeated rolling to achieve a dry density ratio of at least 95% of the maximum Dry Density Ratio (DDR) for
residential areas and gully fill, and 98% DDR for pavement fill (all Standard Compaction method).

Fill must be ‘benched’ into the natural slope, over-filled by 0.5 m (horizontally) and then trimmed back to the
well compacted material.

6.2       Pipelines
The invert level for the sewer and water pipelines are typically expected to be about 1m to 2m BGL. The
anticipated materials at that depth are expected to comprise mostly stiff (or stiffer) high plasticity sandy and
silty clay, and medium dense clayey sand.

The bases for the manholes are expected to be about 2.5m depth BGL.

The founding strata for the pipeline and manholes is expected to have an allowable bearing capacity of at
least 100kPa.

As noted in Section 6.1.2, some groundwater seepage was encountered in the test pit at TP10 in Stage 3
thorough sandy layers within the sandy clay stratum. Seepage should be readily removable from pipeline
excavations by pumping from a sump.

6.3       Pavement Design Parameters
Pavement design will be dependent upon the subgrade materials present after earthworks. Following
anticipated topsoil stripping (and where no filling is proposed), the exposed subgrade will comprise about
100mm of loose to medium dense silty sand over/or clayey sand.

Laboratory testing indicated CBR values of 17% and 19% for the clayey sand (with low plasticity clay fines).
Presumptive CBR values for clayey sand are 5% to 10% (Table 11 of Austroads Guide to Pavement
Technology, Vers 2.1- 2013). Therefore, we recommend adoption of a design CBR of 10% for the clayey
sand.

The silty/sandy clay subgrade is expected to have a CBR value less than 5%, and possibly less than 3% for
silty clay, in which case, additional subgrade treatment may be required, such as over-excavation and
replacement with granular fill (e.g. roadbase)

The above values are applicable to properly drained subgrades only, and should be confirmed by testing
following earthworks. Properly drained subgrades’ require open graded drains, site grades that shed water
and prevent ponding, and subsurface drains adjacent to pavements.

Subgrade inspection and CBR testing should be carried out following bulk earthworks to confirm design CBR
values.

If subgrade materials are allowed to ‘dry out’, significant softening (and resulting subgrade strengths less than
those nominated above) could occur on ‘wetting up’.




2 December 2013
Report N0. 13008-001-Rev1                               12

Page 18

                            55 LAKE MACDONALD DRIVE, COOROY


        LIMITATIONS
Your attention is drawn to the document “Report Limitations”, which is included in Appendix D of this report.
The statements presented in this document are intended to advise you of what your realistic expectations of
this report should be, and to present you with recommendations on how to minimise the risks associated with
the services provided for this project.




2 December 2013
Report N0. 13008-001-Rev1                            13

Page 19

                                                                                  Tectonic Geotechnical Pty Ltd
                                                                                  PO Box 899
                                                                                  Buderim Qld 4556
                                                                                  M: 0437 755 700 / 0437 756 711


                                                                       PROJECT:

                                                                       55 LAKE MACDONALD DRIVE,
                                                                       COOROY
                                           TP5
                                                                       TITLE:

                                                    TP9                SITE PLAN
                                     TP4

                                                                 TP6   CLIENT:

                               TP3                                     KALKEV PTY LTD
                                                 TP11
                 TP8                                      TP10
                                     TP7                               DRAWN:                     DATE:
           HA1         TP13                                            DJQ                        1/12/2013
                              TP1
                       TP12                                            CHECKED:                   DATE:

           HA2            TP2                                          ACD                        2/12/2013

                                                                       SCALE:
0m   50m                                                               As Shown
                                                                       LEGEND:



                                                                                 Test Pit Location


                                                                                 Hand Auger Location




                                                                       PROJECT NO.:             FIGURE:            REV:

                                                                             13008                    1              1

Page 20

                            55 LAKE MACDONALD DRIVE, COOROY




APPENDIX A
Proposed Subdivision Layout
(Callaghan & Toth Drawing No. 1225-30)




1 December 2013
Report No. 13008-001-Rev1

Page 21

                            55 LAKE MACDONALD DRIVE, COOROY




APPENDIX B
Test Pit and Hand Auger Reports and Explanatory Notes




1 December 2013
Report No. 13008-001-Rev1

Page 22

                                                                                                                                                                            Tectonic Geotechnical Pty Ltd                                            TEST PIT NUMBER TP01
                                                                                                                                                                            40 Glenn Vista Drive                                                                                   PAGE 1 OF 1
                                                                                                                                                                            Chevallum Qld 4555
                                                                                                                                                                            Telephone: 0437756711
                                                                                  CLIENT                        Kalkev Pty Ltd                                                                                    PROJECT NAME               Residential Subdivision
                                                                                  PROJECT NUMBER                                          13008                                                                   PROJECT LOCATION 55 Lake MacDonald Drive, Cooroy

                                                                                  DATE STARTED                              17/10/13                                 COMPLETED            17/10/13              R.L. SURFACE           100.8                       DATUM   m AHD
                                                                                  EXCAVATION CONTRACTOR                                                        Roberts Bros                                     EASTING         491344                             NORTHING    7079125
                                                                                  EQUIPMENT                           22t excavator                                                                             TEST PIT LOCATION               Refer site plan
                                                                                  TEST PIT SIZE                            600mm                                                                                LOGGED BY           DJQ                            CHECKED BY     ACD
                                                                                  NOTES                        RL estimated from site plan contours; co-ordinates taken from hand held GPS
                                                                                                                                           Classification
                                                                                                                            Graphic Log




                                                                                                                                                                                                                                                      Samples
                                                                                                                                                                                                                                                                       DCP Test (Blows/100 mm) /
                                                                                                                                                                                           Material Description                                        Tests
                                                                                  Method




                                                                                                                                           Symbol




                                                                                                                                                                                                                                                                        Additional Observations
                                                                                           Water




                                                                                                                                                                                                                                                      Remarks
                                                                                                             RL Depth
                                                                                                             (m) (m)
                                                                                  E




                                                                                                                                            SM              Silty SAND (TOPSOIL), fine to medium grained, grey, low liquid limit silt, roots,
                                                                                                                                                            dry, medium dense



                                                                                                                                            SM              Silty SAND, fine to medium grained, grey, low liquid limit silt, dry to moist,                 DS
                                                                                                                                                            medium dense                                                                                 LL=23
                                                                                                             100.5
                                                                                                                                                                                                                                                         PL=17
                                                                                                                                                                                                                                                       Fines=46%
                                                                                                                                                                                                                                                         LS=4.5
                                                                                                                                            CH              Sandy CLAY, high plasticity, pale grey, orange, fine to medium grained sand,
                                                                                                                                                            moist, stiff                                                                             PP=200kPa to
                                                                                                                     0.5                                                                                                                              300kPa on
                                                                                                                                                                                                                                                       sidewall
                                                                                           Not Encountered




                                                                                                             100.0




                                                                                                                     1.0




                                                                                                             99.5




                                                                                                                     1.5
                                                                                                                                                            Test Pit TP01 terminated at 1.5m
BOREHOLE / TEST PIT 13008 LAKE MACDONALD DVE.GPJ GINT STD AUSTRALIA.GDT 7/11/13




                                                                                                             99.0




                                                                                                                     2.0




                                                                                                             98.5




                                                                                                                     2.5




                                                                                                             98.0




                                                                                                                     3.0

Page 23

                                                                                                                                                                           Tectonic Geotechnical Pty Ltd                                             TEST PIT NUMBER TP02
                                                                                                                                                                           40 Glenn Vista Drive                                                                                    PAGE 1 OF 1
                                                                                                                                                                           Chevallum Qld 4555
                                                                                                                                                                           Telephone: 0437756711
                                                                                  CLIENT                        Kalkev Pty Ltd                                                                                   PROJECT NAME            Residential Subdivision
                                                                                  PROJECT NUMBER                                          13008                                                                  PROJECT LOCATION 55 Lake MacDonald Drive, Cooroy

                                                                                  DATE STARTED                              17/10/13                                 COMPLETED           17/10/13              R.L. SURFACE          101.2                         DATUM   m AHD
                                                                                  EXCAVATION CONTRACTOR                                                       Roberts Bros                                     EASTING        491335                               NORTHING    7079095
                                                                                  EQUIPMENT                           22t excavator                                                                            TEST PIT LOCATION                Refer site plan
                                                                                  TEST PIT SIZE                            600mm                                                                               LOGGED BY          DJQ                              CHECKED BY     ACD
                                                                                  NOTES                        RL estimated from site plan contours; co-ordinates taken from hand held GPS
                                                                                                                                           Classification
                                                                                                                            Graphic Log




                                                                                                                                                                                                                                                      Samples
                                                                                                                                                                                                                                                                       DCP Test (Blows/100 mm) /
                                                                                                                                                                                          Material Description                                         Tests
                                                                                  Method




                                                                                                                                           Symbol




                                                                                                                                                                                                                                                                        Additional Observations
                                                                                           Water




                                                                                                                                                                                                                                                      Remarks
                                                                                                             RL Depth
                                                                                                             (m) (m)
                                                                                  E




                                                                                                                                            SM              Silty SAND (TOPSOIL), fine to medium grained, grey, low liquid limit silt, roots,
                                                                                                                                                            dry to moist, medium dense


                                                                                                             101.0                          SC              Clayey SAND, fine to medium grained, grey, orange, low plasticity clay, moist,
                                                                                                                                                            loose to medium dense


                                                                                                                                                                                                                                                           DS
                                                                                                                                                                                                                                                         LL=29
                                                                                                                                                                                                                                                         PL=16
                                                                                                                                                                                                                                                       Fines=46%
                                                                                                                     0.5                                                                                                                                LS=10.0
                                                                                           Not Encountered




                                                                                                             100.5



                                                                                                                                            CH              Sandy CLAY, high plasticity, pale grey, orange, fine to medium grained sand,
                                                                                                                                                            moist, stiff                                                                             PP=100kPa to
                                                                                                                                                                                                                                                      200kPa on
                                                                                                                                                                                                                                                       sidewalls
                                                                                                                     1.0



                                                                                                             100.0




                                                                                                                     1.5
                                                                                                                                                            Test Pit TP02 terminated at 1.5m
BOREHOLE / TEST PIT 13008 LAKE MACDONALD DVE.GPJ GINT STD AUSTRALIA.GDT 7/11/13




                                                                                                             99.5




                                                                                                                     2.0



                                                                                                             99.0




                                                                                                                     2.5



                                                                                                             98.5




                                                                                                                     3.0

Page 24

                                                                                                                                                                           Tectonic Geotechnical Pty Ltd                                             TEST PIT NUMBER TP03
                                                                                                                                                                           40 Glenn Vista Drive                                                                                   PAGE 1 OF 1
                                                                                                                                                                           Chevallum Qld 4555
                                                                                                                                                                           Telephone: 0437756711
                                                                                  CLIENT                        Kalkev Pty Ltd                                                                                    PROJECT NAME             Residential Subdivision
                                                                                  PROJECT NUMBER                                          13008                                                                   PROJECT LOCATION 55 Lake MacDonald Drive, Cooroy

                                                                                  DATE STARTED                              17/10/13                                 COMPLETED           17/10/13              R.L. SURFACE          100.8                        DATUM   m AHD
                                                                                  EXCAVATION CONTRACTOR                                                       Roberts Bros                                     EASTING        491363                              NORTHING    7079180
                                                                                  EQUIPMENT                           22t excavator                                                                            TEST PIT LOCATION                Refer site plan
                                                                                  TEST PIT SIZE                            600mm                                                                               LOGGED BY          DJQ                             CHECKED BY     ACD
                                                                                  NOTES                        RL estimated from site plan contours; co-ordinates taken from hand held GPS
                                                                                                                                           Classification
                                                                                                                            Graphic Log




                                                                                                                                                                                                                                                      Samples
                                                                                                                                                                                                                                                                      DCP Test (Blows/100 mm) /
                                                                                                                                                                                           Material Description                                        Tests
                                                                                  Method




                                                                                                                                           Symbol




                                                                                                                                                                                                                                                                       Additional Observations
                                                                                           Water




                                                                                                                                                                                                                                                      Remarks
                                                                                                             RL Depth
                                                                                                             (m) (m)
                                                                                  E




                                                                                                                                            SM              Silty SAND (TOPSOIL), fine to medium grained, grey, low liquid limit silt, roots,
                                                                                                                                                            dry, medium dense



                                                                                                                                            SM              Silty SAND, fine to medium grained, grey, low liquid limit silt, dry, medium
                                                                                                                                                            dense
                                                                                                             100.5

                                                                                                                                            SC              Clayey SAND, fine to medium grained, grey, orange, low plasticity clay, moist,
                                                                                                                                                            loose

                                                                                                                     0.5
                                                                                           Not Encountered




                                                                                                             100.0



                                                                                                                                            SC              Clayey SAND, fine to medium grained, orange, red brown, medium to high
                                                                                                                                                            plasticity clay, moist, medium dense
                                                                                                                     1.0

                                                                                                                                                                                                                                                          DS




                                                                                                             99.5




                                                                                                                     1.5
                                                                                                                                                            Test Pit TP03 terminated at 1.5m
BOREHOLE / TEST PIT 13008 LAKE MACDONALD DVE.GPJ GINT STD AUSTRALIA.GDT 7/11/13




                                                                                                             99.0




                                                                                                                     2.0




                                                                                                             98.5




                                                                                                                     2.5




                                                                                                             98.0




                                                                                                                     3.0

Page 25

                                                                                                                                                                            Tectonic Geotechnical Pty Ltd                                            TEST PIT NUMBER TP04
                                                                                                                                                                            40 Glenn Vista Drive                                                                                   PAGE 1 OF 1
                                                                                                                                                                            Chevallum Qld 4555
                                                                                                                                                                            Telephone: 0437756711
                                                                                  CLIENT                        Kalkev Pty Ltd                                                                                    PROJECT NAME               Residential Subdivision
                                                                                  PROJECT NUMBER                                          13008                                                                   PROJECT LOCATION 55 Lake MacDonald Drive, Cooroy

                                                                                  DATE STARTED                              17/10/13                                 COMPLETED            17/10/13              R.L. SURFACE           100.5                      DATUM    m AHD
                                                                                  EXCAVATION CONTRACTOR                                                        Roberts Bros                                     EASTING         491370                            NORTHING     7079217
                                                                                  EQUIPMENT                           22t excavator                                                                             TEST PIT LOCATION               Refer site plan
                                                                                  TEST PIT SIZE                            600mm                                                                                LOGGED BY           DJQ                           CHECKED BY      ACD
                                                                                  NOTES                        RL estimated from site plan contours; co-ordinates taken from hand held GPS
                                                                                                                                           Classification
                                                                                                                            Graphic Log




                                                                                                                                                                                                                                                      Samples
                                                                                                                                                                                                                                                                       DCP Test (Blows/100 mm) /
                                                                                                                                                                                           Material Description                                        Tests
                                                                                  Method




                                                                                                                                           Symbol




                                                                                                                                                                                                                                                                        Additional Observations
                                                                                           Water




                                                                                                                                                                                                                                                      Remarks
                                                                                                             RL Depth
                                                                                                             (m) (m)
                                                                                  E




                                                                                                                                            SM              Silty SAND (TOPSOIL), fine to medium grained, grey, low liquid limit silt, roots,
                                                                                                                                                            dry, loose to medium dense


                                                                                                                                            SM              Silty SAND, fine to medium grained, grey, low liquid limit silt, dry, loose to
                                                                                                                                                            medium dense
                                                                                                                                            SC              Clayey SAND, fine to medium grained, grey, orange, low to medium plasticity
                                                                                                                                                            clay, moist, loose to medium dense



                                                                                                             100.0   0.5
                                                                                           Not Encountered




                                                                                                                                            CH              Sandy CLAY, high plasticity, pale grey, orange/red brown, fine to medium
                                                                                                                                                            grained sand, moist, stiff


                                                                                                             99.5    1.0




                                                                                                             99.0    1.5
                                                                                                                                                            Test Pit TP04 terminated at 1.5m
BOREHOLE / TEST PIT 13008 LAKE MACDONALD DVE.GPJ GINT STD AUSTRALIA.GDT 7/11/13




                                                                                                             98.5    2.0




                                                                                                             98.0    2.5




                                                                                                             97.5    3.0

Page 26

                                                                                                                                                                           Tectonic Geotechnical Pty Ltd                                             TEST PIT NUMBER TP05
                                                                                                                                                                           40 Glenn Vista Drive                                                                                       PAGE 1 OF 1
                                                                                                                                                                           Chevallum Qld 4555
                                                                                                                                                                           Telephone: 0437756711
                                                                                  CLIENT                        Kalkev Pty Ltd                                                                                   PROJECT NAME            Residential Subdivision
                                                                                  PROJECT NUMBER                                          13008                                                                  PROJECT LOCATION 55 Lake MacDonald Drive, Cooroy

                                                                                  DATE STARTED                              17/10/13                                 COMPLETED           17/10/13              R.L. SURFACE          101.5                        DATUM      m AHD
                                                                                  EXCAVATION CONTRACTOR                                                       Roberts Bros                                     EASTING        491464                              NORTHING        7079253
                                                                                  EQUIPMENT                           8t excavator                                                                             TEST PIT LOCATION                Refer site plan
                                                                                  TEST PIT SIZE                            600mm                                                                               LOGGED BY          DJQ                             CHECKED BY         ACD
                                                                                  NOTES                        RL estimated from site plan contours; co-ordinates taken from hand held GPS
                                                                                                                                           Classification
                                                                                                                            Graphic Log




                                                                                                                                                                                                                                                      Samples
                                                                                                                                                                                                                                                                       DCP Test (Blows/100 mm) /
                                                                                                                                                                                          Material Description                                         Tests
                                                                                  Method




                                                                                                                                           Symbol




                                                                                                                                                                                                                                                                        Additional Observations
                                                                                           Water




                                                                                                                                                                                                                                                      Remarks
                                                                                                             RL Depth
                                                                                                             (m) (m)
                                                                                  E




                                                                                                                                            SM              Silty SAND (TOPSOIL), fine to medium grained, grey, low liquid limit silt, roots,
                                                                                                                                                            dry, medium dense


                                                                                                                                            SC              Gravelly Clayey SAND, fine to medium grained, orange, medium plasticity clay,
                                                                                                                                                            fine to coarse size gravel (quatzose), dry, medium dense




                                                                                                             101.0   0.5
                                                                                           Not Encountered




                                                                                                                                                                                                                                                          DS




                                                                                                             100.5   1.0
                                                                                                                                            CH              Sandy CLAY, high plasticity, pale grey, orange/red brown, fine to medium                               slightly friable and fissured
                                                                                                                                                            grained sand, moist, stiff
                                                                                                                                                                                                                                                          DS




                                                                                                             100.0   1.5
                                                                                                                                                            Test Pit TP05 terminated at 1.5m
BOREHOLE / TEST PIT 13008 LAKE MACDONALD DVE.GPJ GINT STD AUSTRALIA.GDT 7/11/13




                                                                                                             99.5    2.0




                                                                                                             99.0    2.5




                                                                                                             98.5    3.0

Page 27

                                                                                                                                                                            Tectonic Geotechnical Pty Ltd                                            TEST PIT NUMBER TP06
                                                                                                                                                                            40 Glenn Vista Drive                                                                                   PAGE 1 OF 1
                                                                                                                                                                            Chevallum Qld 4555
                                                                                                                                                                            Telephone: 0437756711
                                                                                  CLIENT                        Kalkev Pty Ltd                                                                                    PROJECT NAME               Residential Subdivision
                                                                                  PROJECT NUMBER                                          13008                                                                   PROJECT LOCATION 55 Lake MacDonald Drive, Cooroy

                                                                                  DATE STARTED                              17/10/13                                 COMPLETED            17/10/13              R.L. SURFACE           101.5                      DATUM    m AHD
                                                                                  EXCAVATION CONTRACTOR                                                        Roberts Bros                                     EASTING         491540                            NORTHING     7079183
                                                                                  EQUIPMENT                           8t excavator                                                                              TEST PIT LOCATION               Refer site plan
                                                                                  TEST PIT SIZE                            600mm                                                                                LOGGED BY           DJQ                           CHECKED BY      ACD
                                                                                  NOTES                        RL estimated from site plan contours; co-ordinates taken from hand held GPS
                                                                                                                                           Classification
                                                                                                                            Graphic Log




                                                                                                                                                                                                                                                      Samples
                                                                                                                                                                                                                                                                       DCP Test (Blows/100 mm) /
                                                                                                                                                                                           Material Description                                        Tests
                                                                                  Method




                                                                                                                                           Symbol




                                                                                                                                                                                                                                                                        Additional Observations
                                                                                           Water




                                                                                                                                                                                                                                                      Remarks
                                                                                                             RL Depth
                                                                                                             (m) (m)
                                                                                  E




                                                                                                                                            SM              Silty SAND (TOPSOIL), fine to medium grained, grey, low liquid limit silt, roots,
                                                                                                                                                            dry, looses to medium dense



                                                                                                                                            SM              Silty SAND, fine to medium grained, grey, low liquid limit silt, dry, loose to
                                                                                                                                                            medium dense


                                                                                                                                            SC              Clayey SAND, fine to medium grained, grey, orange, low to medium plasticity
                                                                                                                                                            clay, dry to moist, medium dense

                                                                                                             101.0   0.5
                                                                                           Not Encountered




                                                                                                                                                                                                                                                          DS




                                                                                                                                            CH              Sandy CLAY, high plasticity, orange/red brown, grey, fine to medium grained
                                                                                                                                                            sand, moist, very stiff                                                                  PP=200kPa to
                                                                                                             100.5   1.0                                                                                                                              400kPa on
                                                                                                                                                                                                                                                       sidewall




                                                                                                             100.0   1.5
                                                                                                                                                            Test Pit TP06 terminated at 1.5m
BOREHOLE / TEST PIT 13008 LAKE MACDONALD DVE.GPJ GINT STD AUSTRALIA.GDT 7/11/13




                                                                                                             99.5    2.0




                                                                                                             99.0    2.5




                                                                                                             98.5    3.0

Page 28

                                                                                                                                                                            Tectonic Geotechnical Pty Ltd                                            TEST PIT NUMBER TP07
                                                                                                                                                                            40 Glenn Vista Drive                                                                                    PAGE 1 OF 1
                                                                                                                                                                            Chevallum Qld 4555
                                                                                                                                                                            Telephone: 0437756711
                                                                                  CLIENT                        Kalkev Pty Ltd                                                                                     PROJECT NAME               Residential Subdivision
                                                                                  PROJECT NUMBER                                          13008                                                                    PROJECT LOCATION 55 Lake MacDonald Drive, Cooroy

                                                                                  DATE STARTED                              17/10/13                                 COMPLETED            17/10/13              R.L. SURFACE           101.3                      DATUM     m AHD
                                                                                  EXCAVATION CONTRACTOR                                                        Roberts Bros                                     EASTING         491375                            NORTHING      7079146
                                                                                  EQUIPMENT                           22t excavator                                                                             TEST PIT LOCATION               Refer site plan
                                                                                  TEST PIT SIZE                            600mm                                                                                LOGGED BY           DJQ                           CHECKED BY       ACD
                                                                                  NOTES                        RL estimated from site plan contours; co-ordinates taken from hand held GPS
                                                                                                                                           Classification
                                                                                                                            Graphic Log




                                                                                                                                                                                                                                                       Samples
                                                                                                                                                                                                                                                                        DCP Test (Blows/100 mm) /
                                                                                                                                                                                            Material Description                                        Tests
                                                                                  Method




                                                                                                                                           Symbol




                                                                                                                                                                                                                                                                         Additional Observations
                                                                                           Water




                                                                                                                                                                                                                                                       Remarks
                                                                                                             RL Depth
                                                                                                             (m) (m)
                                                                                  E




                                                                                                                                            SM              Silty SAND (TOPSOIL), fine to medium grained, grey, low liquid limit silt, roots,
                                                                                                                                                            dry, medium dense



                                                                                                                                            SM              Silty SAND), fine to medium grained, grey, low liquid limit silt, dry, loose to
                                                                                                                                                            medium dense
                                                                                                             101.0
                                                                                                                                            SC              Clayey SAND, fine to medium grained, grey, orange, low plasticity clay, dry to
                                                                                                                                                            moist, medium dense
                                                                                           Not Encountered




                                                                                                                     0.5                                                                                                                               Bulk DS
                                                                                                                                                                                                                                                      CBR=17.0%




                                                                                                                                            SC              Clayey SAND, fine to medium grained, orange, brown, medium plasticity clay,
                                                                                                                                                            moist, medium dense
                                                                                                             100.5




                                                                                                                     1.0




                                                                                                                                                            Test Pit TP07 terminated at 1.2m
                                                                                                             100.0




                                                                                                                     1.5
BOREHOLE / TEST PIT 13008 LAKE MACDONALD DVE.GPJ GINT STD AUSTRALIA.GDT 7/11/13




                                                                                                             99.5




                                                                                                                     2.0




                                                                                                             99.0




                                                                                                                     2.5




                                                                                                             98.5




                                                                                                                     3.0

Page 29

                                                                                                                                                                                        Tectonic Geotechnical Pty Ltd                                            TEST PIT NUMBER TP08
                                                                                                                                                                                        40 Glenn Vista Drive                                                                                    PAGE 1 OF 1
                                                                                                                                                                                        Chevallum Qld 4555
                                                                                                                                                                                        Telephone: 0437756711
                                                                                  CLIENT                                      Kalkev Pty Ltd                                                                                   PROJECT NAME               Residential Subdivision
                                                                                  PROJECT NUMBER                                                       13008                                                                   PROJECT LOCATION 55 Lake MacDonald Drive, Cooroy

                                                                                  DATE STARTED                                           17/10/13                                 COMPLETED           17/10/13              R.L. SURFACE          99.7                        DATUM     m AHD
                                                                                  EXCAVATION CONTRACTOR                                                                    Roberts Bros                                     EASTING        491321                             NORTHING      7079142
                                                                                  EQUIPMENT                                        22t excavator                                                                            TEST PIT LOCATION               Refer site plan
                                                                                  TEST PIT SIZE                                         600mm                                                                               LOGGED BY          DJQ                            CHECKED BY       ACD
                                                                                  NOTES                                      RL estimated from site plan contours; co-ordinates taken from hand held GPS
                                                                                                                                                        Classification
                                                                                                                                         Graphic Log




                                                                                                                                                                                                                                                                   Samples
                                                                                                                                                                                                                                                                                    DCP Test (Blows/100 mm) /
                                                                                                                                                                                                        Material Description                                        Tests
                                                                                  Method




                                                                                                                                                        Symbol




                                                                                                                                                                                                                                                                                     Additional Observations
                                                                                           Water




                                                                                                                                                                                                                                                                   Remarks
                                                                                                                           RL Depth
                                                                                                                           (m) (m)
                                                                                  E




                                                                                                                                                         SM              Silty SAND (TOPSOIL), fine to medium grained, grey/dark grey, low liquid limit
                                                                                           Groundwater seepage from 0.3m




                                                                                                                                                                         silt, roots, moist, medium dense


                                                                                                                           99.5



                                                                                                                                                         SP              SAND, fine to coarse grained, pale grey/grey, trace low plasticity fines, wet,
                                                                                                                                                                         very loose


                                                                                                                                  0.5
                                                                                                                                                         CH              Sandy CLAY, high plasticity, pale grey, yellow, fine to medium grained sand,
                                                                                                                                                                         moist, stiff
                                                                                                                                                                                                                                                                 PP=100kPa on
                                                                                                                                                                                                                                                                   sidewalls
                                                                                                                           99.0
                                                                                                                                                                         Test Pit TP08 terminated at 0.7m




                                                                                                                                  1.0



                                                                                                                           98.5




                                                                                                                                  1.5
BOREHOLE / TEST PIT 13008 LAKE MACDONALD DVE.GPJ GINT STD AUSTRALIA.GDT 7/11/13




                                                                                                                           98.0




                                                                                                                                  2.0



                                                                                                                           97.5




                                                                                                                                  2.5



                                                                                                                           97.0




                                                                                                                                  3.0

Page 30

                                                                                                                                                                           Tectonic Geotechnical Pty Ltd                                             TEST PIT NUMBER TP09
                                                                                                                                                                           40 Glenn Vista Drive                                                                                   PAGE 1 OF 1
                                                                                                                                                                           Chevallum Qld 4555
                                                                                                                                                                           Telephone: 0437756711
                                                                                  CLIENT                        Kalkev Pty Ltd                                                                                    PROJECT NAME              Residential Subdivision
                                                                                  PROJECT NUMBER                                          13008                                                                   PROJECT LOCATION 55 Lake MacDonald Drive, Cooroy

                                                                                  DATE STARTED                              17/10/13                                 COMPLETED           17/10/13              R.L. SURFACE          102                          DATUM   m AHD
                                                                                  EXCAVATION CONTRACTOR                                                       Roberts Bros                                     EASTING        491483                              NORTHING    7079235
                                                                                  EQUIPMENT                           8t excavator                                                                             TEST PIT LOCATION                Refer site plan
                                                                                  TEST PIT SIZE                            600mm                                                                               LOGGED BY           DJQ                            CHECKED BY     ACD
                                                                                  NOTES                        RL estimated from site plan contours; co-ordinates taken from hand held GPS
                                                                                                                                           Classification
                                                                                                                            Graphic Log




                                                                                                                                                                                                                                                      Samples
                                                                                                                                                                                                                                                                      DCP Test (Blows/100 mm) /
                                                                                                                                                                                           Material Description                                        Tests
                                                                                  Method




                                                                                                                                           Symbol




                                                                                                                                                                                                                                                                       Additional Observations
                                                                                           Water




                                                                                                                                                                                                                                                      Remarks
                                                                                                             RL Depth
                                                                                                             (m) (m)
                                                                                  E




                                                                                                                                            SM              Silty SAND (TOPSOIL), fine to medium grained, grey, low liquid limit silt, roots,
                                                                                                                                                            dry, loose



                                                                                                                                            SM              Silty SAND), fine to medium grained, grey, low liquid limit silt, dry, medium
                                                                                                                                                            dense
                                                                                                                                            SC              Clayey SAND, fine to medium grained, orange, red brown, low to medium
                                                                                                                                                            plasticity clay, dry to moist, medium dense
                                                                                                                                                                                                                                                       Bulk DS
                                                                                                                                                                                                                                                      CBR=19.0%
                                                                                                             101.5   0.5
                                                                                           Not Encountered




                                                                                                             101.0   1.0




                                                                                                                                                            Test Pit TP09 terminated at 1.3m



                                                                                                             100.5   1.5
BOREHOLE / TEST PIT 13008 LAKE MACDONALD DVE.GPJ GINT STD AUSTRALIA.GDT 7/11/13




                                                                                                             100.0   2.0




                                                                                                             99.5    2.5




                                                                                                             99.0    3.0

Page 31

                                                                                                                                                                                         Tectonic Geotechnical Pty Ltd                                             TEST PIT NUMBER TP10
                                                                                                                                                                                         40 Glenn Vista Drive                                                                                   PAGE 1 OF 1
                                                                                                                                                                                         Chevallum Qld 4555
                                                                                                                                                                                         Telephone: 0437756711
                                                                                  CLIENT                                      Kalkev Pty Ltd                                                                                   PROJECT NAME            Residential Subdivision
                                                                                  PROJECT NUMBER                                                        13008                                                                  PROJECT LOCATION 55 Lake MacDonald Drive, Cooroy

                                                                                  DATE STARTED                                            17/10/13                                 COMPLETED           17/10/13              R.L. SURFACE          101                          DATUM   m AHD
                                                                                  EXCAVATION CONTRACTOR                                                                     Roberts Bros                                     EASTING        491533                              NORTHING    7079169
                                                                                  EQUIPMENT                                         8t excavator                                                                             TEST PIT LOCATION                Refer site plan
                                                                                  TEST PIT SIZE                                          600mm                                                                               LOGGED BY          DJQ                             CHECKED BY     ACD
                                                                                  NOTES                                      RL estimated from site plan contours; co-ordinates taken from hand held GPS
                                                                                                                                                         Classification
                                                                                                                                          Graphic Log




                                                                                                                                                                                                                                                                    Samples
                                                                                                                                                                                                                                                                                    DCP Test (Blows/100 mm) /
                                                                                                                                                                                                        Material Description                                         Tests
                                                                                  Method




                                                                                                                                                         Symbol




                                                                                                                                                                                                                                                                                     Additional Observations
                                                                                           Water




                                                                                                                                                                                                                                                                    Remarks
                                                                                                                           RL Depth
                                                                                                                           (m) (m)
                                                                                  E




                                                                                                                                                          SM              Silty SAND (TOPSOIL), fine to medium grained, grey, low liquid limit silt, roots,
                                                                                                                                                                          dry, loose to medium dense



                                                                                                                                                          SC              Silty Clayey SAND, fine to medium grained, grey, brown, low plasticity fines,
                                                                                                                                                                          trace fine to coarse size gravel, dry, medium dense
                                                                                                                                                          SC              Clayey SAND, fine to medium grained, grey, yellow brown, medium plasticity
                                                                                                                                                                          fines, trace fine to coarse size gravel, moist, medium dense


                                                                                                                           100.5   0.5




                                                                                                                                                           CI             Sandy CLAY, medium plasticity, grey, yellow and red brown, fine to medium
                                                                                                                                                                          grained sand, moist, stiff
                                                                                           Groundwater seepage from 1.4m




                                                                                                                           100.0   1.0




                                                                                                                                                           CI             becoming pale grey, red brown




                                                                                                                           99.5    1.5
BOREHOLE / TEST PIT 13008 LAKE MACDONALD DVE.GPJ GINT STD AUSTRALIA.GDT 7/11/13




                                                                                                                           99.0    2.0




                                                                                                                                                                          Depth reach limit of excavator
                                                                                                                                                                          Test Pit TP10 terminated at 2.2m




                                                                                                                           98.5    2.5




                                                                                                                           98.0    3.0

Page 32

                                                                                                                                                                           Tectonic Geotechnical Pty Ltd                                             TEST PIT NUMBER TP11
                                                                                                                                                                           40 Glenn Vista Drive                                                                                   PAGE 1 OF 1
                                                                                                                                                                           Chevallum Qld 4555
                                                                                                                                                                           Telephone: 0437756711
                                                                                  CLIENT                        Kalkev Pty Ltd                                                                                   PROJECT NAME            Residential Subdivision
                                                                                  PROJECT NUMBER                                          13008                                                                  PROJECT LOCATION 55 Lake MacDonald Drive, Cooroy

                                                                                  DATE STARTED                              17/10/13                                 COMPLETED           17/10/13              R.L. SURFACE          100.5                        DATUM   m AHD
                                                                                  EXCAVATION CONTRACTOR                                                       Roberts Bros                                     EASTING        491475                              NORTHING    7079163
                                                                                  EQUIPMENT                           8t excavator                                                                             TEST PIT LOCATION                Refer site plan
                                                                                  TEST PIT SIZE                            600mm                                                                               LOGGED BY          DJQ                             CHECKED BY     ACD
                                                                                  NOTES                        RL estimated from site plan contours; co-ordinates taken from hand held GPS
                                                                                                                                           Classification
                                                                                                                            Graphic Log




                                                                                                                                                                                                                                                      Samples
                                                                                                                                                                                                                                                                      DCP Test (Blows/100 mm) /
                                                                                                                                                                                          Material Description                                         Tests
                                                                                  Method




                                                                                                                                           Symbol




                                                                                                                                                                                                                                                                       Additional Observations
                                                                                           Water




                                                                                                                                                                                                                                                      Remarks
                                                                                                             RL Depth
                                                                                                             (m) (m)
                                                                                  E




                                                                                                                                            SM              Silty SAND (TOPSOIL), fine to medium grained, grey, low liquid limit silt, roots,
                                                                                                                                                            wet, very loose
                                                                                           Not Encountered




                                                                                                                                             CI             Sandy CLAY, medium plasticity, grey, brown, fine to medium grained sand,
                                                                                                                                                            trace fine size gravel, moist, stiff




                                                                                                             100.0   0.5
                                                                                                                                                            Test Pit TP11 terminated at 0.5m




                                                                                                             99.5    1.0




                                                                                                             99.0    1.5
BOREHOLE / TEST PIT 13008 LAKE MACDONALD DVE.GPJ GINT STD AUSTRALIA.GDT 7/11/13




                                                                                                             98.5    2.0




                                                                                                             98.0    2.5




                                                                                                             97.5    3.0

Page 33

                                                                                                                                                                           Tectonic Geotechnical Pty Ltd                                             TEST PIT NUMBER TP12
                                                                                                                                                                           40 Glenn Vista Drive                                                                                   PAGE 1 OF 1
                                                                                                                                                                           Chevallum Qld 4555
                                                                                                                                                                           Telephone: 0437756711
                                                                                  CLIENT                        Kalkev Pty Ltd                                                                                   PROJECT NAME             Residential Subdivision
                                                                                  PROJECT NUMBER                                          13008                                                                  PROJECT LOCATION 55 Lake MacDonald Drive, Cooroy

                                                                                  DATE STARTED                              17/10/13                                 COMPLETED           17/10/13              R.L. SURFACE          100.5                        DATUM   m AHD
                                                                                  EXCAVATION CONTRACTOR                                                       Roberts Bros                                     EASTING        491321                              NORTHING    7079102
                                                                                  EQUIPMENT                           22t excavator                                                                            TEST PIT LOCATION                Refer site plan
                                                                                  TEST PIT SIZE                            600mm                                                                               LOGGED BY          DJQ                             CHECKED BY     ACD
                                                                                  NOTES                        RL estimated from site plan contours; co-ordinates taken from hand held GPS
                                                                                                                                           Classification
                                                                                                                            Graphic Log




                                                                                                                                                                                                                                                      Samples
                                                                                                                                                                                                                                                                      DCP Test (Blows/100 mm) /
                                                                                                                                                                                          Material Description                                         Tests
                                                                                  Method




                                                                                                                                           Symbol




                                                                                                                                                                                                                                                                       Additional Observations
                                                                                           Water




                                                                                                                                                                                                                                                      Remarks
                                                                                                             RL Depth
                                                                                                             (m) (m)
                                                                                  E




                                                                                                                                            SM              Silty SAND (TOPSOIL), fine to medium grained, grey, low liquid limit silt, roots,
                                                                                                                                                            logs, moist, medium dense



                                                                                                                                            SC              Clayey SAND, fine to medium grained, orange, grey, low plasticity clay, dry to
                                                                                                                                                            moist, loose to medium dense
                                                                                           Not Encountered




                                                                                                             100.0   0.5
                                                                                                                                            CH              Silty CLAY, high plasticity, pale grey, orange, some fine to medium grained
                                                                                                                                                            sand, moist, stiff




                                                                                                             99.5    1.0
                                                                                                                                                            Test Pit TP12 terminated at 1m




                                                                                                             99.0    1.5
BOREHOLE / TEST PIT 13008 LAKE MACDONALD DVE.GPJ GINT STD AUSTRALIA.GDT 7/11/13




                                                                                                             98.5    2.0




                                                                                                             98.0    2.5




                                                                                                             97.5    3.0

Page 34

                                                                                                                                                                           Tectonic Geotechnical Pty Ltd                                             TEST PIT NUMBER TP13
                                                                                                                                                                           40 Glenn Vista Drive                                                                                   PAGE 1 OF 1
                                                                                                                                                                           Chevallum Qld 4555
                                                                                                                                                                           Telephone: 0437756711
                                                                                  CLIENT                        Kalkev Pty Ltd                                                                                   PROJECT NAME            Residential Subdivision
                                                                                  PROJECT NUMBER                                          13008                                                                  PROJECT LOCATION 55 Lake MacDonald Drive, Cooroy

                                                                                  DATE STARTED                              17/10/13                                 COMPLETED           17/10/13              R.L. SURFACE          100.5                        DATUM   m AHD
                                                                                  EXCAVATION CONTRACTOR                                                       Roberts Bros                                     EASTING        491323                              NORTHING    7079132
                                                                                  EQUIPMENT                           22t excavator                                                                            TEST PIT LOCATION                Refer site plan
                                                                                  TEST PIT SIZE                            600mm                                                                               LOGGED BY          DJQ                             CHECKED BY     ACD
                                                                                  NOTES                        RL estimated from site plan contours; co-ordinates taken from hand held GPS
                                                                                                                                           Classification
                                                                                                                            Graphic Log




                                                                                                                                                                                                                                                      Samples
                                                                                                                                                                                                                                                                      DCP Test (Blows/100 mm) /
                                                                                                                                                                                          Material Description                                         Tests
                                                                                  Method




                                                                                                                                           Symbol




                                                                                                                                                                                                                                                                       Additional Observations
                                                                                           Water




                                                                                                                                                                                                                                                      Remarks
                                                                                                             RL Depth
                                                                                                             (m) (m)
                                                                                  E




                                                                                                                                            SM              Silty SAND (TOPSOIL), fine to medium grained, grey, low liquid limit silt, roots,
                                                                                                                                                            dry to moist, some small logs, medium dense
                                                                                           Not Encountered




                                                                                                                                            SC              Clayey SAND, fine to medium grained, orange, grey, low plasticity clay, moist,
                                                                                                                                                            loose to medium dense
                                                                                                             100.0   0.5




                                                                                                                                             CI             Sandy CLAY, medium plasticity, pale grey, orange, fine to medium grained
                                                                                                                                                            sand, moist, stiff
                                                                                                             99.5    1.0


                                                                                                                                                            Test Pit TP13 terminated at 1.1m




                                                                                                             99.0    1.5
BOREHOLE / TEST PIT 13008 LAKE MACDONALD DVE.GPJ GINT STD AUSTRALIA.GDT 7/11/13




                                                                                                             98.5    2.0




                                                                                                             98.0    2.5




                                                                                                             97.5    3.0

Page 35

                                                                                                                                                                                         Tectonic Geotechnical Pty Ltd                                        BOREHOLE NUMBER HA1
                                                                                                                                                                                         40 Glenn Vista Drive                                                                                 PAGE 1 OF 1
                                                                                                                                                                                         Chevallum Qld 4555
                                                                                                                                                                                         Telephone: 0437756711
                                                                                  CLIENT                                      Kalkev Pty Ltd                                                                                  PROJECT NAME            Residential Subdivision
                                                                                  PROJECT NUMBER                                                      13008                                                                   PROJECT LOCATION 55 Lake MacDonald Drive, Cooroy

                                                                                  DATE STARTED                                          28/11/13                                   COMPLETED          28/11/13             R.L. SURFACE          100.0                   DATUM        m AHD
                                                                                  DRILLING CONTRACTOR                                                                   Tectonic                                           EASTING        491304                         NORTHING         7079122
                                                                                  EQUIPMENT                                        Hand auger                                                                              HOLE LOCATION             Refer site plan
                                                                                  HOLE SIZE                                       100mm                                                                                    LOGGED BY           DJQ                       CHECKED BY          ACD
                                                                                  NOTES                                      RL estimated from site plan contours; co-ordinates taken from hand held GPS
                                                                                                                                                       Classification
                                                                                                                                        Graphic Log




                                                                                                                                                                                                                                                               Samples
                                                                                                                                                                                                                                                                                  DCP Test (Blows/100 mm) /
                                                                                                                                                                                                       Material Description                                     Tests
                                                                                  Method




                                                                                                                                                       Symbol




                                                                                                                                                                                                                                                                                   Additional Observations
                                                                                           Water




                                                                                                                                                                                                                                                               Remarks
                                                                                                                           RL Depth
                                                                                                                           (m) (m)
                                                                                  HA




                                                                                                                                                        SM               Silty SAND (TOPSOIL), fine to medium grained, dark grey, low liquid limit silt,                    0
                                                                                           Groundwater seepage from 0.2m




                                                                                                                                                                         roots, wet, very loose
                                                                                                                                                        CH               Silty CLAY, high plasticity, pale grey, yellow, trace fine to medium grained sand,                 0
                                                                                                                                                                         wet, soft
                                                                                                                                                                                                                                                                            0

                                                                                                                                                                                                                                                                            0

                                                                                                                                                                                                                                                                            0
                                                                                                                           99.5   0.5
                                                                                                                                                                         becoming firm                                                                                      1

                                                                                                                                                                                                                                                                            2

                                                                                                                                                                         DCP test indicates stiff at 0.8m                                                                   1
                                                                                                                                                                         Borehole HA1 terminated at 0.7m
                                                                                                                                                                                                                                                                            2

                                                                                                                                                                                                                                                                            4
                                                                                                                           99.0   1.0
                                                                                                                                                                                                                                                                            >10




                                                                                                                           98.5   1.5
BOREHOLE / TEST PIT 13008 LAKE MACDONALD DVE.GPJ GINT STD AUSTRALIA.GDT 1/12/13




                                                                                                                           98.0   2.0




                                                                                                                           97.5   2.5




                                                                                                                           97.0   3.0

Page 36

                                                                                                                                                                                         Tectonic Geotechnical Pty Ltd                                        BOREHOLE NUMBER HA2
                                                                                                                                                                                         40 Glenn Vista Drive                                                                               PAGE 1 OF 1
                                                                                                                                                                                         Chevallum Qld 4555
                                                                                                                                                                                         Telephone: 0437756711
                                                                                  CLIENT                                      Kalkev Pty Ltd                                                                                  PROJECT NAME            Residential Subdivision
                                                                                  PROJECT NUMBER                                                      13008                                                                   PROJECT LOCATION 55 Lake MacDonald Drive, Cooroy

                                                                                  DATE STARTED                                          28/11/13                                   COMPLETED          28/11/13             R.L. SURFACE          100.0                   DATUM      m AHD
                                                                                  DRILLING CONTRACTOR                                                                   Tectonic                                           EASTING        491285                         NORTHING       7079086
                                                                                  EQUIPMENT                                        Hand auger                                                                              HOLE LOCATION             Refer site plan
                                                                                  HOLE SIZE                                       100mm                                                                                    LOGGED BY           DJQ                       CHECKED BY        ACD
                                                                                  NOTES                                      RL estimated from site plan contours; co-ordinates taken from hand held GPS
                                                                                                                                                       Classification
                                                                                                                                        Graphic Log




                                                                                                                                                                                                                                                               Samples
                                                                                                                                                                                                                                                                                DCP Test (Blows/100 mm) /
                                                                                                                                                                                                       Material Description                                     Tests
                                                                                  Method




                                                                                                                                                       Symbol




                                                                                                                                                                                                                                                                                 Additional Observations
                                                                                           Water




                                                                                                                                                                                                                                                               Remarks
                                                                                                                           RL Depth
                                                                                                                           (m) (m)
                                                                                  HA




                                                                                                                                                        SM               Silty SAND (TOPSOIL), fine to medium grained, dark grey, low liquid limit silt,                    0
                                                                                           Groundwater seepage from 0.2m




                                                                                                                                                                         roots, wet, very loose
                                                                                                                                                                                                                                                                            0

                                                                                                                                                        CH               Silty CLAY, high plasticity, pale grey, yellow, trace fine to medium grained sand,                 0
                                                                                                                                                                         wet, very soft
                                                                                                                                                                                                                                                                            0

                                                                                                                                                                                                                                                                            0
                                                                                                                           99.5   0.5
                                                                                                                                                                                                                                                                            0

                                                                                                                                                                         becoming firm to stiff                                                                             2

                                                                                                                                                                         DCP indicates becoming stiff at 0.8m                                                               1
                                                                                                                                                                         Borehole HA2 terminated at 0.7m
                                                                                                                                                                                                                                                                            1

                                                                                                                                                                                                                                                                            1
                                                                                                                           99.0   1.0
                                                                                                                                                                                                                                                                            2

                                                                                                                                                                                                                                                                            2

                                                                                                                                                                                                                                                                            4

                                                                                                                                                                                                                                                                            6

                                                                                                                                                                                                                                                                            7
                                                                                                                           98.5   1.5
BOREHOLE / TEST PIT 13008 LAKE MACDONALD DVE.GPJ GINT STD AUSTRALIA.GDT 1/12/13




                                                                                                                           98.0   2.0




                                                                                                                           97.5   2.5




                                                                                                                           97.0   3.0

Page 37

                                                                                            TERMS USED ON LOGS


DRILLING/EXCAVATION METHOD
AD*        Auger Drilling          RD      Rotary Blade or Drag bit            NQ         Diamond Core - 47 mm
*V         V-Bit                   RT      Rotary Tri-cone bit                 NMLC       Diamond Core - 52 mm
*T         TC-Bit                  RA      Rotary Air                          HQ         Diamond Core - 63 mm
HA         Hand Auger                                                          HMLC       Diamond Core – 63mm
ADH        Hollow Auger                                                        BH         Tractor Mounted Backhoe
HA         Hand Auger                                                          EX         Tracked Hydraulic Excavator



WATER
GROUNDWATER NOT             The observation of groundwater, whether present or not, was not possible due to drilling water,
OBSERVED                    surface seepage or cave in of the borehole/test pit.
GROUNDWATER NOT            The borehole/test pit was dry soon after excavation. However, groundwater could be present in
ENCOUNTERED                less permeable strata. Inflow may have been observed had the borehole/test pit been left open
                           for a longer period.

SAMPLING AND TESTING
SPT                Standard Penetration Test to AS1289.6.3.1-2004
5,4,10 N=14        5,4,10 = Blows per 150mm. N = Blows per 300mm penetration following 150mm seating
30/65mm            Where practical refusal occurs, the blows and penetration for that interval are reported
RW                 Penetration occurred under the rod weight only
HW                 Penetration occurred under the hammer and rod weight only
HB                 Hammer double bouncing on anvil
DS                 Disturbed sample
BDS                Bulk disturbed sample
FV                 Field vane shear test expressed as uncorrected shear strength (sv = peak value, sr = residual value)
PP                 Pocket penetrometer test expressed as instrument reading in kPa
U50                Thin walled tube sample - number indicates nominal sample diameter in millimetres
DCP                Dynamic cone penetration test
CPT                Electronic cone penetration test
CPTu               Electronic cone penetration test with pore pressure (u) measurement



                                                                                                                       Rev0
                                                                                                                 October 2013

Page 38

                                                                         METHOD OF SOIL DESCRIPTION
                                                                                      USED ON LOGS
CLASSIFICATION AND INFERRED STRATIGRAPHY
Soil and rock is classified and described in borehole and test pit logs using the preferred method given in AS1726 – 1993,
(Amdt1 – 1994 and Amdt2 – 1994), Appendix A.The material properties are assessed in the field by visual/tactile methods.
Particle Size                                                                      Plasticity Properties

Major Division Sub Division            Particle Size40
          BOULDERS                     > 200 mm
          COBBLES                     63 to 200 mm
                   Coarse              20 to 63 mm
 GRAVEL           Medium               6.0 to 20 mm
                       Fine           2.0 to 6.0 mm
                   Coarse             0.6 to 2.0 mm
                                                         C
  SAND            Medium              0.2 to 0.6 mm
                   Fine               0.075 to 0.2 mm
                SILT                   0.002 to 0.075
             CLAY                      < 0.002 mm mm



MOISTURE CONDITION                                                AS1726 - 1993
Symbol     Term    Description
   D              Dry         Sands and gravels are free flowing. Clays & Silts may be brittle or friable and powdery.
   M             Moist        Soils are darker than in the dry condition & may feel cool. Sands and gravels tend to cohere.
   W              Wet         Soils exude free water. Sands and gravels tend to cohere.

CONSISTENCY AND DENSITY                                          AS1726 - 1993
 Symbol     Term        Undrained Shear                        Symbol        Term             Density Index %        SPT “N” #
                           Strength
    VS           Very Soft             0 to 12 kPa               VL         Very Loose          Less than 15              0 to 4
    S              Soft               12 to 25 kPa                L            Loose               15 to 35              4 to 10
    F              Firm               25 to 50 kPa               MD       Medium Dense             35 to 65          10 to 30
    St             Stiff              50 to 100 kPa               D            Dense               65 to 85          30 to 50
    VSt          Very Stiff          100 to 200 kPa              VD         Very Dense            Above 85           Above 50
     H            Hard             Above 200 kPa
In the absence of test results, consistency and density may be assessed from correlations with the observed behaviour of
the material.
# SPT correlations are not stated in AS1726 – 1993, and may be subject to corrections for overburden pressure and
equipment type.




                                                                                                                                           Rev0
                                                                                                                                   October 2013

Page 39

                            55 LAKE MACDONALD DRIVE, COOROY




APPENDIX C
Laboratory Test Results




1 December 2013
Report No. 13008-001-Rev1

Page 40

                                      Quality of Materials Report
Client:                   Tectonic Geotechnical Pty Ltd                                           Report Number:             G13056 - 5/1

Client Address:           PO Box 899 Buderim QLD 4556
Job Number:               G13056                                                                  Report Date:               25/10/2013

Project:                  Laboratory Testing Project No:13008                                     Order Number:                    -

Location                  55 Lake MacDonald Drive , Cooroy                                                          Page 1 of 1
Lab No:                   97844                                                                                 Sample Location
Date Sampled:             17/10/2013                                                               Test Pit 1
Date Tested:              23/10/2013                                                               Depth 0.2 - 0.3m
Sampled By:               Client                                                                   Supplied 21/10/13
Sample Method:            N/A
Material Source:          Site                                                                    Spec Description:      -

For Use As:               -                                                                       Lot Number:            -
Remarks:                  -                                                                       Spec Number:           -
                                                         A.S. Sieve Sizes         Specification           Percent            Specification
                                                                                   Minimum                Passing             Maximum
           Test Method:            AS1289.3.6.1
                                                                   75.00 mm
                                                                   53.00 mm
                                                                   37.50 mm
                                                                   26.50 mm
                                                                   19.00 mm
                                                                    13.2 mm
                                                                    9.50 mm
                                                                     6.7 mm
                                                                    4.75 mm
                                                                    2.36 mm
                                                                    1.18 mm
                                                                   0.600 mm
                                                                   0.425 mm
                                                                   0.300 mm
                                                                   0.150 mm
                                                                   0.075 mm                                    46


Atterberg Tests                                              Test Method          Specification           Result             Specification
                                                                                   Minimum                                    Maximum
Liquid Limit (%)                                            AS1289.3.1.2                                       23
Plastic Limit (%)                                           AS1289.3.2.1                                       17
Plasticity Index                                            AS1289.3.3.1                                       6
Linear Shrinkage (%)                                        AS1289.3.4.1                                   4.5




                                                                                         Approved Signatory              Form Number

                           This document is issued in accordance with NATA's
                          accreditation requirements. Accredited for compliance
                                           with ISO/IEC 17025.                                                            REP AQUAL-1-7
                                                                                            Mel Burnett
                                                                                         NATA Accred No:1551

Page 41

                                      Quality of Materials Report
Client:                   Tectonic Geotechnical Pty Ltd                                           Report Number:             G13056 - 6/1

Client Address:           PO Box 899 Buderim QLD 4556
Job Number:               G13056                                                                  Report Date:               25/10/2013

Project:                  Laboratory Testing Project No:13008                                     Order Number:                    -

Location                  55 Lake MacDonald Drive , Cooroy                                                          Page 1 of 1
Lab No:                   97845                                                                                 Sample Location
Date Sampled:             17/10/2013                                                               Test Pit 2
Date Tested:              23/10/2013                                                               Depth 0.3 - 0.5m
Sampled By:               Client                                                                   Supplied 21/10/13
Sample Method:            N/A
Material Source:          Site                                                                    Spec Description:      -

For Use As:               -                                                                       Lot Number:            -
Remarks:                  -                                                                       Spec Number:           -
                                                         A.S. Sieve Sizes         Specification           Percent            Specification
                                                                                   Minimum                Passing             Maximum
           Test Method:            AS1289.3.6.1
                                                                   75.00 mm
                                                                   53.00 mm
                                                                   37.50 mm
                                                                   26.50 mm
                                                                   19.00 mm
                                                                    13.2 mm
                                                                    9.50 mm
                                                                     6.7 mm
                                                                    4.75 mm
                                                                    2.36 mm
                                                                    1.18 mm
                                                                   0.600 mm
                                                                   0.425 mm
                                                                   0.300 mm
                                                                   0.150 mm
                                                                   0.075 mm                                    46


Atterberg Tests                                              Test Method          Specification           Result             Specification
                                                                                   Minimum                                    Maximum
Liquid Limit (%)                                            AS1289.3.1.2                                       29
Plastic Limit (%)                                           AS1289.3.2.1                                       16
Plasticity Index                                            AS1289.3.3.1                                       13
Linear Shrinkage (%)                                        AS1289.3.4.1                                   10.0




                                                                                         Approved Signatory              Form Number

                           This document is issued in accordance with NATA's
                          accreditation requirements. Accredited for compliance
                                           with ISO/IEC 17025.                                                            REP AQUAL-1-7
                                                                                            Mel Burnett
                                                                                         NATA Accred No:1551

Page 42

                                              California Bearing Ratio Report (1 Point)
Client:                 Tectonic Geotechnical Pty Ltd                                                                                Report Number:              G13056 - 7/1
Client address:         PO Box 899 Buderim QLD 4556
Job Number:             G13056                                                                                                       Report Date:                28/10/2013
Project:                Laboratory Testing Project No:13008                                                                          Order Number:
Location                55 Lake MacDonald Drive , Cooroy                                                                                             Page 1 of 1
Lab No:                 97846                                                                                                        Sample Location
Date Sampled:           17/10/2013                                                                                                   Test Pit 7
Date Tested:            28/10/2013                                                                                                   Depth 0.3 - 0.7m
Sampled By:             Client                                                                                                       Supplied 21/10/13
Sample Method:          N/A
Material Source:        Site                                                                                                         Test Method :          AS1289.6.1.1
For Use As:             -                                                                                                            Lot Number:            -
Remarks:                -                                                                                                            Item Number :          -




    Maximum Dry Density - MDD (t/m³) :                       1.902                            Dry Density after Soak (t/m³) :                          1.888

   Optimum Moisture Content - OMC (%) :                      12.7                            Moisture Content after Soak (%) :                          11.9

               Compactive Effort :                         Standard                            Density Ratio after Soak (%) :                              99
     Nominated % Maximum Dry Density
               Compaction :                                   100                             Field Moisture Content (%) :                                 9.5
  Nominated % Optimum Moisture Content                                                  Moisture Content (Top) after Penetration
              Compaction :                                    100                                         (%) :                                             -
                                                                                        Moisture Content (Total) after Penetration
  Achieved Dry Density before Soak (t/m³) :                  1.906                                        (%) :                                             -
Achieved Percentage of Maximum Dry Density
                   (%) :                                      100                                    CBR 2.5mm (%) :                                       17

      Achieved Moisture Content (%) :                        12.5                                    CBR 5.0mm (%) :                                       16
  Achieved Percentage of Optimum Moisture
               Content (%) :                                   98                           Minimum Specified CBR Value (%) :                               -
 Test Condition (Soaked/Unsoaked) / Soaking
                Period (Days) :                         Soaked / 4 days
                                                                                                   CBR Value (%) :                                      17.0

           Swell (%) / Surcharge (kg):                    1.0 / 4.5 kg

Soil Description :                                        Silty Clayey Sand(SC)-fine to medium grained,yellow brown,low plasticity fines

                                                                                                                                      Approved Signatory    Form Number

                                                                This document is issued in accordance with NATA's accreditation
                                                                requirements. Accredited for compliance with ISO/IEC 17025.                                 REP ACBR_1_3-3
                                                                                                                                     Mel Burnett
                                                                                                                                     NATA Accred No:1551

Page 43

                                              California Bearing Ratio Report (1 Point)
Client:                 Tectonic Geotechnical Pty Ltd                                                                                Report Number:             G13056 - 8/1
Client address:         PO Box 899 Buderim QLD 4556
Job Number:             G13056                                                                                                       Report Date:               28/10/2013
Project:                Laboratory Testing Project No:13008                                                                          Order Number:
Location                55 Lake MacDonald Drive , Cooroy                                                                                             Page 1 of 1
Lab No:                 97847                                                                                                        Sample Location
Date Sampled:           17/10/2013                                                                                                   Test Pit 9
Date Tested:            28/10/2013                                                                                                   Depth 0.3 - 0.5m
Sampled By:             Client                                                                                                       Supplied 21/10/13
Sample Method:          N/A
Material Source:        Site                                                                                                         Test Method :          AS1289.6.1.1
For Use As:             -                                                                                                            Lot Number:            -
Remarks:                -                                                                                                            Item Number :          -




    Maximum Dry Density - MDD (t/m³) :                       1.753                            Dry Density after Soak (t/m³) :                          1.753

   Optimum Moisture Content - OMC (%) :                      16.5                            Moisture Content after Soak (%) :                          18.1

               Compactive Effort :                         Standard                            Density Ratio after Soak (%) :                           100
     Nominated % Maximum Dry Density
               Compaction :                                   100                             Field Moisture Content (%) :                              16.1
  Nominated % Optimum Moisture Content                                                  Moisture Content (Top) after Penetration
              Compaction :                                    100                                         (%) :                                            -
                                                                                        Moisture Content (Total) after Penetration
  Achieved Dry Density before Soak (t/m³) :                  1.754                                        (%) :                                            -
Achieved Percentage of Maximum Dry Density
                   (%) :                                      100                                    CBR 2.5mm (%) :                                       19

      Achieved Moisture Content (%) :                        16.4                                    CBR 5.0mm (%) :                                       19
  Achieved Percentage of Optimum Moisture
               Content (%) :                                  99                            Minimum Specified CBR Value (%) :                              -
 Test Condition (Soaked/Unsoaked) / Soaking
                Period (Days) :                         Soaked / 4 days
                                                                                                   CBR Value (%) :                                      19.0

           Swell (%) / Surcharge (kg):                    0.1 / 4.5 kg

Soil Description :                                        Clayey Sand(SC)-fine to medium grained,brown,low to medium plasticity fines

                                                                                                                                      Approved Signatory    Form Number

                                                                This document is issued in accordance with NATA's accreditation
                                                                requirements. Accredited for compliance with ISO/IEC 17025.                                REP ACBR_1_3-3
                                                                                                                                     Mel Burnett
                                                                                                                                     NATA Accred No:1551

Page 44

                            55 LAKE MACDONALD DRIVE, COOROY




APPENDIX D
Report Limitations




1 December 2013
Report No. 13008-001-Rev1

Page 45

                                             REPORT LIMITATIONS

This report has been prepared for the purpose outlined in Tectonic’s proposal and no responsibility is
accepted for the use of this report, in whole or in part, for any other purpose.

The scope of Tectonic’s Services are as described in Tectonic’s proposal, and are subject to restrictions and
limitations. Tectonic did not perform a complete assessment of all possible conditions or circumstances that
may exist at the site referenced in the report. If a service is not expressly indicated, do not assume it has
been provided. If a matter is not addressed, do not assume that any determination has been made by
Tectonic in regards to it.

Conditions may exist which were undetectable given that economic and time constraints limit the practical
extent of geotechnical investigation. Variations in conditions may occur between investigation locations, and
there may be special conditions pertaining to the site which have not been revealed by the investigation and
which have not therefore been taken into account in the report. Where variations exist on site, additional
studies and actions may be required.

Tectonic’s opinions are based upon information that existed at the time that the study was performed. The
passage of time, man-made or natural events, may alter the site conditions. It is understood that the Services
undertaken allowed Tectonic to form an opinion of the actual conditions of the site at the time the site was
visited and cannot be used to assess the effect of any subsequent changes in the quality of the site, or its
surroundings, or any laws or regulations.

Any assessments made in this report are based on the conditions indicated from published sources and the
findings of the investigation described. Actual subsurface conditions may differ from those indicated in the
report (e.g. between boreholes or test pits). No warranty is included, either express or implied, that the
actual conditions will conform exactly to the assessments contained in this report.

Where data supplied by the client or other external sources, including previous site investigation data, have
been used, it has been assumed that the information is correct unless otherwise stated. No responsibility is
accepted by Tectonic for incomplete or inaccurate data supplied by others.

This report is provided for the sole use by the Client and its professional advisers. No responsibility
whatsoever for the contents of this report will be accepted to any person other than the Client. Any use which
a third party makes of this report, or any reliance on or decisions to be made based on it, is the responsibility
of such third parties. Tectonic accepts no responsibility for damages, if any, suffered by any third party as a
result of decisions made or actions based on this report.