Geotechnical Report Dec 2013 Revision 1

Attached to the e-mail REC13/0146 - Response to Information Request - Email 2.

of 45

Page text shows just the words. Original shows the document exactly as it was published.

                                  55 LAKE MACDONALD DRIVE, COOROY


where DCP blows >1 per 100mm were also recorded at depths of about 0.5m BGL. Therefore, at HA1 and
HA2, the silty clay may actually be stiff from 0.5m BGL (DCP testing in wet silty clay can give low values that
underestimate the strength of the material).

Groundwater seepage was only encountered in test pits TP8 at a depth of 0.3m BGL and at TP10 at a depth
of 1.4m BGL during the investigation. Groundwater was present in boreholes HA1 and HA2 at about 0.2m
BGL. It should be noted that groundwater seepage may occur from more permeable horizons within the soil
following periods of prolonged or heavy rainfall.

Refer to detailed test pit reports and explanatory notes attached in Appendix B.

5.3        Laboratory Test Results
The results of the laboratory testing are presented below in Table 1.
Table 1: Summary of Laboratory Results
 Test Pit No.                                      TP1                  TP2          TP7                 TP9

 Depth (m)                                       0.2-0.3               0.3-0.5      0.3-0.7            0.3-0.5

 Percent fines (%)                                  46                   46

 Liquid Limit (%)                                   23                   29

 Plastic Limit (%)                                  17                   16

 Plasticity index (%)                                6                   13

 Linear Shrinkage (%)                               4.5                 10.0

 CBR (%)                                                                             17.0                19.0

 Field Moisture Content (%)                                                           9.5                18.1

 Optimum Moisture Content (%)                                                        12.7                16.5
Fines Content is the % of clay/silt fraction in the soil profile

The above laboratory test results indicate that the soil tested from TP1 is silty sand, with low liquid limit silt. .
The sample tested from TP2 is clayey sand, with low plasticity clay.




2 December 2013
Report N0. 13008-001-Rev1                                          9
Log in to download the original file

Geotechnical Report Dec 2013 Revision 1.pdf · 3.3 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.