                       WATER SUPPLY AND SEWER NETWORK ANALYSIS
Client: Noosa Shire Council                        Location: 62 Lake Macdonald Drive, Cooroy




            WATER SUPPLY AND SEWER NETWORK ANALYSIS
                                             AT

                              62 LAKE MACDONALD DRIVE, COOROY

                                             FOR

                                    NOOSA SHIRE COUNCIL

                                     DATE: AUGUST 2023
                                    PROJECT NO: 233467
                           REPORT NO: AG/AG/M23-0030RPT ISSUE A




Covey Associates Pty Ltd                 1                                 Project No: 141753
Consulting Engineers                                                         101036Rpt Iss A
Log in to download the original file

Appendix G Water and Sewer Analysis.pdf · 7.9 MB (large file)

The download may take up to a minute.

Full text of the other 30 pages

Page 2

                       WATER SUPPLY AND SEWER NETWORK ANALYSIS
Client: Noosa Shire Council                        Location: 62 Lake Macdonald Drive, Cooroy


                           DOCUMENT ISSUE APPROVAL


Project No:           233467


Title:                Water Supply and Sewer Network Analysis


Client:               Noosa Shire Council


Date:                 August 2023


Issue:                A


Distribution:         Unitywater – One (1) copy
                      Noosa Shire Council – One (1) copy
                      Covey Associates Pty Ltd – One (1) copy



© Copyright Covey Associates Pty Ltd (2023).

This document is the property of Covey Associates Pty Ltd. This document and the information
contained in it are solely for the use of the authorised recipient and this document may not be
used, copies of reproduced in whole or part for any purpose other than that for which it was
supplied by Covey Associates Pty Ltd. Covey Associates Pty Ltd makes no representation,
undertakes no duty and accepts no responsibility to any third party who may use or rely upon this
document or the information contained in it.

COPYRIGHT NOTICE:

This material is the intellectual property and copyright of Covey Associates Pty Ltd.




         Allister Gaffney                                          Shane Rynne
Author: Allister Gaffney                                  Reviewed: Shane Rynne
Senior Water Resource Engineer                            Senior Civil Engineer
BEng (Civil), MEng, RPEQ                                  BEng (Civil), GradDipMunEng,
                                                          MIEAust, RPEQ

Page 3

                       WATER SUPPLY AND SEWER NETWORK ANALYSIS
Client: Noosa Shire Council                        Location: 62 Lake Macdonald Drive, Cooroy


                                        CONTENTS

1.0 INTRODUCTION                                                                          1

2.0 WATER NETWORK ANALYSIS                                                                2

     2.1    Demand                                                                        2

     2.2 Serviceability Requirements                                                      3
    2.2.1 Service Pressure                                                                3
    2.2.2    Fire Flow                                                                    3

     2.3    Scenarios                                                                     3

     2.4    Peak Hour                                                                     3

     2.5    Fire Flow                                                                     4

3.0 SEWER NETWORK ANALYSIS                                                                5

     3.1    Loading                                                                       5

     3.2    Serviceability Requirements                                                   5

     3.3    Scenarios                                                                     5

     3.4 Network Assessment                                                               6
    3.4.1 Pump Station Capacity                                                           7
    3.4.2    Rising Main Velocity                                                         7
    3.4.3    Operational Storage                                                          7
    3.4.4    Emergency Storage                                                            7
    3.4.5    Gravity Sewer Performance                                                    8

4.0 CONCLUSION                                                                            8

5.0 REFERENCES                                                                            9

                                     LIST OF APPENDICES
APPENDIX A        Site Plans
APPENDIX B        Water Results
APPENDIX C        Sewer Data and Results
APPENDIX D        Unitywater’s Service Advice Notice

Page 4

                       WATER SUPPLY AND SEWER NETWORK ANALYSIS
Client: Noosa Shire Council                        Location: 62 Lake Macdonald Drive, Cooroy


1.0 INTRODUCTION
This report demonstrates the findings of a water supply and sewer network analysis undertaken for
the proposed subdivision for residential housing at 62 Lake Macdonald Drive, Cooroy as requested
in the service advice notice (SAN) from Unitywater shown in Appendix D.

Using the InfoWater and InfoSWMM models provided by Unitywater on the 17th July 2023 the
proposed development water and sewer infrastructure was added to the respective models to
determine the impacts of the proposed development on the surrounding water and sewer network.

The site is located at 62 Lake Macdonald Drive, Cooroy. The real property description is Lot 105
SP118458. The total site area is approximately 3.54 hectares. The site currently consists of a
storage shed, vegetation and open space. The proposed development application is for a lot
reconfiguration for residential purposes. A site locality plan is shown in Figure 1.

The development is located within water DMA zone COORO (“the DMA”). The development
sewerage will drain to the existing sewer pump station (SPS) CRY020 before discharging to the
Cooroy Sewage Treatment plant (STP-CRY001). The scope of the sewer analysis is from the
development connection point to pump station CRY020.




                                   Figure 1 – Site Locality Plan




Covey Associates Pty Ltd                    1                                  Project No: 233467
Consulting Engineers                                                            M23-003Rpt Iss A

Page 5

                       WATER SUPPLY AND SEWER NETWORK ANALYSIS
Client: Noosa Shire Council                        Location: 62 Lake Macdonald Drive, Cooroy



2.0 WATER NETWORK ANALYSIS
There is one connection point proposed for the development off the existing DN250 DICL main on
Dianella Ct. A new DN150 PVC-O water mains is proposed generally alongside the proposed road
within the development. Refer to the Site plans in Appendix A for the development layout.


2.1 Demand

For this assessment, the equivalent persons (EP) was determined based on 100 units within the
development. The development proposes 90 x one and two-bedroom units and 10 x three-
bedroom units distributed equally over the three lots. It is assumed that these units will have a
maximum of two storeys.

The assumptions used to calculate the total EP were as follows (based on Unitywater’s Net Serv
Plan (2019):
   • 2.64 EP per detached dwelling or three-bedroom unit
   • 1.77 EP per one to two-bedroom unit

Based on these assumptions, the total demand for the development was 186 EP.

The following values were adopted from the South East Queensland Water Supply and Sewerage
Design and Construction Code (SEQ WS&S D&C Code, 2020) to calculate the water demand:

•   Average day,             AD = 230 L/EP/day
•   Non-revenue water,       NRW = 30 L/ EP/day
•   Peak day,                PD = 2 x AD
•   Peak hour,               PH = 4 x AD

The water demand estimated for the proposed development was based on the estimated EP as
shown in Table 1.
                              Table 1 – Development Water Demand
                                                Water Demand
                          Design
                                        L/EP/day               L/s
                         Parameter
                            AD            230                 0.49

                           NRW             30                 0.06

                            PD            490                 1.05

                            PH            950                 2.04

The calculated demand for the proposed development was distributed among the proposed nodes
in the InfoWater model. The diurnal water supply demand patterns used for each water demand
node in the InfoWater model was medium density residential (MDR) which was provided together
with the model supplied by Unitywater.




Covey Associates Pty Ltd                   2                                   Project No: 233467
Consulting Engineers                                                           M23-0030Rpt Iss A

Page 6

                       WATER SUPPLY AND SEWER NETWORK ANALYSIS
Client: Noosa Shire Council                        Location: 62 Lake Macdonald Drive, Cooroy

2.2 Serviceability Requirements

2.2.1 Service Pressure

The services pressure requirements that were adopted in accordance with SEQ WS&S D&C Code
(2020) included:

•   Minimum 22m residual pressure during peak hour demand; and,
•   Maximum 55m service pressure.

2.2.2 Fire Flow

The fire flow requirements adopted in accordance with SEQ WS&S D&C Code (2020) are as
follows:

•   15 L/s for 2 hours with a 2/3 peak hour (PH) background demand for residential;
•   30 L/s for 4 hours with a 2/3 peak hour (PH) background demand for commercial/ industrial;
•   12m minimum pressure at flowing hydrant; and,
•   6m minimum pressure elsewhere in the system.


2.3 Scenarios

The scenarios that were used in the assessment of the water supply network were based on the
Unitywater InfoWater model supplied and are listed in Table 2. The 2036 scenarios represent the
ultimate 20-year design horizon as Unitywater did not provide a 2041 scenario. The full
development loading was added to both the 2021 and 2036 post-development scenarios.



                                 Table 2 – Water Modelling Scenarios
                           Scenario
                                                             Model Alias
                  Year     Development Stage

                  2021     Pre-development        2021_Committed_Network_2021PD

                  2021     Post-development       2021_CN_2021PD_Covey

                  2036     Pre-development        2036_Committed_Network_2036PD

                  2036     Post-development       2036_CN_2036PD_Covey


2.4 Peak Hour

The service pressure results for the critical nodes during peak hour are shown in Table 3 and in
Appendix B. The table demonstrates the lowest pressure results for the most critical node in the
development and the most critical node in the existing network during peak hour (5:30pm).
UW1686 is in the highest location in the development. NOON122 demonstrated the lowest
pressure in the existing DMA and is located along Kensington Dr.

The results demonstrated that in all pre-development scenarios there are 31 nodes that did not
meet the minimum residual pressure of 22m. These nodes are shown in Appendix B. Further, in
the post-development scenarios, no additional nodes fell below the minimum residual pressure.
Therefore, the proposed development has a non-worsening effect on the peak hour pressure. It is
recommended that Unitywater review the existing failing nodes. In all modelled scenarios within

Covey Associates Pty Ltd                      3                                   Project No: 233467
Consulting Engineers                                                              M23-0030Rpt Iss A

Page 7

                       WATER SUPPLY AND SEWER NETWORK ANALYSIS
Client: Noosa Shire Council                        Location: 62 Lake Macdonald Drive, Cooroy

the DMA, excluding the failing nodes, the service pressure is above 22m and is therefore
considered to be acceptable.


                            Table 3 –Peak Hour Pressure Analysis Results
                                                        Pressure (m)
               Year        Node            Pre-            Post-
                                                                         % Difference
                                       development      development
               2021     UW1686               -              31.5              -

                        NOON122            <0               <0                -

               2036     UW1686               -              30.7              -

                        NOON122            <0               <0                -


2.5 Fire Flow
For the purpose of the model, each node in the development was assigned a 15 L/s fire flow
demand for residential. Using the assigned fire flow demand for the proposed development nodes
and the existing fire flow demands assigned by Unitywater to the existing network a fire flow event
was simulated for each fire node individually. All fire nodes in the model were analysed to
determine their minimum residual pressure during a fire flow event at that hydrant. The worst case
2/3 PH background demand occurred at approximately 4:30pm. As such this was the start time for
the fire flow analysis.

In both the pre-development and post-development scenarios several nodes in the existing
network had residual pressure below 12m during a fire flow event. These nodes have been
included in Appendix B. It is noted that the residual pressure at these nodes was not noticeably
worsened in the post-development cases and therefore the addition of the proposed development
did not have a worsening effect on the network with regards to fire flow.

In all scenarios, except for the failing nodes, all hydrants maintained adequate pressure during a
fire flow analysis. The results for the most critical node (UW1686) in the proposed development
and the most critical node in the DMA (NTHWJ002542) are shown in Table 4 and Appendix B.


                                  Table 4 – Fire Flow Analysis Results

                                                      Residual Pressure (m)
             Year          Node              Pre-            Post-
                                                                           % Difference
                                         development      development
             2021       UW1686                   -           28.00                -

                      NTHWJ002542                <0            <0                 -

             2036       UW1686                   -           27.83                -

                      NTHWJ002542                <0            <0                 -




Covey Associates Pty Ltd                         4                                    Project No: 233467
Consulting Engineers                                                                  M23-0030Rpt Iss A

Page 8

                       WATER SUPPLY AND SEWER NETWORK ANALYSIS
Client: Noosa Shire Council                        Location: 62 Lake Macdonald Drive, Cooroy


3.0 SEWER NETWORK ANALYSIS
3.1 Loading

The following values were adopted based on SEQ WS&S D&C Code – Design Criteria (2020) to
calculate the sewer design loading:

   •   Average dry weather flow,   ADWF = 200 L/EP/day*
   •   Peak wet weather flow,      PWWF= 5 x ADWF*

*Assuming RIGSS sewer will be adopted for construction.

The EP for sewer loading is 186 EP. Table 5 shows the development sewer loading based on the
total EP.

                             Table 5 – Development Sewer Loading

                                              Sewer Loading
                       Parameter       L/EP/day             L/s
                         ADWF             200              0.43
                        PWWF             1000              2.15

3.2 Serviceability Requirements

All modelled scenarios were compared to the requirements from the SEQ WS&S D&C Code –
Design Criteria (2020) and design assumptions which included (but are not limited to):

   •   Emergency storage of 6 hours at average dry weather flow (ADWF) for new pump stations
       and 4 hours at ADWF for existing pump stations
   •   Maximum depth of flow for gravity sewer of 75% of pipe diameter
   •   Maximum rising main velocity of 3.0m/s (1-2 m/s preferred)
   •   Duty flow of pump stations to be greater than or equal to PWWF


3.3 Scenarios

The scenarios that were used in the assessment of the sewer network were based on the
Unitywater InfoSWMM model suppled and are listed in Table 6. The 2036 scenarios represent the
design horizon as a 2041 scenario was not provided in the model from Unitywater. The full
development was added to all post-development scenarios.




Covey Associates Pty Ltd                  5                                  Project No: 233467
Consulting Engineers                                                         M23-0030Rpt Iss A

Page 9

                       WATER SUPPLY AND SEWER NETWORK ANALYSIS
Client: Noosa Shire Council                        Location: 62 Lake Macdonald Drive, Cooroy


                               Table 6 – Sewer Modelling Scenarios
                           Scenario
                                                                   Model Alias
             Year            Development Stage

             2021       Pre-development                2021_PWWF

             2021       Post-development               2021_PWWF_COVEY

             2031       Pre-development                2031_PWWF

             2031       Post-development               2031_PWWF_COVEY

             2036       Pre-development                2036_PWWF

             2036       Post-development               2036_PWWF_ COVEY



3.4 Network Assessment

There are two proposed connection points for the development to existing maintenance structures
one in the north and the other in the south on Dianella Ct as shown in the site plans in Appendix A.
The connection point drains to the existing sewer pump station CRY020. CRY020 ultimately
discharges to the Cooroy Sewage Treatment Plant. The proposed development will use DN150
gravity sewers to convey flow to the connection points.

As part of this analysis, the development and associated demand was added to the model based
on the site plans shown in Appendix A. The results from the sewer network assessment are shown
in Appendix C.

In the model provided it was identified that SPS-CRY020 utilised an outdated pump curve for the
2021 and 2036 scenarios. Upon further discussions with Callaghan & Toth it was determined that
Unitywater recently upgraded this pump station with two new pumps (Flygt NP3153 SH3-274) with
a duty flow of approximately 16 L/s. Refer to Appendix C for pump information.

In the 2021 pre-development scenarios the Flygt NP3153 SH3-274 pump model had adequate
capacity to cater for the incoming PWWF flow of 14 L/s. In the 2021 post-development scenario,
the new Flygt pumps had adequate capacity for the incoming flow of 16 L/s due to the increase in
PWWF from the proposed development.

In the 2036 pre-development scenario, the pumps had adequate capacity for the incoming PWWF
of 15 L/s. In the 2036 post-development scenario, the PWWF further increased to 17 L/s due to the
inflow of the proposed development. Due to the increased inflow a pump upgrade was required
which increased the duty flow to 18 L/s. Further modelling confirmed that with the full development
loading, the pump upgrade would be required before 2031 based on Unitywater’s current demand
forecast. However, in the 2031 post-development scenario the existing pumps at CRY020 had
adequate capacity up to a sewer loading from the development of 100 EP (assumed to equate to
the yield from lot 1 and 2 – 51 units).

Note that the pump upgrades and new selected pumps detailed in this report are indicative only
and will need to be determined at detailed design as part of a network works application.




Covey Associates Pty Ltd                     6                                    Project No: 233467
Consulting Engineers                                                              M23-0030Rpt Iss A

Page 10

                       WATER SUPPLY AND SEWER NETWORK ANALYSIS
Client: Noosa Shire Council                        Location: 62 Lake Macdonald Drive, Cooroy

3.4.1   Pump Station Capacity

An assessment was conducted on the existing capacity of the SPS-CRY020 which is the pump
station located immediately downstream of the development connection point.

The modelled SPS Capacity and the modelled PWWF is based on the results demonstrated in the
InfoSWMM model with the inclusion of development loading. The results of the analysis are shown
in Table 7. As shown the capacity of the pump station is greater than the expected 2036 PWWF
demonstrating that the pump station has the capacity to cater for the increase in loading from the
development.

                     Table 7 – Post Development Pump Station Performance
                                                  Modelled PWWF (L/s)    Ratio of SPS
                                 Modelled SPS                            Capacity to
               SPS I.D              Capacity        Planned Horizon      2036 PWWF
                                      (L/s)
                                                   2021         2036

               CRY020                   18              14            16                 1.1



3.4.2   Rising Main Velocity

The rising main velocity for all pump stations under 2036 post-development loading was analysed.
The analysis showed that the velocity of all rising mains downstream of the pumpstations was
lower than the recommended maximum velocity of 3.0 m/s. Therefore, the rising main velocities
are acceptable.


3.4.3   Operational Storage

The required operational storage was determined for the pump station based on the pump duty for
2036 post-development flows as shown in Table 8. The analysis showed that the wet well has
adequate operational storage capacity to cater for the increased loading from the development.
Appendix C demonstrates the wet well depth over the modelling time period.

                               Table 8 – Wet Well Operational Storage
                                                                                                Ratio of
                            Effective                                       Required
                                          Calculated                                             storage
            Operational       Well                      Total Pump          minimum
  SPS I.D                                  available                                           capacity to
             Depth (m)      diameter                     Duty (L/s)         operating
                                         volume (m3)                                            required
                               (m)                                         volume (m3)
                                                                                                storage
 CRY020         0.43            2                1.4         18                1.4                 1.0



3.4.4   Emergency Storage

The required and available emergency storage was calculated for the pump station catchment
based on the 2036 post-development loading. The existing pump station CRY020 catchment has
1200 EP as detailed in the model provided by Unitywater. As shown in Table 9, the emergency
storage for the pump station was adequate to cater for both existing and development loading.




Covey Associates Pty Ltd                     7                                       Project No: 233467
Consulting Engineers                                                                 M23-0030Rpt Iss A

Page 11

                       WATER SUPPLY AND SEWER NETWORK ANALYSIS
Client: Noosa Shire Council                        Location: 62 Lake Macdonald Drive, Cooroy


                              Table 9 – Emergency Storage Results
                                                             Ratio of
                                   Total         Total
                                                             available
                                  storage       storage
                      SPS I.D                               storage to
                                 required      available
                                                             required
                                    (m3)          (m3)
                                                              storage
                      CRY020         46            69           1.5



3.4.5   Gravity Sewer Performance

All sewer mains between the development connection point and pump station CRY020 maintained
a maximum allowable depth of 75% x pipe diameter (i.e. 75% maximum depth ratio) during
PWWF, with the exception of pipe 2558134 which had a depth ratio of 76% during the 2036 pre-
development scenario. The depth ratio of this pipe increased slightly to 86% in the 2036 post-
development case however surcharging was not identified in any of the manholes within this area.
Therefore, the proposed development is considered to have a non-worsening effect on the existing
gravity sewer performance.

Further, for all development scenarios the development internal gravity sewer maintained an
acceptable flow depth. Therefore, the development is considered to have a non-worsening effect
on the surrounding sewer network.


4.0 CONCLUSION
The water supply analysis identified one water connection point off Dianella Ct. It is proposed to
extend the existing water main, as described earlier in this report, through the development to
serve the proposed development which includes a subdivision for the purpose of residential
housing.

The analysis demonstrated that, within the DMA, several existing nodes fell below the minimum
required pressure of 22m head during a peak hour simulation. However, in the post-development
scenarios no additional nodes fell below the minimum required pressure. It was demonstrated that
during a fire flow event in the pre-development scenarios that several existing nodes had a
residual pressure below 12m head. However, in the post-development scenarios no additional
nodes fell below 12m head and the proposed development had a negligible effect on any other
existing nodes.

In summary, the results from the water analysis demonstrated that the proposed development will
have a non-worsening effect on the surrounding network up to and including the design horizon
(2036). Further, the proposed extension to the water network provides adequate flow and pressure
to the proposed development both during peak hour and under fire flow conditions.

The sewer network analysis analysed the network between the development connection points to
the existing sewer pump station CRY020 which ultimately discharges to STP-CRY001 via a rising
main.

The initial assessment of the existing sewer network identified that the pumps in CRY020 had
adequate capacity for all pre-development scenarios and the 2021 post-development scenario. For
the 2036 post-development scenario, with the development loading, a pump upgrade was
required. Through further analysis it was determined that the pump station capacity needed to
increase to 18 L/s. It is recommended that the pump station capacity be upgraded before 2031
based on Unitywater’s current demand forecast. With the proposed pump upgrade detailed in this

Covey Associates Pty Ltd                    8                                   Project No: 233467
Consulting Engineers                                                            M23-0030Rpt Iss A

Page 12

                       WATER SUPPLY AND SEWER NETWORK ANALYSIS
Client: Noosa Shire Council                        Location: 62 Lake Macdonald Drive, Cooroy

report, the downstream network demonstrated acceptable performance between the development
connection point and pump station CRY020. Further, using gravity sewer mains the performance
of the network within the proposed development was also acceptable.

Therefore, as demonstrated in the report, with the inclusion of the proposed pump station upgrade
at CRY020 the development will not have a detrimental impact on current and future Unitywater
customers.


5.0 REFERENCES
SEQ Water Supply and Sewerage Design & Construction Code – SEQ WS&S D&C Code SEQ
(2020) Design Criteria

Unitywater (2019) Netserv Plan Appendix B – Schedule of Works




Covey Associates Pty Ltd                   9                                   Project No: 233467
Consulting Engineers                                                           M23-0030Rpt Iss A

Page 13

APPENDIX A
SITE PLANS

Page 14

 

 

  
 

LEGEND AERIAL IMAGE SUPPLIED BY nearmag

5m wide
Vegetation Buffer di

 

 

105
SP18458

 
   

Areas and dimensions are approximate only
and subject to final Survey and Council
approval. Contours are LiDar derived.

 

 

 

 

 

 

 

 

 

 

 

 

 

Vv
Scale 1:1250 -— Lengths are in metres.
Lull ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! J
Te) 0 lo 20 30 40 50 60 70 80 90 100 II0 120 130 140 150 160 170 180 190
CLIENT
PLAN OF DEVELOPMENT Noosa Shire Council
MURRAY & TacalrrY WAP REF
ASSOCIATES Proposed Subdivision of Cooroy o44S ee4e4
SURVEYORS & TOWN PLANNERS i Lot 105 on SP118458 DATE 5/07/2023 | Bary AHO
Murray Building,15-17 Currie St. Nambour Ph.(07)5441 2188 P.O. Box 246 FILE 100988_(Proposal)_NSC.dwg
Branch Offices at Caboolture Chinchilla Roma Gympie & Emerald DRAWN | CHECKED | ORIGINAL
LF BWB POR 105
CADASTRAL SURVEYOR LOCAL SCALE TOE No
AUTHORITY: NOOSA SHIRE COUNCIL 1:1250 100988

 

 

 

 

 

 

Page 15

                                                                                                                                                         SK400 - Water and Sewer Schematic
      8                                     29
               6                                                                                                             3               5
                         4
                                                                                                          12
                                                                                                                                                                                                                                                                                                                                        33
                                            27
                                                                                                                                                    7                                                                                                                                     Water connection to                                                                            1
                                                                                                                                                                                                                                                                                          ex DN250 DICL

                                                                                                    10                                                           12
 7                                     25                                                                                                                                                                                                                                                                                                         31
           5
                    3                                                                                              4                                10
                                                                                                8                              6                                                                                                                                 1
                                                                                                                                          8
                                   23                                                                                                                                                                                       FH                                                             Ex DN150 PVC-U
                                                                                                                                                                      57                                                    R.L 108.0                                     3

                         21                                                                 4                  6
                                                                                                                                                                                                                                                                                  5                                                                           29
                                                                                                                                                                                                                                                       2                                  Sewer connection 1
                                                                                                                                                                                DN150 PVC-O                                                                                               ex7 manhole
                             19                                                    8                                               51
                                                                                                6                                                                               Water main                                                                   4
                                                                                                          4
                                                                                                                                                                                                                                                                                                          9
                                  17                                                                                    49
                                                                                                                                                                                                                                                                          8
      12                                         15                                                                                                                                                                                                              6                                                                                                 27
                                                                                                                                                                                                                                                                                                              11


                                                                                                                                                                               DN150 PVC-U                                                                                        2
                                                                                                                                                                                                                                                                                      Denotes indicative
                                                                                                                                                                                                                                                                                                   13
                                                                             7                                                                                                                                                                                            4
                                                                                       5
                                                                                                                                                                               Sewer Main                                                                                             hydrant
                                                                                                     47
                                                                                                                                                                                                                                           FH
                                                                41
                                                                                                                                                                                                                                           R.L 115.0                  6                                                       15                                         25

                                                                                                                                                                                                                                                                                                         1
                                                                                                                                                                               42                                                              62                             5
                                                                                                                                                                                                                                                                                                                                   17
                                                                37                                                                                                                                                                                                                    3
                                                                                                                                                                                                                                                                                                     10

                                                                                                                                                                                                                                                                                                                                                                              23
                                                                                                                                                                                                                                                                                                                             19

  134A                                                                                                                                                                                                                                                                                    12

                                                            35                                                                                                                                                                                                                                                      21
                                                                                                                                                                                                                                                        FH
                                                                                                                                                                                                                                                        R.L 123.00                             14                                                       Sewer connection 2
                                                                                                                                                                                                                                                                                                                                                                          21
                                                                                                                                                                                                                                                                                                                                                        ex manhole
 132A                                                                                                                                                                                                                                                                                                                   23
                                                                                                                                                                                                                                                                                                    16
                                                           31                                             38                                                                                                                                                                                                                                 29
                                                                                                                            2C                                                                                                1A
                                                                                                                                        2B                                      2                                             DN150 PVC-U                                                                                                                                               19
                                                                                                                                                   2A                                                                                                                                                                                                   Ex DN150 PVC-U
                                                                                                                                                                           4
                                                                                                                                                                                                                              Sewer Main
                                                           29                                                                                                                                                                                                                                                            25
                                                                                                                                                             11/4                   10/4
                                                                                            34                         36
      128A

                                                                                                                                                                                                                3A
                                                            25                                                     32                                                                                                2/3A                                                                                          27                                                                           17
                                                                                                                                                             6                                                                1/3B
                                                                                       30                                                                                                                                               2/3B

                                                                                                                                                         8                                                                         3B
                                                                                                              28
                                                                                                                                                                                                      3D                      3C
                                                      23                                                                                                                                                                                                         19
                                                                                 24
                   124                                                                                                                        8A                                                                            1/3C
                                                                                                                                                                                                                                     3C
                                                                                                         26                                                                                                 5
                                                                                                                                                                      10
                                                                                                                                                                                              1/5                                                                                                                                                                                  6A
                                                                              22                                                        8B                                                            2/5
                                                                                                                                                                                                                3/5
                                                                                                                                                                                                                        4/5
                                                      21                                                                                                                                                                       5/5
                                                                                                                                                             10A                                      7                                                15
                                                                        22A                     22B
122                                                                                                                     6/12       5/12                                                     1/7     2/7

08/08/2023, 09:50:27                                                                                                                                                                                                                                   Note:                                                                                                       1:2,257
                                                                                                                                                                                                                                                       Fire hydrant (FH) surface levels are                                             0              0.03         0.05                          0.1 mi
            Water System Valve Water Auxiliary Valve Water Trunk Main                                                                                                                  Manhole                          Cadastre                       indicative and are to be confirmed at
                                                                                                                                                                                                                                                       detailed design.
Water Fitting                                                        Reflux                                             Trunk Main                                     Sewer Gravity Main                                               Base           Any discrepencies are to be reported to                                          0              0.04        0.08                          0.16 km
                                                                                                                                                                                                                                                       Covey Associates Pty Ltd for
            Tee                                                      Scour                                              Reticulation Main                                              Trunk Main                                       Easement       determination.
                                                                                                                                                                                                                                                                                                                                                   Source: Esri, Maxar, Earthstar Geographics, and the GIS
            Cross                                          Water Hydrant                                 Sewer Manhole                                                                 Reticulation Main                                Strata (Lot)                                                                                               User Community
                                                                                                                                                                                                                                                                                                                                                                        Covey Associates Pty Ltd
            Tapping Device                                           Hydrant                                            Maintenance Shaft                                                                                               Unitywater Operational Area                                                                                                     Sketch
                                                                                                                                                                                                                                                                                                                                                                        Date: 8.8.23 | Drawn: AG
                                                                                                                                                                                                                                                                                                     Unitywater
          © State of Queensland (Department of Resources), 2023 | Moreton Bay Regional Council 2015. For information and updates, planning scheme amendments or other planning related enquires contact MBRC Strategic Planning ([email protected]) For technical enquires regarding the

Page 16

APPENDIX B
WATER RESULTS

Page 17

Figure B1 – 2036 Post-development Peak Hour Residual Pressures




               UW1686




Figure B2 – 2036 Post-development Fire Flow Residual Pressures




               UW1686

Page 18

Table B1— 2036 Post-development Peak Hour Failing Nodes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ID Pressure (m)
NOON122 <0
NOO217 <0
WJ007160 0.28
NOO4861 0.83
NOOS9 1.06
NOO65 2.46
NOO61 3.07
NOO67 3.08
NOO69 3.77
3208189 3.85
NOO71 3.85
3208187 3.87
3208185 3.88
UW1504 3.9
G6011156 3.9
UW1423 4.1
NOOS55 4.99
NOOS53 5.37
2089827 11.93
2158358 17.21
8099 17.24
5060564 17.35
2168355 17.38
8092 17.39
5060565 17.42
5074715 17.44
2102568 17.53
8088 17.53
5060567 17.82
5060566 19.94
5060568 19.98
8104 19.98
5060569 20.01
8095 20.02
5060570 20.08

 

 

 

 

Page 19

Table B2- 2036 Post-development Fire Flow Failing Nodes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ID Residual
Pressure (m)
UW1687 <0
UW1686 <0
NTHWJ002542 <0
NTHWJ002578 <0
NTHWJ002579 0.69
2170822 4.84
2102561 4.84
NTHWJ002575 6.14
5043706 6.4
2169232 6.85
2102567 7.38
2170980 8.09
2167282 8.86
2089827 11.68

 

 

 

 

Page 20

APPENDIX C
SEWER DATA AND RESULTS

Page 21

NP 3153 SH 3~ 274
Patented self cleaning semi-open channel impeller, ideal for pumping in
most waste water applications. Possible to be upgraded with Guide-pin®
for even better clogging resistance. Modular based design with high
adaptation grade.



Technical specification
                                                                          Curves according to: Water, pure ,4 °C,1 kg/dm³,1.569 mm²/s
                                                                                  [m] Head
                                                                                   48
                                                                                   46
                                                                                   44
                                                                                   42
                                                                                   40
                                                                                   38
                                                                                   36
                                                                                   34
                                                                                   32
                                                                                   30
                                                                                   28
                                                                                   26
                                                                                   24
                                                                                   22                                 61.2%
                                                                                   20
                                                                                   18
                                                                                   16
                                                                                   14
                                                                                   12
                                                                                   10                                                    274 176mm
                                                                                    8
                                                                                    6
                                                                                    4
                                                                                    2
                                                                                    0
                                                                                      0    5         10     15   20       25   30   35     [l/s]
                                                                                                                                     Curve: ISO 9906


Configuration
Motor number                          Installation type
N3153.182 21-18-2FB-W                 P - Semi permanent, Wet
11KW
Impeller diameter                     Discharge diameter
176 mm                                80 mm

Pump information                                                              Materials
Impeller diameter                                                             Impeller
176 mm                                                                        Grey cast iron

Discharge diameter
80 mm

Inlet diameter
150 mm

Maximum operating speed
2900 rpm

Number of blades
2




Max. fluid temperature
40 °C


    Project                                                                 Created by         michael nguyen    Last update        10/21/2020
    Block                                                                   Created on         10/21/2020

Page 22

NP 3153 SH 3~ 274
Technical specification
Motor - General
Motor number              Phases                           Rated speed                           Rated power
N3153.182 21-18-2FB-W     3~                               2900 rpm                              11 kW
11KW
ATEX approved             Number of poles                  Rated current                         Stator variant
No                        2                                18 A                                  7

Frequency                 Rated voltage                    Insulation class                      Type of Duty
50 Hz                     415 V                            H                                     S1
Version code
182


Motor - Technical
Power factor - 1/1 Load   Motor efficiency - 1/1 Load      Total moment of inertia               Starts per hour max.
0.94                      89.9 %                           0.032 kg m²                           30

Power factor - 3/4 Load   Motor efficiency - 3/4 Load      Starting current, direct starting
0.93                      91.4 %                           128 A

Power factor - 1/2 Load   Motor efficiency - 1/2 Load      Starting current, star-delta
0.88                      92.1 %                           42.7 A




     Project                                            Created by       michael nguyen        Last update              10/21/2020
     Block                                              Created on       10/21/2020

Page 23

 

 

NP 3153 SH 3~ 274

P.

Di

erformance curve FLYGT

uty point a xylem brand

 

Flow Head

Skee ess ts ss

Sess SRPRB

  
 

Curves according to: Water, pure4 °C, 1 kg/dm?,1.569 mm?/s

 

Head

61.2%

3
I

x
8
totter tPF

274 176mm

©
iti

>

 

Pump efficiency
Overall efficiency

274 Trem

os
Power input P1 274 176mm (P1)
Shaft power P2
| 176mm (P2)

 

 

NPSH-values 274 176mm

 

 

 

TTT ot
0 2 4 6 8 10 #12 #414 «#16 «618 ©6200 «220 4 288 3 H__—(i 86 8B 4042S is]

Curve: ISO 9906
Project Created by michael nguyen Last update 10/21/2020
Block Createdon 10/21/2020

 

 

Page 24

NP 3153 SH 3~ 274
Duty Analysis

                                                             Curves according to: Water, pure ,4 °C,1 kg/dm³,1.569 mm²/s

[m] Head
 48
 46
 44
 42
 40
 38
 36
 34
 32
 30
 28
 26
 24
                                                                      61.2%
 22
 20
 18                                                            61.2%
 16
 14                                                    61.2%
 12
                                              61.2%
 10
                                                                                                                              274 176mm
  8                                 61.2%                                                                        45 Hz
  6                                                                                                 40 Hz
  4                                                                                    35 Hz
                                                                          30 Hz
  2
  0
    0        4          8          12           16            20          24            28          32           36               40           [l/s]
Operating characteristics
  Pumps /        Flow       Head        Shaft power        Flow          Head         Shaft power    Hydr.eff.         Specific        NPSHre
  Systems                                                                                                               Energy




  Project                                             Created by     michael nguyen                      Last update              10/21/2020
  Block                                               Created on     10/21/2020

Page 25

NP 3153 SH 3~ 274
Dimensional drawing




                                                                           530


                                                           85               445

                             2" Guide bars
                                                             115




                                                                                                                       Min water level
                                                       240
                               DN80




                                                                                                                895
                      400




                                                                                                                      280
                                                                                                   Z
                            270




                                                       Z


                                                                                                                90
                            15




                                                                70

                                                                           965
                                              Ref.Line                       710
                                                                      140              180
                                                                             45°
                                                                                                 180
                                                                                                140
                                       100




                                                                                 200




                                                                                                              180




                                                        60
                                                                                          Z-Z


                                                                                 Bolt Ø20(4x)
                                  Outlet center line




                                                                     250


                                                                                                  Weight              Pump Stand
                                                                                                   kg
                                                                                                Discharge DN 80
                                                                                                                       220S cale
                                                                                                                                 35      Date
                                                       NP,FP 3153 SH                            outlet
                                                                                                P ump outlet DN 80        1:20 200624
                                                                                                P ump inlet               Drawing number        Revision
                                                                                                S uction
                                                                                                inlet
                                                                                                                         6926300 8



 Project                                                   Created by        michael nguyen                    Last update                           10/21/2020
 Block                                                     Created on        10/21/2020

Page 26

   Figure C1 – 2036 Post-development SPS-CRY020 pumped flow




Figure C2 – 2036 Post-development SPS-CRY020 Operational Storage




      Table C1 – 2036 Gravity Sewer Depth Capacity Results


                             Capacity d/D
                                                    Percentage
           ID          Pre              Post       Increase (%)
                   Development       Development

         2558134      0.76                  0.86       13

Page 27

APPENDIX D
UNITYWATER’S SERVICE ADVICE NOTICE

Page 28

                                                                                                                                     Head Office:
                                                                                                                     Ground Floor, 33 King Street
                                                                                                                            Caboolture QLD 4510
                                                                                                                                Mailing Address:
                                                                                                                PO Box 953, Caboolture QLD 4510
                                                                                                                    1300 0 UNITY (1300 086 489)
                                                                                                                           www.unitywater.com
                                                                                                                                   ABN: 89 791 717 472




                                                           Services Advice Notice

              South-East Queensland Water (Distribution and Retail Restructuring) Act 2009


                                                             Notice Details

             Development Application No:                              2023022849

             Street Address:                                          62 Lake Macdonald Drive, COOROY, QLD 4563.

             Property Description:                                    Lot 105 SP118458

             Proposal:                                                100 Dwellings development on 1 into 3 subdivision

             Local Government Area:                                   Noosa Shire Council

             Date of Issue:                                           15/05/2023

             Assessment Officer:                                      Don Jayasinghe

             Responsible officer:                                     Bruk Gebreselassie

             This notice is provided in accordance with Section 99BRAC of the South-East Queensland
             Water (Distribution and Retail Restructuring) Act 2009.

             Please note that the Service Advice Notice is advisory only and does not represent
             approval of the connection or any associated works. The Service Advice Notice is valid for
             6 months from the date of this notice.

             Application must be made to Unitywater for approval of the connection or associated works.

             • Proposed development lot is located within Unitywater’s current water supply connections
               area and outside future sewer connections area.

             • Demand generated by this development exceeds the Unitywater’s planning assumptions
               for the development lot/s. However, Unitywater may be amenable to approving water
               supply and sewerage connections for the development if the demand of the proposed
               development will not have a detrimental effect on any existing or future customers within
               Unitywater’s water supply and sewerage connection and future connection areas.

             • This will need to be demonstrated by the applicant via a network analysis by a competent
               and suitably qualified consultant who can carry out such analysis. As a part of this analysis,
               a viable sewer and water connection strategy will need to be produced.

             • The water supply network analysis shall cover the DMA-COORO and the sewerage
               analysis shall cover gravity mains from the connection point up to and including SPS-
               CRY020.
                                                                                                                                       Page 1 of 4
Unitywater is a statutory authority that provides water and sewerage services for the                             Unitywater has certification to
                                                                                                                  OH&S ISO 4801:2001 Reg No 4260
Moreton Bay, Sunshine Coast and Noosa Council areas.                                                              Environmental ISO 14001:2004 Reg No 4259
                                                                                                                  Quality Systems ISO 9001:2008 Reg No 4258

                                                     Revision No: 2                Effective Date: 19/02/2015              Next Review Date:19/02/2018

Page 29

             • A free copy of Unitywater’s network models for this location is available to the developer
               on request subject to conditions. Please contact Senior Engineer Network Modelling,
               Mathy Jegan at [email protected]

       Reconfiguration of a in to 3 subdivision
          • The developer will be required to provide reticulated water supply to all 3 lots within the
             subdivision and connection(s) to Unitywater’s existing water supply network. Water mains
             shall be provided along the full frontage/s of the development site for each stage to ensure
             future mains extension can occur without disturbing developed footpath and the need for
             council approval for works in roads.

             • The developer will be required to provide reticulated sewerage to all 3 lots within the
               development, including a property connection to each lot and connection(s) to Unitywater’s
               existing sewerage network.

       Community housing within the subdivision
          • Community housing within the subdivision will be required to provide;
             o Metered water service to all units within the subdivided lot with a primary meter and
                 sub- meters in accordance with Queensland Plumbing and Wastewater Code 2010
                 – Part 4 and Unitywater’s sub metering policy.
             o A single sewer connection to the community title lot from Unitywater’s existing
                 sewerage network and internal sewers with property connection to all units within
                 the development in accordance with SEQ design standards.
          • The connection application shall accompany plans indicating,
             o The location of any metered water connection/s and sewerage property connections
                 including offsets from boundaries and invert levels for new sewerage connections.
             o Any proposed large diameter water connections (greater than Ø25mm), above
                 ground master meter assembly (This shall be located within the development
                 property boundary) and proposed sub-meter installations.

       Fire Fighting Requirements (Commercial or Industrial and Units)
           • Direct connection of pressure boosting pumps to Unitywater network is not favoured by
              Unitywater. Sometimes the requests may be considered depending on the capacity,
              condition and sufficient connectivity of the reticulation system in the area. If there is any
              such proposal, details of the pumps (pump curves and design calculations) needs to
              be submitted to Unitywater’s Development Services for approval prior to installation.
              This request shall include a certification by the hydraulic consultant that the maximum
              flow rate of the installed pumps will be no greater than Unitywater’s standards of service,
              relevant for the site.

             • Unitywater’s level of service towards firefighting capacity is guided by SEQ Design &
               Construction Guidelines whereas the internal fire suppression systems of buildings shall
               comply with the requirements of AS 2419.Therefore it is the responsibility of the developer
               to design and install the necessary infrastructure such as pumps, break tanks etc, so that
               the internal fire suppression system complies with the relevant standards.

                                                                                                                                     Page 2 of 4
Unitywater is a statutory authority that provides water and sewerage services for the                           Unitywater has certification to
                                                                                                                OH&S ISO 4801:2001 Reg No 4260
Moreton Bay, Sunshine Coast and Noosa Council areas.                                                            Environmental ISO 14001:2004 Reg No 4259
                                                                                                                Quality Systems ISO 9001:2008 Reg No 4258

                                                     Revision No: 2                Effective Date: 19/02/2015           Next Review Date: 19/02/2018

Page 30

             • The Usage of street hydrants as standalone firefighting facility to a building will be entirely
               at the risk of the developer. Unitywater will not guarantee that the street hydrants will comply
               with the requirements of AS 2419 or of QFES. This applies to dry hydrant systems too.

             • It is strongly recommended that the developer submits an application for flow & pressure
               information about the water mains that the development is getting connected to. This
               information will provide details of the expected flow & pressure of Unitywater’s street
               watermain in the vicinity of the development from a hydraulic model prediction. The
               application       can    be      downloaded      from     Unitywater’s      web      site
               https://www.unitywater.com/faults-and-outages/water-supply-problems/water-pressure
               (Form 8578)

             • Unitywater, at its discretion, may change the operational regime of its water mains.
               However, it won’t be changed below Unitywater’s minimum level of service towards street
               hydrants. These values are shown in Table 1 below. For more details, please refer to the
               latest version of SEQ Design & Construction Code.

                                                                                              Flow available            Residual
                                                                                            from Unitywater             Head in Water
                                            Type of Use                                            Main                 main (meters)
                                                                                             (Litres/second)

                 Residential dwellings of less than 3 storey                                            15                        12

                 Commercial that is ancillary to residential use                                        15                        12

                 Multi Storey residential greater than 3 storeys                                        30                        12

                 Commercial and or Industrial                                                           30                        12


             • Location of existing Unitywater infrastructure can be viewed at Unitywater’s website.
               Precise details of infrastructure are available via Detailed Infrastructure Plan (DIP) on
               application. Further information on this process is available at Unitywater website
               http://www.unitywater.com/reference library.

             • This proposal would require the applicant to apply to Unitywater for a ‘Staged or Other
               Connection Application’ which includes application/s for ‘network works’. For further
               information on this process refer to Unitywater’s website at http://unitywater.com/Building-
               and-developing.

             • For current information in relation to all Unitywater’s fees applicable to connection
               applications and development related works please refer to Unitywater website at
               https://www.unitywater.com/Building-and-developing/pricing-fees-and-charges.

             • Should an approval for connection be provided by Unitywater, the developer will need to
               apply to Unitywater for a Private Works Quote in relation to the cost for new metered water
               supply service connections and live connections to existing water/sewer infrastructure by
                                                                                                                                     Page 3 of 4
Unitywater is a statutory authority that provides water and sewerage services for the                           Unitywater has certification to
                                                                                                                OH&S ISO 4801:2001 Reg No 4260
Moreton Bay, Sunshine Coast and Noosa Council areas.                                                            Environmental ISO 14001:2004 Reg No 4259
                                                                                                                Quality Systems ISO 9001:2008 Reg No 4258

                                                     Revision No: 2                Effective Date: 19/02/2015           Next Review Date: 19/02/2018

Page 31

                 Unitywater. A copy of the connection approval and associated approved plans detailing the
                 new connections must accompany the private works quotation application. Please refer
                 Unitywater’s website at http://www.unitywater.com/private-works. for further details.

             • It is the Applicant’s responsibility to ensure that it has all necessary consents and approvals
               to carry out any connection related works in a publicly controlled place (e.g. Council, DTMR)
               or property that is not owned or controlled by the Applicant prior to starting such works.

             • All water supply and sewerage works must be designed and constructed in accordance with
               the South-East Queensland Water Supply and Sewerage Design and Construction Code,
               Unitywater’s Connections Administration Manual and any other matter Unitywater considers
               to be relevant to the connection or supply of its water services or wastewater services.
             • Easements will be required in accordance with the South-East Queensland Water Supply
               and Sewerage Design and Construction Code over water/sewerage mains located in private
               property boundaries.

             • Payment of Levied Charges will be required in accordance with Unitywater’s Infrastructure
               Charges for water supply and sewerage.

                 If you have any queries about the advice, please contact                                                Unitywater            at
                 [email protected] or by phone on 1300 086 489.

                 Yours sincerely,
                 Development Services
                 Unitywater




                                                                                                                                     Page 4 of 4
Unitywater is a statutory authority that provides water and sewerage services for the                           Unitywater has certification to
                                                                                                                OH&S ISO 4801:2001 Reg No 4260
Moreton Bay, Sunshine Coast and Noosa Council areas.                                                            Environmental ISO 14001:2004 Reg No 4259
                                                                                                                Quality Systems ISO 9001:2008 Reg No 4258

                                                     Revision No: 2                Effective Date: 19/02/2015           Next Review Date: 19/02/2018

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.