             • The Usage of street hydrants as standalone firefighting facility to a building will be entirely
               at the risk of the developer. Unitywater will not guarantee that the street hydrants will comply
               with the requirements of AS 2419 or of QFES. This applies to dry hydrant systems too.

             • It is strongly recommended that the developer submits an application for flow & pressure
               information about the water mains that the development is getting connected to. This
               information will provide details of the expected flow & pressure of Unitywater’s street
               watermain in the vicinity of the development from a hydraulic model prediction. The
               application       can    be      downloaded      from     Unitywater’s      web      site
               https://www.unitywater.com/faults-and-outages/water-supply-problems/water-pressure
               (Form 8578)

             • Unitywater, at its discretion, may change the operational regime of its water mains.
               However, it won’t be changed below Unitywater’s minimum level of service towards street
               hydrants. These values are shown in Table 1 below. For more details, please refer to the
               latest version of SEQ Design & Construction Code.

                                                                                              Flow available            Residual
                                                                                            from Unitywater             Head in Water
                                            Type of Use                                            Main                 main (meters)
                                                                                             (Litres/second)

                 Residential dwellings of less than 3 storey                                            15                        12

                 Commercial that is ancillary to residential use                                        15                        12

                 Multi Storey residential greater than 3 storeys                                        30                        12

                 Commercial and or Industrial                                                           30                        12


             • Location of existing Unitywater infrastructure can be viewed at Unitywater’s website.
               Precise details of infrastructure are available via Detailed Infrastructure Plan (DIP) on
               application. Further information on this process is available at Unitywater website
               http://www.unitywater.com/reference library.

             • This proposal would require the applicant to apply to Unitywater for a ‘Staged or Other
               Connection Application’ which includes application/s for ‘network works’. For further
               information on this process refer to Unitywater’s website at http://unitywater.com/Building-
               and-developing.

             • For current information in relation to all Unitywater’s fees applicable to connection
               applications and development related works please refer to Unitywater website at
               https://www.unitywater.com/Building-and-developing/pricing-fees-and-charges.

             • Should an approval for connection be provided by Unitywater, the developer will need to
               apply to Unitywater for a Private Works Quote in relation to the cost for new metered water
               supply service connections and live connections to existing water/sewer infrastructure by
                                                                                                                                     Page 3 of 4
Unitywater is a statutory authority that provides water and sewerage services for the                           Unitywater has certification to
                                                                                                                OH&S ISO 4801:2001 Reg No 4260
Moreton Bay, Sunshine Coast and Noosa Council areas.                                                            Environmental ISO 14001:2004 Reg No 4259
                                                                                                                Quality Systems ISO 9001:2008 Reg No 4258

                                                     Revision No: 2                Effective Date: 19/02/2015           Next Review Date: 19/02/2018
Log in to download the original file

Appendix G Water and Sewer Analysis.pdf · 7.9 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.