                                                        TOOCONSULTING


Live Load*

Balconies and stairs                        4.0 kPa

Residential areas                           2.5 kPa (Point Load 1.8 kN)

Internal garages                            3.0 kPa (Point Load 9 kN)

Driveway, Service Vehicle
Delivery/Loading Area                       10.0 kPa (Point Load 31 kN)
                                            (or construction loading)

Mechanical and electrical plant rooms       8.0 kPa (min) (Point Load
                                                   4.5 kN)

External Terrace Areas                      5.0 kPa (min)

    *   Design Live Load must never be less than construction loading

Earthquake Load


The building will be designed for seismic load in accordance with the
 relevant Australian Standard being AS/NZS 1170.4.
• Importance Level 2
• Soil Factor: Class Ce (most of loose sand layer to be removed from
     building platform)
• Earthquake Design Category I

Wind Load

The building will be designed for wind loads in accordance with the
relevant Australian Standards (being AS/NZS 1170.2) for the following
parameters:

Basic Wind Velocity VR        -      57m/s (Ult Strength Limit State)
Region                        -      B
Terrain Category              -      2.0
Multiplier factors            Mz, cat = 0.96, Ms = 1 .0, Mh = 1.3
Design Wind Speed             -      72 m/s Ult limit state
                                     60 m/s Permissible Stress Design

Soil Retaining Structures: Refer also to final Geotechnical Report

Soil Density = 19 kN/m3
Horizontal Pressure - sloping backfill Ko = 0.75;
                     horizontal backfi l l Ko = 0.5
Surcharge: adjacent blocks -allow 10 kPa L.L. surcharge.
Provide vertical wick drainage behind all contiguous piled retaining
structures at 4m centres
Provide continuous sub-soil drains behind all conventional retaining walls
Factor of safety against sliding:- temporary 1.2, permanent 2.0

                                                                          11

Used in these records

About this file

File size
14.8 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

08_0169 Information Response to DERM - 71 Seaview Terrace Sunshine Beach.pdf · 14.8 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.