PROJECT:
                                                                                                                                                                                                         REVISIONS
ONSITE WASTEWATER TREATMENT AND EFFLUENT DISPOSAL SYSTEM                                                                                                                                  #
                                                                                                                                                                                          A
                                                                                                                                                                                               DATE       SUBJECT
                                                                                                                                                                                               06/11/2024 REVISION A
                                                                                                                                                                                                                            AUTHORISED
                                                                                                                                                                                                                            C. TAYLOR


FOR TINY HOME AT 328 UPPER PINBARREN CREEK ROAD, PINBARREN

GENERAL NOTES                                                                      LEGEND
 1. LOCATION OF HSTP, ORG, VENT PIPE AND OTHER WASTE PIPES TO BE DETERMINED BY                     PROPERTY BOUNDARY                                                                          TAYLOR ENVIRONMENTAL
     PLUMBER                                                                                       EASEMENT
 2. REFER TO COMPLIANCE PERMIT FOR CONDITIONS OF COUNCIL APPROVAL                                  CONTOUR - MINOR
 3. PROPERTY FEATURES, STRUCTURES AND CONTOURS HAVE BEEN REPRODUCED BASED ON                       CONTOUR - MAJOR
     THE BEST AVAILABLE INFORMATION AND MAY NOT BE COMPLETE OR ACCURATE                            DECOMMISSION
 4. THE SYSTEM INSTALLER IS RESPONSIBLE TO ESTABLISH THE LOCATION, LEVELS AND
     DEPTHS OF ALL EXISTING SERVICES ON-SITE PRIOR TO COMMENCING ANY WORKS                         MSES VEGETATION
 5. LOCATIONS AND SETOUT DIMENSIONS SHOWN ARE APPROXIMATE ONLY AND ARE TO BE                       VEGETATION LINE
     CONFIRMED ON SITE.                                                                            TREE LINE
 6. ACCESS AND LAY DOWN AREAS ARE TO BE CONFIRMED BY THE SYSTEM INSTALLER                          PROTECTED TREE
 7. EXISTING BUILDINGS AND EXTERNAL STRUCTURES SHOWN ON THESE DRAWINGS ARE                         INTERMITTENT WATERBODY
     OBTAINED FROM THE AVAILABLE INFORMATION AND MAY NOT BE COMPLETE AND                           PERMANENT WATERBODY
     ACCURATE                                                                                      FLOW PATH
 8. ALL DIMENSIONS ARE IN MM U.N.O                                                                 DEFINED FLOOD LINE
 9. PLUMBING AND DRAINAGE TO QLD PLUMBING & WASTEWATER ACT, AS / NZS 3500                          CHANGE OF GRADE
 10. ALL PIPE WORK TO AS / NZS 4020                                                                TOP OF BANK
 11. ALL TANKS TO BE INSTALLED AND ANCHORED IN COMPLIANCE WITH THE                                 RETAINING WALL
     MANUFACTURERS SPECIFICATIONS
 12. FLEXIBLE JOINTS ON ALL INSTALLED TANKS (AS / NZS 3500)                                        WASTEWATER COMPONENT
 13. THERE SHALL BE NO CROSS CONNECTION BETWEEN ANY WASTEWATER / EFFLUENT                          GRAVITY DRAINAGE - NEW
     PIPEWORK AND ANY POTABLE WATER SUPPLY PIPEWORK                                                GRAVITY DRAINAGE - EXISTING
 14. MINIMUM DISTANCE BETWEEN TANKS AND BUILDINGS TO BE MAINTAINED (AS/NZS 3500)                   RISING MAIN - NEW
 15. USE ONLY A LICENSED DRAINER THAT HAS BEEN ACCREDITED BY THE SYSTEM                            RISING MAIN - EXISTING
     SUPPLIER.
 16. FINAL LOCATION OF THE LAND APPLICATION AREA AND ASSOCIATED PIPE WORK CAN                      STORMWATER PIPE
     ONLY BE ALTERED ON SITE TO MEET THE SITE CONDITIONS AFTER APPROVAL FROM                       WATER MAINS
     TAYLOR ENVIRONMENTAL (AUSTRALIA) PTY LTD                                                      ELECTRICAL - OVER HEAD
                                                                                                                                                                                                QBCC LICENCE NUMBER 150 556 72
 17. GRADE ALL BATTERS EVENLY AT 1 IN 5, UNLESS NOTED OTHERWISE                                    ELECTRICAL - UNDERGROUND                                                                        ABN NUMBER 95268308955
 18. ANY SOILS ENCOUNTERED WHICH SHOW EVIDENCE OF CONTAMINATION ARE TO BE                          COMMS SERVICES
     STOCKPILED SEPARATELY. CONTAMINATED SOIL SHALL BE HANDLED IN ACCORDANCE                       NBN SERVICES
     WITH ALL WORKPLACE HEALTH & SAFETY AND ENVIRONMENTAL REGULATIONS                              TELSTRA SERVICES
                                                                                                                                                                                                     Phone: +61 400 301 364
 19. IT IS THE INSTALLERS RESPONSIBILITY TO PROVIDE ACCURATE 'AS CONSTRUCTED'                      GAS SERVICES                                                                                  Email: [email protected]
     DRAWINGS TO RELEVANT LOCAL AUTHORITY AND INCUR ASSOCIATED COST                                FIRE MAIN SERVICES                                                                             Web: www.taylorenviro.com.au
 20. ALL DISTURBED AREAS TO BE REINSTATED TO NATURAL GROUND CONDITIONS
 21. EXISTING TOPSOIL IS TO BE RETAINED AND SET ASIDE (WINDROWED) TO PREVENT
     DAMAGE FROM MACHINERY AND REDISTRIBUTED ONCE INSTALLATION IS COMPLETE
 22. AT LEAST A 5 TONNE MACHINE WITH POSI-TRACK SYSTEM IS REQUIRED FOR             ABBREVIATIONS
     EARTHWORKS TO ELIMINATE POTENTIAL TRACK INDENTATIONS INTO GROUND LEVEL
 23. ALL MATERIALS SHALL BE NEW, PROVEN IN SERVICE AND SUITABLE FOR THE INTENDED   AAV       AIR ADMITTANCE VALVE
     USE                                                                           AES       ADVANCED ENVIRO SEPTIC OSSF SYSTEM
 24. IT IS THE RESPONSIBILITY OF THE INSTALLER TO ENGAGE THE DESIGNER TO           AS
                                                                                   B
                                                                                             AUSTRALIAN STANDARD
                                                                                             HAND BASIN                           PIN                                                     WASTE WATER TREATMENT &
     UNDERTAKE INSPECTIONS DURING INSTALLATION. FAILURE TO DO SO WILL RESULT IN                                                       BARR
     THE FORM 8 / COMMISSIONING CERTIFICATE NOT BEING ABLE TO BE COMPLETED         BTH
                                                                                   COS
                                                                                             BATH TUB
                                                                                             CLEAR OUT TO SURFACE                            EN                                           EFFLUENT DISPOSAL SYSTEM
 25. DO NOT SCALE FROM DRAWINGS                                                                                                                   CRE
 26. TAYLOR ENVIRONMENTAL TAKES NO RESPONSIBILITY FOR WORKS UNDERTAKEN BY THE      CS        CLEANERS SINK                                              EK
     INSTALLER AND/OR INSTALLATIONS THAT ARE NOT IN ACCORDANCE WITH THESE PLANS    DG        DISCONNECTOR GULLY
 27. THESE PLANS ARE TO BE READ IN CONJUNCTION WITH THE SITE AND SOIL REPORT,      DW        DISHWASHER                                                                                   AUTHORISED FOR ISSUE             DATE
     ARTICULATED JOINT DESIGN AND REGULATOR ISSUED COMPLIANCE PERMITS              e??       EXISTING ITEM
                                                                                   FFL       FINISHED FLOOR LEVEL
                                                                                   FSL       FINISHED SURFACE LEVEL               UP
SANITARY DRAINAGE AND PLUMBING                                                                                                       PE                                                                                   06/11/2024
 1. SANITARY DRAINAGE SHALL BE ∅100 UPVC AT A 1:60 MINIMUM GRADE                   FWG       FLOOR WASTE GRATE                          R   PIN
 2. IO's UNDER CONCRETE/IMPERMEABLE GROUND COVERINGS SHALL BE TAKE TO SURFACE      HSTP      HOME SEWAGE TREATMENT PLANT                       BA
     LEVEL AS AN IOS AND FITTED WITH AN APPROVED SCREW CAP                         IL        INVERT LEVEL                                         RR                                      STREET ADDRESS
 3. ORG' RISERS SHALL BE TO AS3500.2 AND EXTEND TO AN APPROVED GRATE AT 150mm      IO        INSPECTION OPENING                                      EN
                                                                                   IOS       INSPECTION OPENING TO SURFACE                              C    RE                           328 UPPER PINBARREN CREEK RD, PINBARREN
     BELOW LOWEST FIXTURE, 75mm ABOVE GROUND LEVEL AND ABOVE DEFINED FLOOD                                                                                      EK
                                                                                   IV        INDEXING VALVE
     LEVEL
                                                                                   LAA       LAND APPLICATION AREA
                                                                                                                                                                     RO                   LOT & PLAN
 4. UNDERSLAB SANITARY DRAINAGE SHALL BE INSTALLED IN ACCORDANCE WITH THE                                                                                              AD
                                                                                   LT        LAUNDRY TUB
     ARTICULATED JOINT DESIGN (WHERE REQUIRED) AND AS3500.2 APPENDIX G
                                                                                   NGL       NATURAL GROUND LEVEL                                                                         LOT 3 RP851976
 5. LAGGING IN ACCORDANCE WITH AS3500
                                                                                   ORG       OVERFLOW RELIEF GULLY
 6. BURIED PIPEWORK SHALL BE 200mm DEEP IN NON TRAFFICABLE AREAS AND 500mm
                                                                                   OSSF      ON-SITE SEWAGE FACILITY
                                                                                                                                                                                          COUNCIL
     DEEP IN TRAFFICABLE AREA, OR IN ACCORDANCE WITH AS3500
                                                                                   RL        REDUCED LEVEL                                                                                NOOSA SHIRE
INSTALLATION                                                                       S         SINK
  1. IT IS THE INSTALLERS RESPONSIBILITY TO ENSURE THAT ALL COMPONENTS COMPLY      SHR       SHOWER                                                                                       NAME OF CLIENT
      WITH THESE GUIDES UPON COMMISSIONING OF THIS SYSTEM                          ST        STACK
  2. ALL BURIED PIPE WORK IS TO BE IDENTIFIED WITH UNDERGROUND MARKING TAPE        UR        URINAL                                                                                       VIKI DIOSZOGI
      PLACED ABOVE THE PIPE WORK                                                   V         VENT
                                                                                   WC        WATER CLOSET                                                                                 DESIGNER
  3. ALONG THE BOUNDARY OF THE LAND APPLICATION AREA THERE SHALL BE AT LEAST 2
      WARNING SIGNS CLEARLY VISIBLE TO ADVISE THAT RECYCLED WATER IS USED (EACH                                                                                                           C. TAYLOR
      SIGN SHALL COMPLY WITH AS1319 AND HAVE THE WORDING RECYCLED WATER - AVOID
      CONTACT DO NOT DRINK)                                                                                                                                                               DRAWN
MAINTENANCE                                                                                                                                                                               M. MAHONY
 1. SYSTEM TO BE SERVICED AND MAINTAINED IN ACCORDANCE WITH MANUFACTURE
                                                                                                                                                                                          DRAWING DETAILS
     SPECIFICATIONS AND COUNCIL GUIDELINES
 2. SEPTIC TANKS TO BE CHECKED FOR SOLIDS BUILD UP ANNUALLY                                                                                                           SUBJECT PROPERTY    TITLE PAGE
 3. SEPTIC TANKS TO PUMPED OUT IF 31 FULL OF SOLIDS OR 5 YEARS (WHICHEVER IS
     SOONER)                                                                                                                                                                1:7500 @ A3   JOB NUMBER
 4. LAND APPLICATION IS IMPORTANT AND IS TO BE REGULARLY MOWED AND ANIMALS
     AND VEHICLES EXCLUDED                                                                                                                                                                TE249167
                                                                                                                                                                                              SCALE         REVISION          DWG #
                                                                                                                                                                                              1:7500            A              SL0
Log in to download the original file

SSE - TE249167 - 328 Upper Pinbarren Creek Road, Pinbarren Qld 4568.pdf · 3.3 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.