Appendix 3- Engineering Drawings · MCU17/0027

Attached to the e-mail Engineering plans, Landscape Plan and Response to Code (Email 2 of 2) MCU17/0027 & OPW17/0119.

of 9

Text shows just the words. Original shows the document exactly as it was published.

                                                                             PROPOSED HOUSE
                                                                    AT 27 & 29 GRANT ST, NOOSA HEADS
                                                                          FOR G & M ROBERTSON
                                                                               JOB No. 1537




                                             SCHEDULE OF DRAWINGS

                                 1537-R01     Locality Plan and Schedule of Drawings
                                 1537-R02     Access Driveway, Stormwater and Sewer Plan
                                 1537-R03     Earthworks and Erosion Sediment Plan
                                 1537-R04     Car Turning Templates

                                 1537-ST01    Retaining Walls Layout Plan
                                 1537-ST02    Retaining Walls Section Details - Sheet 1 of 3
                                 1537-ST03    Retaining Walls Section Details - Sheet 2 of 3
                                 1537-ST04    Retaining Walls Section Details - Sheet 3 of 3
                                 1537-ST05    Driveway Slab Layout & Slab Joint Plan
                                                                                                                                                                                               SUBJECT SITE




                                    PROPERTY DESCRIPTION
                                    Lot 4 on SP230068
                                    Lot 6 on SP179879
                                                                                                                                                                                                                                                           LOCALITY PLAN




                                                                                                                                                                                                                                                             PROJECT:             JOB NUMBER
REV DATE DESCRIPTION                    BY   CHKD                                                                     SCALE                                                APPROVED
                                                                                                                                                                                                                                                                                       1537
 1   24.03.17   APPROVAL ISSUE          JG     CL
                                                     DATUM                   AHD                                                                                                                                                                                              SHEET:        OF
                                                     DESIGN                  DK
                                                                                                                                                                         .................                                                                                              1        5


                                                                                                                                                                      Director: PETER BARLOW                                                                 DRAWING TITLE:   DRAWING NUMBER         REV
                                                     DRAWN                   JG
                                                                                                                                                                             (RPEQ 1330)
                                                     DESIGN CHECK            PB
                                                                                                                                                                      DRAWING STATUS
                                                                                                                                                                                                 07 5443 8285
                                                                                                                                                                                                                                                                                   R01                1
                                                                                                                                                                                                [email protected]     www.barlowshelley.com.au
                                                                                        This drawing is not to be copied or amended without written permission from
                                                     DATE                  20-03-17     Barlow Shelley Consulting Engineers
                                                                                                                                                                            FOR APPROVAL        PO Box 899, Maroochydore,4558 ABN 89 215 591 077
Full text of the other 8 pages

Page 2

                                                                                                                                                                                                        t




                                                                                                                                                                                                             t
                                                                                 18




                                                                                                                                                                                                                   t




                                                                                                                                                                                                                                                     G
                                                                                                                                                                                                                                                        R
                                                                                                                                                                                                                                                           AN
                                                                                                                                                                                                                       t




                                                                                                                                                                                                                                                             T
                                                                                                                                                                                                                                                                   S
                                                                                                                                                                                                                              t
                                                                              17                                                                                                                                                                                                                                                       LEGEND




                                                                                                                                                                                                                                                                    T
                                                                                                                                                                                                                                                                                                                                       D         D        EXISTING STORMWATER




                                                                                                                                                                                                                                    t
                                                                                                                                                                                                                                                                                                                                                          EXISTING SEWER MAIN
                                                                                                                                                                                                                                                                                                                                                          EXISTING WATERMAIN




                                                                                                                                                                                                                                         t
                                                                                                                                                                                                                                                                                  EXISTING WATER METERS                                                   EXISTING ENERGEX - UNDERGROUND

                                                                            16                                                                                                                                                                                                                                                             t         t    EXISTING TELSTRA




                                                                                                                                                                                                                                              t
                                                                                                                                                                                                                                                                                                                                                          PROPOSED HOUSE




                                                                                                                                                                                                                                                       t

                                                                                                                                                                                                                                                              EX
                                                                                                                                                                                                                                                                IST
                                                                                                                                                                                                                                                                   IN
                                                                                                                                                                                                                                                                                                                                                          PROPOSED CONCRETE DRIVEWAY




                                                                                                                                                                                                                                                                     G



                                                                                                                                                                                                                                                                                   Ke
                                                                                                                                                                                                                                                               t

                                                                                                                                                                                                                                                                      EL



                                                                                                                                                                                                                                                                                      rb
                                                                                                                                                                                                                                                                         EC t



                                                                                                                                                                                                                                                                                          &
                                                                      15




                                                                                                                                                                                                                                                                           TR



                                                                                                                                                                                                                                                                                            Gu
                                                                                                                                                                                                                                                                             IC
                                                                                                                                                                                                                                                                                ITY



                                                                                                                                                                                                                                                                                              tte
                                                                                                                                                                                                                                                                                      EX


                                                                                                                                                                                                                                                                                                  r
                                               REFER STRUCTURAL




                                                                                                                                                                                                                                                                                          IST
                                               DRAWINGS FOR DRIVEWAY




                                                                                                                                                                                                                                                                                             ING
                                                                                                                                                                                                                                                                             EX
                                                                                                                                                                                                                                                                              t I ST
                                               CONSTRUCTION DETAILS




                                                                                                                                                                                                                                                                                              WA
                                                                                                                                                                                                                                                                                    IN



                                                                                                                                                                                                                                                                                                   TE
                                                                                                                                                                                                                                                                                      G
                                                                                                                                                                                                                                                                                      TE


                                                                                                                                                                                                                                                                                                      R
                                                                                                                                                                                                                                                                                       t ST


                                                                                                                                                                                                                                                                                                      PIP
                                                                                                                                                                                                                                                                                         L
                                                                      14




                                                                                                                                                                                                                                                                                                          E
                                                                                                                                                                                                                                                                                            RA
                                                                                                                                   2%




                                                                                                                                                                                                                                                                                                    t
                                                                                                                                                                                     PROPOSED HOUSE



                                                                                                                     5%
                                                                                                                                                                                           FFL14.400




                                                                                                                                                                                                                                                                                                              t
                                              EXISTING STORMWATER PIT
                                              TO BE REMOVED.
                                                                 13




                                                                                                                                                                                                                                                                                                                  t
                                   SEWER MANHOLE TO BE
                                   RAISED TO NEW DRIVEWAY




                                                                                                                                                                                                                                                                                                                      t
                                   LEVEL. LID CHANGED TO
                                                                                                     %




                                   TRAFFICABLE LID.
                                                                                                    15.2




                                   EX SL: 12.36




                                                                                                                                                                                                                                                                                                                             t
                                   NEW SL: 12.80




                                                                                                                                                                                                                                                                                                                                   t
                JOIN NEW DRIVEWAY
                                                                 12




                SMOOTHLY TO EXISTING
                                                                             16%
                                                                                                                                                                                                 2%
                                                                                             1.0%




                PROPOSED GRATED
                STORMWATER DRAIN.                                                                                                                                                         5%
                CONNECT INTO EXISTING
                PIT.
                                                                                                                                                 11.5%
                                                                                                                                                                        1.0%




                                                                                                                                                                                                                                                                                                          DRAIN TO BOTTOM OF
                                                                                                                                                                                                                                                                                                          RETAINING WALL AS PER
                                                KERB TO TOP OF
                                                                                                                                          12




                                                                                                                                                                                                                                                                                                          LANDSCAPE DRAWINGS
                                                RETAINING WALL TO
                                                DIRECT FLOWS INTO
                                                                        EXISTING HCB
                                                EXISTING PIT

                                                                          EXISTING STORMWATER
                                                                          PIPE TO BE REMOVED TO
                                                                          NEXT PIT.
                                                                                                                                                                                                                             HOUSE PLUMBING
                                                                                                                                                                                                                             INDICATIVE ONLY. REFER                                                                                            NOTE:
                                                                                                                                                                                                                             TO PLUMBER FOR DETAILS                                                                                            REFER IPWEA STD DRAWING RS-050
                                                                                                                                                                                                                                                                                                                                               FOR NOTES.
                                                                                                                                                                                                       STORMWATER PIPE FOR
                                                                                                                                                                                                       HOUSE CONNECTION
                                                                                                                                                                                                       IL 11.32

                                                                                                               EXISTING HCB                                                                                                                                                                                                                    NOTE:
                                                                                                                                                                               12                                                                                                                                                              DRIVEWAY GRADE AS PER AS/NZS
                                                                                                                                                                                                                                                                                                                                               2890.1. SECTION 2.6 - DESIGN OF
                                                                                                                                                                                                                                                                                                                                               DOMESTIC DRIVEWAYS.



                                                                                                                                                                                                                                                                                                                  PROJECT:                                                                 JOB NUMBER
REV DATE DESCRIPTION                               BY   CHKD                                                                        SCALE                                                       APPROVED
                                                                                                                                                                                                                                                                                                                                                                                             1537
 1   24.03.17    APPROVAL ISSUE                    JG       CL
                                                                 DATUM                 AHD                                                                                                                                                                                                                                                                                          SHEET:        OF
                                                                 DESIGN                DK              0              2               4              6              8               10m
                                                                                                                                                                                               .................                                                                                                                                                                              2         5


                                                                                                                                                                                           Director: PETER BARLOW                                                                                                 DRAWING TITLE:                                                    DRAWING NUMBER          REV
                                                                 DRAWN                 JG
                                                                                                                                                                                                  (RPEQ 1330)
                                                                 DESIGN CHECK          PB                                           SCALE 1:200 A3
                                                                                                                                                                                          DRAWING STATUS
                                                                                                                                                                                                                                              07 5443 8285
                                                                                                                                                                                                                                                                                                                                                                                           R02               1
                                                                                                                                                                                                                                             [email protected]     www.barlowshelley.com.au
                                                                                                      This drawing is not to be copied or amended without written permission from
                                                                 DATE               20-03-17          Barlow Shelley Consulting Engineers
                                                                                                                                                                                                  FOR APPROVAL                               PO Box 899, Maroochydore,4558 ABN 89 215 591 077

Page 3

                                                                                                                                                                                            5
                                                                                                                                                                                         .1
                                                                                                                                                                                     20
                                                                                                                                                                                               t

                                                                                                                                                                                                                                                                                                                                                              LEGEND




                                                                                                                                                                                                         t
                                                                                                                                                                                                                                                                                                                                                              D             D                       EXISTING STORMWATER
                                                                             18




                                                                                       X
                                                                                                                                                                                                                                                                                                                                                                                                    EXISTING SEWER MAIN




                                                                                                                                                                                                                t
                                                                                                                                                                                                                                                                                                                                                                                                    EXISTING WATERMAIN

                                                                                                                                                                                                                                                                                                                                                                                                    EXISTING ENERGEX - UNDERGROUND




                                                                                                                                                                                                                      t
                                                                                      X
                                                                                                                                                                                                                                                                                                                                                                  t               t                 EXISTING TELSTRA

                                                                                                                                                                                                                                                                                                                                                                      X               XSF           PROPOSED SEDIMENT FENCING




                                                                                                                                                                                                                           t
                                                                           17




                                                                                  X
                                                                                                                                                                                                                                                                       REFER LANDSCAPE
                                                                                                                                                                                                                                                                                                                                                                            PP                      PROPOSED INLET PROTECTION




                                                                                                                                                                                                                                 t
                                                                                                                                                                                                                                                                       DRAWINGS FOR EXACT
                                                                                                                                                                                                                                                                       LEVELS AND STRUCTURAL




                                                                                 X
                                                                                                                                                                                                                                                                       ENGINEERS DRAWINGS                                                                                                           TOP OF RETAINING WALLS    (REFER LANDSCAPE AND STRUCTURAL




                                                                                                                                                                                                                                         t
                                                                                                                                                                                                                                                                       FOR RETAINING WALL                                                                                                           BOTTOM OF RETAINING WALLS ENGINEERS DRAWINGS FOR DETAILS)
                                                                                                                                                                                                                                                                       DETAILS




                                                                             X
                                                                       16                                                                                                                                                                                                                                                                                                                           PROPOSED EARTHWORKS CUT




                                                                                                                                                                                                                                                 t
                                                                                                                                                                                                                                                                                                                                                                                                    PROPOSED EARTHWORKS FILL



                                                                            X




                                                                                                                                                                                                                                                        t




                                                                                                                                                                                                                                                                                Ke
                                                                                                                                                                                                                                                               t
                                                                           X




                                                                                                                                                                                                                                                                                    rb
                                                                                                                                                                                                                                                                                     &
                                                              15                                                                                                                                                                                                                                                                                                                                  GEOTEXTILE FABRIC TO




                                                                                                                                                                                                                                                                                         Gu
                                                                                                                                                                                                                                                                       t




                                                                                                                                                                                                                                                                                            tte
                                                                                                                                                                                                                                                                                                                                                                                                  BE WRAPPED OVER




                                                                                                                                                                                                                                                                                             r
                                                                       X




                                                                                                                                                                                                                                                                                                                                                                                                  GRATE AND SECURED
                                                                                                                                                                                                                                                                                                                                                                                                  UNDER AS SHOWN




                                                                                                                                                                                                                                                                               t
                                                                                                                                           GARAGE
                                                                                                                                            FFL14.400                                                                                                                                                                                                                                                                                       FSL
                                                                       X




                                                                                                                                                                                                                                                                                        t
                                                              14 SF
                                                                                                                                                                                                                                                                                                                                                                                                                      ALLOTMENT
                                                                       X




                                                                                                                                                                                                                                                                                                  t
                                                                                                                                                                                                                                                                                                                                                                                                                          PIT




                                                                                                                                                                                                                                                                                                       t
                                                                   X




                                                                                                                                                                                                                                                                                                                                                                                                   FIELD INLET PROTECTION PP
                                                                                                                                                                                                                                                                                                                                                                                                   SCALE 1:20
                                                           13




                                                                                                                                                                                                                                                                                                              t
                                                                X




                                                                                                                                                                                                                                                                                                                      t
                                                                                                                                                                                                                                                                                                                                                                                      3.0m MAX                            3.0m MAX                      F42 GEOFABRIC
                                                              X




                                                                                                                                                                                                                                                                                                                                                                                                                      SPILL THRU WEIR                   FABRIC (TO AS 1304)




                                                                                                                                                                                                                                                                                                                              t
                                                                                                                                                                                                                                                                                                                  X                                                                                                    (IF REQUIRED)
                                                                                 CONSTRUCTION
                                                                                 ENTRY/EXIT
                                                                                                                                                                                                          GARAGE
                                                                                                                                                                                                                                                                                                                                                                                                                300
                                                              X




                                                                                                                                                                                                           FFL14.400                                                                                    X
                                                                                                                                                                                                                                                                                                                                                    600                                                                                                                    200




                                                                                                                                                                                                                                                                                                                                         t
                                                                                                                                                                                                                                                                                                                                                                          GROUND LEVEL
                                                       12




                                                                                                                                                                                                                                                                                              X
                                                                                                                                                                                                                                                                                                                                                    600
                                                                                                                                                                                                                                                                                    X                                                                                                                                                                   POSTS OR STEEL PICKETS
                                                                                       CE                                                                                                                                                                                                                                                                                                     SEDIMENT FENCE SF                                         DRIVEN 600mm INTO
                                                                                                                                                                                                                                                                           X   SF                                                                                                                                                                       GROUND
                                                                                                                                                                                                                                                                                                                                                                                              SCALE 1:100
                                                                                                                                                                                                                                                                   X
                                                       X   PP                                                                                                                                                                                                                                                                                                         SEDIMENT & EROSION CONTROL PROGRAM
                                                                   X             X           X
                                                                                 SF                                                                                                                                                                     X                                                                                                                       OBJECTIVE/TARGET            THE CONTRACTOR MUST COMPLY WITH ALL STATUTORY
                                                                                                                                                                                                                                                                                                                                                                                                            REGULATIONS AND MAINTAIN THEM DURING EARTHWORKS/
                                                                                                                                                                                                                                             X                                                                                                                                                              CONSTRUCTION. ALL PROVISIONS AND SPECIFICATIONS
                                                                                                 X




                                                                                                                                                                                                                                                                                                                                                                                                            OUTLINED WITH THE APPROVED ENVIRONMENTAL
                                                                                                                                                                                                                                                                                                                                                                                                            MANAGEMENT PLAN MUST BE ADHERED TO, ALONG WITH
                                                                                                                     12




                                                                                                                                                                                                                                     X                                                                                                                                                                      ALL EROSION AND SEDIMENT CONTROL MEASURES
                                                                                                                                                                                                                                                                                                                                                                                                            PRESCRIBED WITHIN THESE DRAWINGS BY THE
                                                                                                                                                                                                                                                              EL                                                                               NT
                                                                                                     X




      PHASING OF WORKS                                                                                                                                                                                                                                      NN                                                                               ME
                                                                                                                                                                                                                                                                                                                                                                                                            SITE ENGINEER
                                                                                                                                                                                                                                                        HA
                                                                                                                                                                                                                                                      &C                                                                                  IGN
                                                                                                                                                                                                                           X
                                                                                                                                                                                                                                                 RB                                                                                 Y   AL                                      MANAGEMENT                  THE SITE FOREMAN IS TO IDENTIFY AND CHECK THE
         PROVIDE SITE FACILITIES NEAR ENTRANCE, IF REQUIRED                                                                                                                                                                                  KE                                                          15                       RT                                            STRATEGY                    DIRECTION OF STORMWATER FLOWS AS SHOWN ON PLAN.
                                                                                                           X




                                                                                                                                                                                                                                                                                                      MIN m                 E
                                                                                                                                                                                                                       X                                                                                                 OP                                                                                 PROVIDE BARRIERS AND OTHER MEASURES SHOWN ON
         CONSTRUCT 'NO-GO- FENCING TO ALL VEGETATION PROTECTION AREAS                                                                                                                                                                                                                                                  PR           BERM (300mm MIN HEIGHT)
                                                                                                                                                                                                                                                                                                                                                                                                            PLAN TO PREVENT STORMWATER FLOWS OVER
                                                                                                                                                                                                                                                                                                                                                                                                            EMBANKMENTS, AND SEDIMENT INTO GULLY PITS
         CLEAR VEGETATION AND RETAIN MULCH FOR SITE USE. DO NOT STRIP TOPSOIL.                                                                                                                                                                                         NOMINALLY 200mm
                                                                                                                                                                                                               X                                                                                                                    RUN-OFF FROM PAD
                                                                                                                X




         ERECT SEDIMENT FENCING WITH PROGRESSIVE STRIPPING OF TOPSOIL (SF-01)                                   SF                                                                                                                                                                                                                                                              TASKS / ACTIONS             ERECT SEDIMENTATION BARRIERS AS DETAILED.
                                                                                                                                                                                                                                                                                                                                                                                                            STRATEGICALLY PLACE CHECK DAMS
         COMPLETE EARTHWORKS AND PROGRESSIVELY STABILISE WITH MULCH/LANDSCAPING
                                                                                                                                              PP                                                     X   SF                                                                                                                                                                                                 AROUND GULLY PITS
         DE-ESTABLISH WORK EQUIPMENT AND FACILITIES.
                                                                                                                         X




                                                                                                                                                                                                                                  GEOTEXTILE FABRIC                                                                                                                             PERFORMANCE                 THE SITE FOREMAN IS TO CHECK FOR EROSION AND
         ERECT 'NO-GO' FENCING AROUND COMPLETED WORKS TO PROHIBIT ACCESS.                                                                                                               X                                                                                                                                                                                       INDICATORS                  SEDIMENT FLOWS AT THE BASE OF EMBANKMENTS AFTER
                                                                                                                                                                                                                                  BIDUM U34 OR
                                                                                                                                                                                                                                  SIMILAR                                                                         3m                                                                                        SIGNIFICANT RAINFALL AND SHOULD ASCERTAIN THE
                                                                                                                                                                                                                                                                                                                   MIN                                                                                      WORKING EFFECTIVENESS OF CHECK DAMS DURING
                                                                                                                                 X




                                                                                                                                                                            X                                                                                                                                                                                                                               THIS WET WEATHER
                                                                                                                                                                                                                               UNBOUND PAVEMENT MATERIAL (GRAVEL)
                                                                                                                                                                                                                                                                                                                                                                                FREQUENCY /                 SITE FOREMAN TO MONITOR PERFORMANCE AFTER
                                                                                                                                                                X                                                              TO GRADING 'B', TABLE 9 OF QUEENSLAND                                                                                                            DEADLINE                    EVERY HEAVY DOWNFALL
                                                                                                                                           X




                                                                                                                                                                                                                               TRANSPORT SPECIFICATION MRSS11.04 -
        NOTE:                                                                                                                                                                                                                  EXCLUDE MATERIAL FINER THAN AS SIEVE                                                                                                             RESPONSIBILITY              THE SITE FOREMAN IS RESPONSIBLE FOR ALL INSPECTIONS

        CUT/FILL SHADING TO FINISHED
                                                                                                                                                     X
                                                                                                                                                         12                                                                    2.36mm                                                                                                                                           REPORTING REVIEW            SITE WORKMEN ARE TO ADVISE THE FOREMAN IF ANY
        SURFACE LEVEL.                                                                                                                                                                                                                       TEMPORARY CONSTRUCTION ENTRY / EXIT CE                                                                                                                         SEDIMENT & EROSION CONTROL DEVICES ARE FAILING

                                                                                                                                                                                                                                              N.T.S.                                                                                                                            CORRECTIVE ACTIONS          THE SITE FOREMAN IS TO REPORT AND ORDER THROUGH
                                                                                                                                                                                                                                                                                                                                                                                                            SUPERVISOR, EXTRA BARRIER OR CHECK DAMS AS
                                                                                                                                                                                                                                                                                                                                                                                                            REQUIRED



                                                                                                                                                                                                                                                                                                                                             PROJECT:                                                                                                             JOB NUMBER
REV DATE DESCRIPTION                                            BY         CHKD                                                                SCALE                                                           APPROVED
                                                                                                                                                                                                                                                                                                                                                                                                                                                                      1537
 1   24.03.17   APPROVAL ISSUE                                    JG        CL
                                                                                      DATUM           AHD                                                                                                                                                                                                                                                                                                                                                    SHEET:        OF
                                                                                      DESIGN          DK             0          15              30             45               60             75m
                                                                                                                                                                                                              .................                                                                                                                                                                                                                                        3         5


                                                                                                                                                                                                         Director: PETER BARLOW                                                                                                              DRAWING TITLE:                                                                                                  DRAWING NUMBER          REV
                                                                                      DRAWN           JG
                                                                                                                                                                                                                (RPEQ 1330)
                                                                                      DESIGN CHECK    PB                                     SCALE 1:1500 A3
                                                                                                                                                                                                     DRAWING STATUS
                                                                                                                                                                                                                                                                        07 5443 8285
                                                                                                                                                                                                                                                                                                                                                                                                                                                                  R03                 1
                                                                                                                                                                                                                                                                       [email protected]     www.barlowshelley.com.au
                                                                                                                 This drawing is not to be copied or amended without written permission from
                                                                                      DATE           20-03-17    Barlow Shelley Consulting Engineers
                                                                                                                                                                                                                   FOR APPROVAL                                        PO Box 899, Maroochydore,4558 ABN 89 215 591 077

Page 4

                                                                                                                                                                                                    t
                                 4.90




                     1.10        2.80
                        B85                    meters
                       Width               :    1.94
                       Track               :    1.77
                       Lock to Lock Time   :    6.0
                       Steering Angle      :    30.0
                      B85 PASSENGER VEHICLE




                                                                                                                                                                                                                                                                      PROJECT:             JOB NUMBER
REV DATE DESCRIPTION                                    BY   CHKD                                                           SCALE                                                      APPROVED
                                                                                                                                                                                                                                                                                                1537
 1   24.03.17   APPROVAL ISSUE                          JG    CL
                                                                    DATUM           AHD                                                                                                                                                                                                SHEET:        OF
                                                                    DESIGN          DK         0             15              30             45              60              75m
                                                                                                                                                                                     .................                                                                                           4        5


                                                                                                                                                                                  Director: PETER BARLOW                                                              DRAWING TITLE:   DRAWING NUMBER         REV
                                                                    DRAWN           JG
                                                                                                                                                                                         (RPEQ 1330)
                                                                    DESIGN CHECK    PB                                    SCALE 1:1500 A3
                                                                                                                                                                                  DRAWING STATUS
                                                                                                                                                                                                            07 5443 8285
                                                                                                                                                                                                                                                                                            R04                1
                                                                                                                                                                                                           [email protected]     www.barlowshelley.com.au
                                                                                              This drawing is not to be copied or amended without written permission from
                                                                    DATE           20-03-17   Barlow Shelley Consulting Engineers
                                                                                                                                                                                        FOR APPROVAL       PO Box 899, Maroochydore,4558 ABN 89 215 591 077

Page 5

CONCRETE NOTES:
C1.      ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF
         THE RELEVANT CURRENT AUSTRALIAN STANDARD CODES (AS3600, AS2870 & AS1379), BUILDING
         BY-LAWS AND THE ORDINANCES OF THE RELEVANT LOCAL AUTHORITY
C2.      CONCRETE SPECIFICATION                                                                                                                                                                                                                                                                                    GRANT STREET
                                                    MAX.        MAX.               MIN.                                                                                                                                                                                                                                                                                                                        RETAINING WALL
                                                                                                                                                                                                                                                                                                                                                                                                               RW2 AS DETAILED.
                   ELEMENT        GRADE            SLUMP     AGGREGATE            COVER
                                                    (mm)      SIZE (mm)            (mm)                                                                                                                                                                                                    320° 59' 40"                                                  RW2        140° 59' 40"                          142° 55' 20"




                                                                                                                                                                                                                                                                                                                                                  RW2




                                                                                                                                                                                                                                                                                                                                                                    RW2
                                                                                                                                                                                                                                                                                             14.392 m                                                                    13.827 m                           4.975 m
           BLOCK CORE FILL          N20             230             6                55                                                                                                                                         0"
                                                                                                                                                                                                                          05' 3
                                                                                                                                                                                                                     300°                                                                           RW2                                                                                                  RW2
C3.      WHERE FLOOR SLABS ARE TO BE TILED, THE FOLLOWING RECOMMENDATIONS ARE MADE, IN                                                                                                                                       22 m
         ORDER TO MINIMIZE THE THE EFFECTS OF SHRINKAGE:-                                                                                                                                                               10.2                                                                                                                             RW2
 -       PROVISION OF SL92 SLAB MESH (OR EQUIVALENT)                                                                                                                                                                                                                                                                                                                                                           RW
 -       PLACEMENT OF TILES SHOULD BE DELAYED FOR AS LONG AS POSSIBLE (PREFERABLY 3                                                                                                                                                                      2                                                             RW1                                                   RW1                                 1
                                                                                                                                                                                                                                                    RW                                      RW1
         MONTHS OR MORE)
                                                                                                                                                                                0"
-        USE OF ELASTIC TILE ADHESIVES AND PROVISION OF FLEXIBLE JOINTS BETWEEN TILES.                                                                                  1  '2
C4.      ALL CONCRETE TESTING IS TO BE CARRIED OUT BY A NATA REGISTERED LABORATORY, IN                                                                              7°2              m
                                                                                                                                                               27               31                                                                        1
         STRICT ACCORDANCE WITH THE REQUIREMENTS OF AS1012.                                                                                                               6.9                                                                       RW
         THE FOLLOWING TESTING SCHEDULE IS TO BE ADOPTED IN ADDITION TO THE REQUIREMENTS
         OF THE MANUFACTURERS QUALITY ASSURANCE PROGRAM.
 -       A MINIMUM OF ONE TEST (3 CYLINDERS) TO BE TAKEN FROM EACH ELEMENT CAST ON ANY                                                                                                                           2
                                                                                                                                                                                                               RW                                                                                   RETAINING WALL




                                                                                                                                                                                                                                                                                                                                                                                                                                   RW1
         GIVEN DAY (EG. COLUMNS, FOOTINGS, ETC)
                                                                                                                                                         .0m




                                                                                                                                                                                                                                   2
                                                                                                                                                       20




                                                                                                                                                                                                                                RW
 -       A MINIMUM OF ONE TEST (3 CYLINDERS) TO BE TAKEN FROM EACH CONCRETE STRENGTH                                                                                                                                                                                                                RW1 AS DETAILED.
         GRADE CAST ON ANY GIVEN DAY                                                                                                                            .5m
 -       A MINIMUM OF ONE TEST (3 CYLINDERS) TO BE TAKEN FROM EACH 50M³ OR PART THEREOF
                                                                                                                                                             19
         CAST ON ANY GIVEN DAY FOR EACH STRENGTH GRADE.                                                                                                                    .0m
                                                                                                                                                                        19




                                                                                                                                                                                                                                       RW3
C5.      SLABS TO BE CURED AND KEPT MOIST FOR 7 DAYS (MINIMUM)                                                                                                                                                                                                  RETAINING WALL
C6.      NO CONCRETE TO BE POURED WHEN SITE TEMPERATURE EXCEEDS 35° C OR FALLS BELOW 5°C                                                                                                     m                                                                  RW3 AS DETAILED.
                                                                                                                                                                                     1   8.5
C7.      CONSTRUCTIONS JOINTS OR POUR BREAKS WHERE NOT SHOWN ON THE APPROVED PLANS OR
                                                                                                                                                                                                 .0m




                                                                                                                                                                                                                       2
         DETAILS SHALL BE LOCATED AND FORMED TO THE APPROVAL OF THE ENGINEER.




                                                                                                                                                                                                                     RW
                                                                                                                                                                                             18
C8.      NO PENETRATIONS, RECESSES OR CHASES OTHER THAN THOSE SHOWN ON THE STRUCTURAL
         DRAWINGS SHALL BE MADE IN CONCRETE MEMBERS WITHOUT THE APPROVAL OF THE




                                                                                                                                                                                                                                                                                                                                                                                                                             232° 55' 20"
                                                                                                                                                                                                         .5m




                                                                                                                                                                                                                                                                                                                                                                                                                                            33.711 m
         ENGINEER.                                                                                                                                                                                     17
C9.      AT PENETRATIONS IN SLABS, UNLESS OTHERWISE DETAILED, REINFORCEMENT MUST NOT BE




                                                                                                                                                                                                                                             RW3
         CUT BUT SHALL BE GATHERED EQUALLY TO EACH SIDE OF THE PENETRATIONS AND EXTRA                                                                                                                               .0m
                                                                                                                                                                                                               17
         REINFORCEMENT PROVIDED BETWEEN THE PENETRATIONS AS DIRECTED BY THE ENGINEER.
         WHERE MORE THAN ONE (1) PARALLEL SLAB MESH WIRE IS CUT, PROVIDE 1/N12 (1200 LONG)
                                                                                                                                                                                                                               .5m
         TRIMMER BAR EACH SIDE OF PENETRATION.                                                                                                                                                                            16
                                                                                                                                                                                                                                                                                                                                        RETAINING WALL
BLOCK MASONRY WALL SPECIFICATION:                                                                                   REINFORCEMENT NOTES:                                                                                                           RW                                                                                   RW5 AS DETAILED.
M1. ALL CONCRETE BLOCK MASONRY WORK IS TO BE EXECUTED IN ACCORDANCE WITH THE CURRENT          R1.                               ALL STEEL REINFORCEMENT SHALL BE IN ACCORDANCE WITH THE                                                              3
     EDITION OF:                                                                                                                REQUIREMENTS OF THE RELEVANT CURRENT AUSTRALIAN
              AS 3700 - SAA MASONRY CODE                                                                                        STANDARD CODES (AS3600 & AS4671).
              AS 2733 - CONCRETE MASONRY UNITS                                                R2.                               REINFORCEMENT IS PRESENTED DIAGRAMMATICALLY. IT IS NOT
              AS 3600 - CONCRETE STRUCTURES                                                                                     NECESSARILY SHOWN IN TRUE PROJECTION.




                                                                                                                                                                                                                                                                  18
                                                                                                                                                                                                                                                                    8°
              AS 123 - MORTAR & MASONRY CONSTRUCTION                                          R3.                               PROVIDE THE ENGINEER WITH 48 HOURS NOTICE OF




                                                                                                                                                                                                                                                                       40
                                                                                                                                                                                                                                                               39




                                                                                                                                                                                                                                                                                                                                                                     5
                                                                                                                                                                                                                                                                                                                              RW




                                                                                                                                                                                                                                                                                                                                                                  RW
              AS 2699 - MASONRY WALL TIES




                                                                                                                                                                                                                                                                         '2
                                                                                                                                REINFORCEMENT BEING READY FOR INSPECTION.




                                                                                                                                                                                                                                                                 .90




                                                                                                                                                                                                                                                                                                                                                                                    RW4
                                                                                                                                                                                                                                                                          0"




                                                                                                                                                                                                                                                                                                                                    5
                                                                                                                                                                                                                                                                   7m
              AS 2975 - MASONRY CONSTRUCTION ACCESSORIES.                                     R4.                               NO CONCRETE IS TO BE POURED WITHOUT THE PRIOR
M2. 'CLEAN OUT' BLOCKS TO BE USED AT FIRST COURSE ABOVE EACH FLOOR AND ALL MORTAR TO BE                                         APPROVAL OF THE ENGINEER.
     REMOVED FROM CORES PRIOR TO CONCRETE FILLING.                                            R5.                               SPLICES IN REINFORCEMENT SHALL BE MADE ONLY IN THE
M3. CONCRETE MIX USED TO FILL CAVITY TO HAVE CHARACTERISTIC COMPRESSIVE STRENGTH OF 20MPa                                       POSITIONS SHOWN. WHERE NOT SPECIFIED, LAPS SHALL BE IN
     (F'C), MAXIMUM SLUMP 230mm, MAXIMUM AGGREGATE SIZE 6mm (MAXIMUM 6 COURSE HEIGHT PLACED                                     ACCORDANCE WITH AS3600 AND NOT LESS THAN: N12 - 400, N16 -
                                                                                                                                                                                                                                                                                                                                                                         4           RETAINING WALL
     AT ONE TIME).                                                                                                              500, N20 - 650, N24 -800, N28 - 1100, N32 - 1400, N36 - 1700.                                                                                                                                                                      RW
M4. BLOCKWORK MUST NOT BE BUILT ON CONCRETE SLABS OR BEAMS UNTIL FORMWORK SUPPORTING          R6.                               WELDING OF REINFORCEMENT WILL NOT BE PERMITTED.                                                                                   INDICATES APPROX.                                                                                                  RW4 AS DETAILED.
     SAME HAS BEEN REMOVED.                                                                   R7.                               REINFORCEMENT MUST NOT BE CONTINUOUS THROUGH                                                                                      LOCATION OF DRAINAGE
M5. MORTAR TO BE MIXED IN THE PROPORTION OF 1: 0.5: 4.5 CEMENT: HYDRATED LIME: SAND                                             CONSTRUCTION JOINTS.                                                                                                              PIT TO BE REMOVED.
     (OR EQUIVALENT CEMENT - SAND MORTAR PLASTICISER) AND MORTAR COMPRESSIVE STRENGTH AT R8.
                                                                                                                                                                                                                                                                                                                                                    142° 55' 20"                          322° 55' 20"
                                                                                                                                SPACEMENT OF SUFFICIENT "STOOLS" UNDER MAIN BOTTOM
     28 DAYS TO BE 20MPa MINIMUM.                                                                                               REINFORCEMENT BAR AND TOP CROSS BAR IN SLABS TO ALLOW                                                                                                                                           4                       1.786 m
                                                                                                                                                                                                                                                                                                                             RW                                                            13.695 m
M6. CHARACTERISTIC COMPRESSIVE STRENGTH OF BLOCK F'UC = 15MPa U.N.O.                                                            ADEQUATE SUPPORT IN CORRECT POSITION DURING CONCRETING
                                                                                                                                                                                                                                                                                                                                                    SCREW PIERS 1200 CLEAR                 INDICATES APPROX.




                                                                                                                                                                                                                                                                                                                                          "
M7. COVER TO REINFORCEMENT 20mm MIN. FROM INSIDE FACE OF BLOCK UNLESS OTHERWISE DETAILED,                                       (BUT NOT GENERALLY GREATER THAN 900mm SPACINGS). SUPPLY




                                                                                                                                                                                                                                                                                                                                        50
                                                                                                                                                                                                                                                                                                                                                    OF SEWER FOUND 300 MIN




                                                                                                                                                                                                                                                                                                                                    6'
     NOTED OR SPECIFIED.                                                                                                        AND LAY STEEL FABRIC IN FLAT SHEETS AT SPLICES. PROVIDE 225                                                                                                                                                                                                LINE OF SEWER MAIN.




                                                                                                                                                                                                                                                                                                                                °5
                                                                                                                                                                                                                                                                                                                                         8m
                                                                                                                                                                                                                                                                                                                                                    BELOW INVERT.




                                                                                                                                                                                                                                                                                                                              93
M8. PROVIDE STARTER BARS TO MATCH VERTICAL REINFORCEMENT 700 X 400 LEG UNLESS OTHERWISE                                         MINIMUM OVERLAP OF TRANSVERSE WIRES TO ALL EDGES OF




                                                                                                                                                                                                                                                                                                                                        6.2
     DETAILED, NOTED OR SPECIFIED.                                                                                              SLAB FABRIC LAPS. (IE TWO WIRES OF EACH SHEET OVERLAPPING                                                                                                                                                     INDICATES APPROX. MANHOLE, ISOLATE
M9. PROVIDE TIE BARS TO MATCH VERTICAL REINFORCEMENT.                                                                           PLUS 25mm) PROVIDE 'L' BARS TO ALL BEAM CORNERS AND                                                                                                                                                           RW4 FOOTING WITH 10mm ABLEFLEX.
M10. PROVIDE 290D BOND BEAM ABOVE AND BELOW ALL OPENINGS REINFORCED WITH 2-N12 HORIZONTAL                                       INTERSECTIONS. 500 MINIMUM LAPS.
     WHERE SILL OR LINTEL REINFORCEMENT IS NOT NOMINATED.                                                                       REINFORCEMENT SYMBOLS:                                                                                                                                                                              INDICATES APPROX. DRAINAGE PIT.
M11. PROVIDE VERTICAL CONSTRUCTION JOINTS AT 6000 MAX CRS TO THE APPROVAL OF THE                                                N GRADE 500 MPa DEFORMED BAR
     SUPERINTENDENT UNLESS OTHERWISE DETAILED, NOTED OR SPECIFIED. VERTICAL CONSTRUCTION                                        SL GRADE 500 MPa DEFORMED SLAB MESH
     JOINTS ARE NOT REQUIRED IF THE SPECIFIED BOND BEAM IS CONTINUOUS OVER WITH VERTICAL WALL
     STEEL CORE FILLED IN REINFORCED BOND BEAM AND CORES ONLY.
                                                                                                                                Y GRADE 410 MPa DEFORMED BAR
                                                                                                                                S GRADE 250 MPa DEFORMED BAR - POOLS CONSTRUCTION
                                                                                                                                                                                                                                                   RETAINING WALLS SITE LAYOUT PLAN 1:200 @ A3
M12. PROVIDE N12 VERTICAL REINFORCEMENT AS NOMINATED ON PLAN AND AT 1200 MAX. CRS. ABOVE AND                                    R GRADE 250 MPa PLAIN BAR                                                                                          REFER TO ARCHITECTURAL SPECIFICATIONS FOR ALL SET OUT DIMENSIONS, FINISHING, FLASHING, SURFACE FALLS AND WATER PROOFING. etc
     BELOW ALL OPENINGS UNLESS OTHERWISE DETAILED, NOTED OR SPECIFIED.

                                                                                                                                                                                                                                                                                                                     PROJECT:                                                                                            JOB NUMBER
REV DATE DESCRIPTION                         BY     CHKD DRAWN
                                                             I GDETAL
                                                                    IS                                              SCALE                                                                   APPROVED                                                                                                                 PROPOSED RETAINING WALLS                                                                                1537
 1    24.03.17   APPROVAL ISSUE               NN      PB                                                                                                                                                                                                                                                             NO.27-29 GRANT STREET, NOOSA
                                                           DATUM            AHD                                                                                                                                                                                                                                                                                                                                     SHEET:                    OF
                                                           DESIGN           DK
                                                                                      0              2              4               6              8                10m                  .................                                                                                                           G & M ROBERTSON                                                                                                   1               5


                                                                                                                                                                                            DANIEL KENNA                                                                                                             DRAWING TITLE:                                                                              DRAWING NUMBER                            REV
                                                           DRAWN            NN
                                                                                                                   SCALE 1:200 A3                                                            (RPEQ 15522)                                                                                                           RETAINING WALLS LAYOUT PLAN
                                                           DESIGN CHECK     DK
                                                                                                                                                                                DRAWING STATUS
                                                                                                                                                                                                                                                        p 07 5443 8285                                                                                                                                                 ST01                                 1
                                                                                      This drawing is not to be copied or amended without written permission from                                                                                       e [email protected] w www.barlowshelley.com.au
                                                           DATE           MAR 2017    Barlow Shelley Consulting Engineers                                                                  FOR APPROVAL                                                 a PO Box 899 Maroochydore 4558 ABN 89 215 591 077

Page 6

                                                                 SELECTED DRAIN (CONCRETE
                                                                 SPOON OR GRATED CHANNEL)                                                                                                                                                            RW2 FOOTING AS DETAILED.


                                                                                       CAPPING BLOCK OR DOMED                                                                                                                                                          SELECTED DRAIN (CONCRETE
                                                                                       CORE FILL (TYPICAL)                                                                                                                                                             SPOON OR GRATED CHANNEL)


                                                                                                                                                                                                                                                                                                  CAPPING BLOCK OR DOMED
                                                                                                                                                                                                                                                                                                  CORE FILL (TYPICAL)




                                                                                                                                             1200Ht - 200 SERIES
                                                                                       N12 @ 400CRS HORIZ.




                                                                                                                                                                                                                                            FILL
                                                                                                                                                                                                                      400
                                                                                                                                                                                                                                                                                                  10mm ABLEFLEX.

                                                                                       N12 @ 400 CRS, EACH WAY.



                                                                                       SELECTED WATERPROOFING                                                                                                                                                                                     N16 @ 400 CRS VERT.
                                                                                       TANKING WITH COREFLUTE.
                                                                                                                                                                                                                                                                                                  N12 @ 400CRS HORIZ.
                                                                                                                                                                                                THICKEN FOOTING
                                                                                       2/Ø90 AGG. PIPES 1:100 MIN                                                                               EDGE 300W TO BEAR
                                                                                       FALL DISCHARGE CLEAR OF                                                                                  ONTO 300 SERIES
                                                    55 COVER                           WALL.                                                                                                    MASONRY AS SHOWN.                                                                                                                         SELECTED FREE                   SELECTED DRAIN (CONCRETE
                                                                                                                                                                                                                                                                                                  N16 @ 400CRS HORIZ.
                                                                                                                                                                                                                                                                                                                                          DRAINING BACKFILL.              SPOON OR GRATED CHANNEL)




                                                                                                                                             800Ht - 300 SERIES
                                                                                                                                                                                                                                                                                                  1600Ht MAX.
                                 800 - 300 SERIES




                                                                                                                                                                                                 SELECTED
                                                                                                                                                                                                 WATERPROOFING                                                                                                                                                                           CAPPING BLOCK OR DOMED
                                                                                                                                                                                                 TANKING WITH                                                                                                                                                                            CORE FILL (TYPICAL)
                                                                                                                                                                                                 COREFLUTE.




                                                                                                                                   FILL
                                                                                                                            400




                                                                                                                                                                                                                      2800Ht - 300 SERIES
                                                                                   'C' BLOCKS.
                                 300




                                                                                                                                                                                                                                                                                                                                                                                         N12 @ 400CRS HORIZ.
                                                                                                                                                                                                                                                                                                                                    SELECTED




                                                                                                                                                                                                                                                                                                                                                                                                                        1800Ht - 200 SERIES
                                                                                                                                                                   THICKEN FOOTING                                                                                                                                                  WATERPROOFING
     3-N16 100 OVER PIERS,                                                                                                                                         EDGE 300W TO BEAR                                                                                                                                                TANKING WITH
     50 TOP COVER.                                                                      1400                                                                       ONTO 300 SERIES                                                                                                                                                  COREFLUTE.
                                                                                                                                                                   MASONRY AS SHOWN               GRAVEL BACK FILL.                                                                               N20 STARTERS @
                                                                                     RW2                                                                           OPPOSITE, WHERE                                                                                                                400CRS, 1600 LAPS.
     N20 BAR, 450 LONG.                                                                                                                                            APPLICABLE.                                                                                                                    N16 @ 400CRS HORIZ.
                                                                                                            N12 @ 400 CRS EACH                                                                                                                                                                                                                                                           N12 @ 400CRS, VERTICAL.
                                                                                                            WAY TOP & BOTTOM,
                                                                                                                                                                                                  A14 GEOTEXTILE                                                                                                                    GRAVEL BACK FILL.
                                                                                                            50 COVER. (TYPICAL)
                                                                                                                                                                                                  FABRIC.
                                                                             N16 STARTER BARS @                                                                                                                                                    55 COVER                                                                                                    55 COVER
                                                                                                                                                                                                                                                                                                  2/Ø90 AGG. PIPES 1:100 MIN                                                             2/Ø90 AGG. PIPES 1:100 MIN
                                                                             200CRS, 800 MIN LAP.
                                                                                                                                                                                                                                                                                                  FALL DISCHARGE CLEAR OF                                                                FALL DISCHARGE CLEAR OF
                                                                                                                                                                                                                                                                                                  WALL.                             A14 GEOTEXTILE                                       WALL.
                                                                             10T SWL SCREW PIER @ 2400CRS.                                                                                                                                                                                                                          FABRIC.
                                                                             FOUND BELOW BASE OF BOTTOM
                                                                                                                                                                                                                                                                                                  'C' BLOCKS.                                                                            'C' BLOCKS.
                                                                             TERRACES. CONTRACTOR TO CONFIRM
                                                                             CAPACITY & FOUNDING DEPTH.


                                                    RW2 - RETAINING WALL DETAIL                                                                                                                                       300
                                                                                                                                                                                                                                                                                                                                                                                         N16 STARTER BARS @
                                                                                                                                                                                                                                                                                                                                                                                         200CRS, 800 MIN LAP.
                                                    SCALE 1:20
                                                                                                                                                                                                                                                                                                                            2400

                                                                                                                                                                                                                                                                                                                         RW1                               N16 @ 400 CRS EACH
                                                                                                                                                                                                                                                                                                                                                           WAY TOP & BOTTOM,
                                                                                                                                                                                                                                                                                                                                                           50 COVER. (TYPICAL)


                                                                                                                                                                                                                                                                  RW1 - RETAINING WALL DETAIL
                                                                                                                                                                                                                                                                  SCALE 1:20

                                                                                                                                                                                                                                                                                                                         PROJECT:                                                                              JOB NUMBER
REV DATE DESCRIPTION                                             BY   CHKD DRAWN
                                                                               I GDETAL
                                                                                      IS                                                    SCALE                                                   APPROVED                                                                                                             PROPOSED RETAINING WALLS                                                                 1537
 1   24.03.17   APPROVAL ISSUE                                   NN    PB                                                                                                                                                                                                                                                NO.27-29 GRANT STREET, NOOSA
                                                                            DATUM                  AHD                                                                                                                                                                                                                                                                                                   SHEET:        OF
                                                                            DESIGN                 DK
                                                                                                              0             0.2            0.4                      0.6    0.8          1.0m      .................                                                                                                      G & M ROBERTSON                                                                           2                          5


                                                                                                                                                                                                    DANIEL KENNA                                                                                                         DRAWING TITLE:                                                                  DRAWING NUMBER                           REV
                                                                            DRAWN                  NN
                                                                                                                                            SCALE 1:20 A3                                            (RPEQ 15522)                                                                                                        RETAINING WALLS SECTION DETAILS
                                                                            DESIGN CHECK           DK
                                                                                                                                                                                               DRAWING STATUS
                                                                                                                                                                                                                                                              p 07 5443 8285                                                                                                                                ST02                                   1
                                                                                                                                                                                                                                                              e [email protected] w www.barlowshelley.com.au
                                                                            DATE                 MAR 2017
                                                                                                              This drawing is not to be copied or amended without written permission from
                                                                                                              Barlow Shelley Consulting Engineers                                                  FOR APPROVAL                                               a PO Box 899 Maroochydore 4558 ABN 89 215 591 077
                                                                                                                                                                                                                                                                                                                         SHEET 1 OF 3

Page 7

                                                                                            SELECTED DRAIN (CONCRETE
                                                                                            SPOON OR GRATED CHANNEL)

                                                                                                                                                                                                                                                                                                                     HANDRAIL BY OTHERS.
                                                                                                                                CAPPING BLOCK OR DOMED
                                                                                                                                                                                                                                                                DRIVEWAY AS SPEC'D.
                                                                                                                                CORE FILL. (TYPICAL)
                                 1200Ht - 200 SERIES




                                                                                                                                                                                            1200Ht - 200 SERIES
                                                       GRAVEL                                                                   N12 @ 400CRS HORIZ.
                                                       BACK FILL.                                                                                                                                                                                                                                                    N12 @ 400CRS SLAB TIES.
                                                                                                                                                                                                                                                                                                                     (600 LAP, TYPICAL)
                                                                                                                                                                                                                                             A14 GEOTEXTILE
                                                                                                                                                                                                                                             FABRIC.

                                                                                                                                N12 @ 400 CRS, VERTICAL.
                                                       A14                                                                                                                                                                                   GRAVEL BACK FILL.
                                                       GEOTEXTILE




                                                                                                                                                                                                                                                                                                                                                1800Ht - 200 SERIES
                                                       FABRIC.                                                                                                                                                                                                                                                       N12 @ 400 CRS, EACH WAY.

                                                                                                                                                                                                                                             A14 GEOTEXTILE
                                                                                                                                2/Ø90 AGG. PIPES 1:100 MIN                                                                                   FABRIC.
                                                                                                                                                                                                                                                                                                                     N12 @ 400CRS HORIZ.
                                                                                                                                FALL DISCHARGE CLEAR OF
                                                       SELECTED                                                                 WALL.
                                                       WATERPROOFING                                                                                                                                                                         2/Ø90 AGG. PIPES 1:100




                                                                                                                                                                                            800Ht - 300 SERIES
                                 800 - 300 SERIES




                                                       TANKING WITH                                        200                                                                                                                               MIN FALL DISCHARGE                                                      SELECTED WATERPROOFING
                                                                     55 COVER
                                                       COREFLUTE.                                                                                                                                                                            CLEAR OF WALL.                                                          TANKING WITH COREFLUTE.

                                                                                                                                                                                                                                                                                                                  55 COVER
                                                                                                                                                                                                                                                               SL72 MESH,
                                                                                                                                                                                     FILL
                                                                                                                                                                               400
                                                                                                                                                                                                                                                               40 COVER.
                                                                                                                       'C' BLOCKS.                                                                                                                                                                                    'C' BLOCKS.
                                 300




                                                                                                                                                                                                                                                                                                                                                300
                                                                                                                                                                                                                                                                                                                     N16 STARTER BARS @
                                                                                                                                                                                                                                                                                                                     200CRS, 800 MIN LAP.


                                                                                                    1400                                                                                                                                                                          1400                                   3-N16 1500 LONG,
                                                                                                                                                                                                                                                                                                                         50 TOP COVER.
                                                                                              RW3                                                                                                                                                                           RW4                                          N20 BAR, 450 LONG.

                                                                                   N12 @ 400CRS EACH                              N16 STARTER BARS @                                                                                                      N12 @ 400CRS,
                                                                                   WAY TOP & BOTTOM,                              200CRS, 800 MIN LAP.                                                                                                    BOTTOM 50 COVER.
                                                                                   50 COVER. (TYPICAL)

                                                       RW3 - RETAINING WALL DETAIL                                                                                                                                                        RW4 - RETAINING WALL DETAIL
                                                       SCALE 1:20                                                                                                                                                                         SCALE 1:20




                                                                                                                                                                                                                                                                                                 PROJECT:                                                                 JOB NUMBER
REV DATE DESCRIPTION                                         BY     CHKD DRAWN
                                                                             I GDETAL
                                                                                    IS                                                   SCALE                                                                     APPROVED                                                                      PROPOSED RETAINING WALLS                                                      1537
 1   24.03.17   APPROVAL ISSUE                                NN     PB                                                                                                                                                                                                                          NO.27-29 GRANT STREET, NOOSA
                                                                          DATUM               AHD                                                                                                                                                                                                                                                                     SHEET:        OF
                                                                          DESIGN              DK
                                                                                                           0             0.2            0.4             0.6            0.8           1.0m                         .................                                                              G & M ROBERTSON                                                                3        5


                                                                                                                                                                                                                   DANIEL KENNA                                                                  DRAWING TITLE:                                                       DRAWING NUMBER         REV
                                                                          DRAWN               NN
                                                                                                                                         SCALE 1:20 A3                                                              (RPEQ 15522)                                                                 RETAINING WALLS SECTION DETAILS
                                                                          DESIGN CHECK        DK
                                                                                                                                                                                            DRAWING STATUS
                                                                                                                                                                                                                                      p 07 5443 8285                                                                                                                     ST03                 1
                                                                                                                                                                                                                                      e [email protected] w www.barlowshelley.com.au
                                                                          DATE              MAR 2017
                                                                                                           This drawing is not to be copied or amended without written permission from
                                                                                                           Barlow Shelley Consulting Engineers                                                                     FOR APPROVAL       a PO Box 899 Maroochydore 4558 ABN 89 215 591 077
                                                                                                                                                                                                                                                                                                 SHEET 2 OF 3

Page 8

                     CAPPING BLOCK OR




                                                                                                                                                                                                                                              KN AT
                     DOMED CORE FILL




                                                                                                                                                                                                                                                   S
                                                                                                                                                                                                                                           IC RO
                                                                                                                                                                                                                                                ES
                     (TYPICAL)




                                                                                                                                                                                                                                         TH TH
                                                                                                                                                                                                                                                             SL92 MESH,




                                                                                                                                                                                                                                             5
                                                                                                                                                                                                                                          12
                                                                                                                                                                                                                                                             50 COVER.
                                  WATER FEATURE
                                    BY OTHERS




                                                                                            1200Ht - 200 SERIES
                     N12 @ 400CRS HORIZ.
                                                                                                                                                                                      RETAINING                                                                                            SL92 MESH,
                                                                                                                                                                                      WALL RW2                                                                                             50 COVER.
                                                                                                                                                                                      FOOTING.
                     N12 @ 400 CRS,




                                                                                                                                                                                                                                                                                           KN AT
                     EACH WAY.




                                                                                                                                                                                                                                                                                        IC R O
                                                                                                                                                                                                                                                                                               S
                                                                                                                                                                                                                                                                                             ES
                                                                                                                                                                                                                                                                                      TH T H
                     SELECTED WATERPROOFING




                                                                                                                                                                                                                                                                                          5
                                                                                                                                                                                                                                                                                       12
                                                                                                                      DRIVEWAY AS SPEC'D.
                     TANKING WITH COREFLUTE.
                                                                                                                                                                                      RETAINING                                         APPROVED
                     'C' BLOCKS.                                                                                                                                                                                                      COMPACTED FILL
                                                                                                                                                                                      WALL RW2.
       200




                                                                                                                  N12 STARTER BARS @                                                                                                                   N12 DOWELS @
                                                          1000                                                    400CRS, 600 MIN LAP.                                                                                                                 300CRS, 600 LAP.
                                                                                                                                                                                                                    CONTINUOUS MOISTURE

                SL72 MESH,                  RW5                       N12 @ 400 CRS EACH
                                                                                                                                                                                                                    BARRIER ON COMPACTED
                                                                                                                                                                                                                    SAND BED.
                                                                                                                                                                                                                                                       RETAINING WALL
                                                                      WAY TOP & BOTTOM,                                                                                                                                                                RW2 FOOTING.
                40 COVER.
                                                                      50 COVER. (TYPICAL)


                      RW5 - RETAINING WALL DETAIL                                                                                                                                TYPICAL CONCRETE STAIR DETAILS
                      SCALE 1:20                                                                                                                                                 SCALE 1:20


                        NOTE: MIN. BOULDER MASS TO BE 500Kg
                        TYPICAL. ANGULAR BOULDERS TO BE USED                                                              400
                        TO PROVIDE MECHANICAL INTERLOCK.                                                                 MIN.




                                                                                 1
                                            WALL HEIGHT




                                                                        2
                                      'H'




                                                                                                                                   A14 GEOTEXTILE
                                                                                                                                   FABRIC.                                            BOULDER RETAINING WALL
                                                                                                                                                                                       WALL HEIGHT                        IN NATURAL
                                                                                                                                                                                                                                                  "W" WIDTH
                                                                                                                                                                                           "H"                              SOIL "D"
                                                                                                                                                                                       UP TO 1000mm                             300                    350
                                                                                                                                   CONCRETE BASE
                                                                                                                                   300 DEEP.                                                  1500mm                            500                    500
                                            OF TOE
                                            DEPTH
                                      'D'




                                                                                                                                                                                              2000mm                            700                    750

                                                                                                                                   Ø100 AGG. DRAIN,
                                                                                                                                   DISCHARGE FREE
                                                                                                                                   OF WALL.
                                                                       'W'
                                                                 MIN. W
                                                                        ID
                                                                 AT BA TH
                                                                        SE


                      BOULDER RETAINING WALL DETAIL
                      NOT TO SCALE
                                                                                                                                                                                                                                                                                                                             PROJECT:                              JOB NUMBER
REV DATE DESCRIPTION                                             BY    CHKD DRAWN
                                                                                I GDETAL
                                                                                       IS                                                                        SCALE                                                    APPROVED                                                                                           PROPOSED RETAINING WALLS                   1537
 1   24.03.17    APPROVAL ISSUE                                  NN         PB                                                                                                                                                                                                                                               NO.27-29 GRANT STREET, NOOSA
                                                                                     DATUM                                AHD                                                                                                                                                                                                                                  SHEET:        OF
                                                                                     DESIGN                               DK
                                                                                                                                    0            0.2            0.4             0.6            0.8           1.0m       .................                                                                                    G & M ROBERTSON                             4        5


                                                                                                                                                                                                                          DANIEL KENNA                                                                                       DRAWING TITLE:                    DRAWING NUMBER         REV
                                                                                     DRAWN                                NN
                                                                                                                                                                 SCALE 1:20 A3                                             (RPEQ 15522)                                                                                      RETAINING WALLS SECTION DETAILS
                                                                                     DESIGN CHECK                         DK
                                                                                                                                                                                                                     DRAWING STATUS
                                                                                                                                                                                                                                                                  p 07 5443 8285                                                                                  ST04                 1
                                                                                                                                                                                                                                                                  e [email protected] w www.barlowshelley.com.au
                                                                                     DATE                               MAR 2017
                                                                                                                                   This drawing is not to be copied or amended without written permission from
                                                                                                                                   Barlow Shelley Consulting Engineers                                                   FOR APPROVAL                             a PO Box 899 Maroochydore 4558 ABN 89 215 591 077
                                                                                                                                                                                                                                                                                                                             SHEET 3 OF 3

Page 9

     THIS DRAWING IS TO BE READ IN CONJUNCTION WITH THE             REINFORCED CONCRETE NOTES:
     GEOTECHNICAL REPORT REFERENCE:
     BY:         TECTONIC ENGINEERS                                 1. ALL FOOTINGS TO BE FOUND INTO STIFF TO VERY
     REF:        17019-001-Rev0                                        STIFF SILTY CLAY OF YELLOW BROWN AND PALE
     DATED:      7th FEBRUARY 2017                                     GREY APPEARANCE.                                                                                                                                                                                                             PROPOSED RESIDENCE BY OTHERS.
     ALL FOOTINGS TO BE FOUND INTO SIMILAR FOUNDATION               2. ALL BEAMS TO HAVE N12 CORNER BARS (600x600) TO
     MATERIAL. SHOULD THE FOUNDATION MATERIAL VARY                     MATCH REINF AS SPECIFIED. PROVIDE 2/N12 SPLICE
     FROM THE SITE INVESTIGATION REPORT, CONSULT                                                                                                                                                                              ET1                                                                                                                                                       ET1
                                                                       BARS (600mm LAP) AT ALL BEAM JUNCTIONS.
     ENGINEER.                                                      3. BASES OF ALL EXCAVATIONS TO BE FINISHED SOUND
     NOTE: THE FOOTINGS & SLAB AS DETAILED HAVE BEEN                   AND FREE OF ANY LOOSE MATERIAL PRIOR TO
                                                                                                                                                                                                                               125
                                                                       PLACEMENT OF CONCRETE.
     DESIGNED FOR         "S"
                       TYPE SOIL CLASSIFICATION IN
                                                                    4. TERMITE PROTECTION TO BE PROVIDED IN
     ACCORDANCE WITH AS2870-2011.                                                                                                                                                                                              SCJ                                                                                                                                                      SCJ
                                                                       ACCORDANCE WITH THE BUILDING CODE OF
                                                                       AUSTRALIA AND OTHER RELEVANT CODES.
     CONCRETE NOTES:                                                5. ALL SURFACE RUNOFF TO BE DIRECTED AWAY FROM




                                                                                                                                                                                                                                                                                                                                                                                                    ET1
                                                                       RESIDENCE. PROVIDE SURFACE FALLS TO SUIT.                                                                                                                                                                                                                                                                       125
     1. ALL SLAB THICKNESSES ARE NOMINAL ONLY. ALL                  6. IF LARGE TREES ARE REMOVED DURING SITE




                                                                                                                                                                                                                     ET1
        FALLS ARE IN ADDITION TO THE THICKNESS                         PREPARATION THE VOIDS ARE TO BE EXCAVATED,
        NOMINATED. SLAB TOP REINFORCEMENT TO MATCH                     BACKFILLED & COMPACTED WITH SUITABLE                                                                                                                                                                                                                                                                            SCJ
                                                                                                                                                                                                                                        SCJ
        SLAB FALLS.                                                    MATERIAL SIMILAR TO THE EXCAVATED MATERIAL.




                                                                                                                                                                                                                                                                ET1
     2. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH




                                                                                                                                                                                                                                                                                                                                                                           ET1
        ARCHITECTS, HYDRAULIC AND CIVIL CONSULTANTS
        DRAWINGS FOR ALL LEVELS, FALLS, GRADES,                      FOOTING LEGEND:
        DRAINAGE ETC.
                                                                                                                                                                                                                                                                                                                                                   WATER FOUNTAIN
     3. SLAB SURFACE IS TO BE CURED UTILISING FOSROC                MARK         DESCRIPTION
                                                                                                                                                                                                                                                                                                                                                   BY OTHERS.
        CONCURE HR90 APPLIED IN ACCORDANCE WITH                                                                                                                                                                                                       S CJ                                                                                                                       SCJ
                                                                         ET1     300W x 250D M.C. EDGE THICKENING
        MANUFACTURERS SPECIFICATIONS.
                                                                         SCJ     SAW-CUT CONSTRUCTION JOINT

     SLAB NOTES:                                                         TDJ     TWO-WAY DOWELED CONSTRUCTION JOINT                                                                                                                                                 5




                                                                                                                                                                                                                                                                                                                                                                                              ET1
                                                                                                                                                                                                                                                                 12
     DRIVEWAY SLABS:                                                     SP1   10T SWL SCREW PIER 600 CLEAR OF SEWER
                                                                                                                                                                                                                                                                           J
     N32 CONCRETE GRADE | 125mm THICK MINIMUM                                  FOUND 300 MIN BELOW INVERT.                                                                                                                                                              SC




                                                                                                                                                                                                                                                ET
                                                                                                                                                                                                                                                                                                                                                                      SC




                                                                                                                                                                                                                                                  1
     SL92 MESH, 40mm TOP COVER                                                                                                                                                                                                                                                                                            ET1                                             J




                                                                                                                                                                                                                                                                                                            SC
                                                                                                                                                                                                                                                                                                             J
                                                                                                                                                                                                                                                                                                                                J
                                                                                                                                                                                                                                                                                                                           TD                               125




                                                                                                                                                                                                                                                                                                                                                  SC
                                                                                                                                                                                                                                                                                                                                                   J
               PROVIDE 20mm SAW CUT                         SL92 MESH,
               FILL WITH APPROVED                           40 TOP COVER.                                         SL92 MESH, 40 TOP COVER.                                                                                                                                                              J
                                                                                                                                                                                                                                                                                                   TD                                                               ET1




                                                                                                                                                                                                                                                                        SC




                                                                                                                                                                                                                                                                                                                                    SC
               FLEXIBLE SEALANT.




                                                                                                                                                                                                                                                                          J
                                                                                                                                                                                                                               INDICATES APPROX.




                                                                                                                                                                                                                                                                                                                                       J
                                                                                                                                                                                              OPTIONAL KERB /
                                                                                                                                                                                              WHEEL GUARD.                     LOCATION OF




                                                                                                                                                                                                                                                                                                                                                              1
                                                                                                                                                                                                                                                                                                                                                           SP
                                                                                                                                                                                                                               DRAINAGE PIT TO
                                                                                        125
         125




                                                                                                                                                                                FSL




                                                                                                                                                                                       200
                                                                                                                                                                                                                               BE REMOVED.                                 J
                                                                                                                                                                                                                                                                        TD
                                                                                                                                                                                ET1




                                                                                                                                                                                                                                                                                         SC
               COMPACTED SANDBED              SCJ           CUT EVERY SECOND                                                                                                                                                                                                                                          1




                                                                                                                                                                                                                                                                                               J
                                                                                                        3-L11 TM, 50mm                                       300                                                                                                                                                 ET
               WITH VISQUEEN                                WIRE OF MESH IN
                                                                                                        BOTTOM COVER.
               VAPOUR BARRIER OVER                          LINE WITH JOINT.                                                                                                                                                                                                 125                                 1
               (CONTINUOUS)                                                                                                                                                                                                                                                                                 SP

                   SAW-CUT JOINT SCJ                                                    EDGE THICKENING ET1                                                                                                                                                                                                                                2-N12 CRACKER BARS




                                                                                                                                                                                                                                                               ET
                                                                                                                                                                                                                                                                 1
                                                                                                                                                                                                                                                                                                                                           TO MAN HOLE.

                   SCALE 1:20                                                           SCALE 1:20
                                                                                                                                                                                                                                                                                                                     INDICATES APPROX.
                                                                                                                                                                                                                                                                                                                     DRAINAGE PIT.
                                     30mm UV RATED SEALANT.                                   TERMINATE MESH
                                                                                              50 FROM SLAB EDGE.
                                     N12 TRIMMER TO EACH                                      PLATE DOWEL
                                     SLAB. 30 EDGE COVER.                                     SLEEVE. (TAPERED)
                                                                                                                                                                                                                                                                EXISTING DRIVEWAY
                                                                                                                                                                                                                                                                TO REMAIN.
                                        125




                                      COMPACTED SANDBED WITH                           LESA SYSTEMS PLATE DOWEL.
                                      CONTINUOUS POLYTHENE
                                                                           TDJ         INSTALLED TO MANUF. SPEC. 10mm
                                      MEMBRANE OVER.                                   PLATE DOWELS IN JOINT.
                                                                                                                                                                                                   DRIVEWAY SLAB LAYOUT & SLAB JOINT PLAN 1:100 @ A3
                                    TWO-WAY DOWELED JOINT TDJ                                                                                                                                      REFER TO ARCHITECTURAL SPECIFICATIONS FOR ALL SET OUT DIMENSIONS, FINISHING, FLASHING, SURFACE FALLS AND WATER PROOFING. etc

                                    SCALE 1:20
                                                                                                                                                                                                                                                                                                            PROJECT:                                                                                      JOB NUMBER
REV DATE DESCRIPTION                                BY   CHKD DRAWN
                                                                  I GDETAL
                                                                         IS                                                     SCALE                                                        APPROVED                                                                                                       PROPOSED RETAINING WALLS                                                                           1537
 1      24.03.17   APPROVAL ISSUE                   NN       PB                                                                                                                                                                                                                                             NO.27-29 GRANT STREET, NOOSA
                                                                  DATUM               AHD                                                                                                                                                                                                                                                                                                             SHEET:        OF
                                                                  DESIGN              DK
                                                                                                  0             1.0            2.0             3.0            4.0           5.0m         .................                                                                                                  G & M ROBERTSON                                                                                     5        5


                                                                                                                                                                                             DANIEL KENNA                                                                                                   DRAWING TITLE:                                                                           DRAWING NUMBER          REV
                                                                  DRAWN               NN
                                                                                                                             SCALE 1:100 A3                                                   (RPEQ 15522)                                                                                                  DRIVEWAY SLAB LAYOUT & SLAB JOINT PLAN
                                                                  DESIGN CHECK        DK
                                                                                                                                                                                      DRAWING STATUS
                                                                                                                                                                                                                                    p 07 5443 8285                                                                                                                                                        ST05                1
                                                                                                  This drawing is not to be copied or amended without written permission from                                                       e [email protected] w www.barlowshelley.com.au
                                                                  DATE              MAR 2017      Barlow Shelley Consulting Engineers                                                        FOR APPROVAL                           a PO Box 899 Maroochydore 4558 ABN 89 215 591 077

Used in these records

About this file

File size
2.2 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Appendix 3- Engineering Drawings.pdf · 2.2 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.