2016-11-08 S&O Agenda - Item 1, Attachment 1 - Annual Report 2015-16

of 70

Page text shows just the words. Original shows the document exactly as it was published.

Page text read automatically using OCR, there may be inaccuracies

Text sections have not been matched to the original PDF pages. Use the original document to check page numbers.

PLANNING & ENVIRONMENT COMMITTEE MEETING AGENDA                                 8 NOVEMBER 2016


          b.    automatic tank gauging (ATG) that includes an automatic system using an
                arrangement of sensor probes and other devices that monitor the underground
                petroleum storage system and provide inventory information and leak testing;
          c.    a tank pit observation well at the lowest point of each tank excavation pit.
    51.   Leak detection systems for the underground pipework must include:
          a.    electronic line leak detection (ELLD) for pressure piping; or
          b.    safe suction for suction piping;
          c.    for remote fill lines, a statistical inventory reconciliation system to monitor leaks
                in the fill lines.
    52.   All underground pipework must be made of approved, non-corrodible materials which
          include either:
          a.    fibre-reinforced thermosetting resin composite (fibreglass) compatible with the
                product to be transferred; or
          b.    flexible plastic meeting the requirements of UL971 Standard for non-metallic
                underground piping for flammable liquids.
    53.   All product piping must have secondary containment consisting of double-walled
          piping with an interstitial space.
    54.   A Certificate of Compliance is to be provided by the manufacturer that the pipework
          meets the Standard and be provided to Council prior to the commissioning the UPSS.
          Fill/Vapour Recovery Points
    55.   Each tank fill point is to be:
          a.    clearly labelled and identified in compliance with AS 4977-2008 Petroleum
                products - Pipeline, road tanker compartment and underground tank
                identification
          b.    fitted with a camlock type or other liquid-tight connection
          c.    provided with spill containment of at least 15L capacity per spill point.
    56.   All fill and vapour recovery points must be earthed in compliance with AS 1020-1984
          The control of undesirable static electricity and AS 3000-2007 Electrical installations.
          Monitoring
    57.   Monitoring of the interstitial space of the double walled tanks or product piping must
          be capable of detecting a release through either wall of the tank or product piping. A
          6-monthly inspection program conducted by a suitably qualified and experienced
          person is required to monitor the following:
          a.    the system is active;
          b.    leak detection measurements (e.g. liquid levels or pressure levels) are within
                manufacturer’s tolerances;
          c.    leak detection measurements are recorded;
          d.    any loses outside the manufacturer’s leak detection tolerances are to be
                reported to council in writing and the tank owner immediately.
          Fuel Dispensing Area (FDA)
    58.   The FDA must be designed and constructed to ensure that no vehicle may be
          refuelled outside the delineated area.
    59.   The FDA must be designed and constructed so as to prevent the entry of watershed
          from overland stormwater flows entering the fuel dispensing forecourt.

                                                                                     Page 13 of 70
Log in to download the original file

2016-11-08 S&O Agenda - Item 1, Attachment 1 - Annual Report 2015-16(PDF, 7MB).pdf · 7.6 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.