Attachment A – Analysis of floorplan requirements for Gold Standard Liveable Housing Design Material Change of Use for Multiple Dwellings (8 Dwellings) 25 & 27 Toolar Street, TEWANTIN QLD 4656 Lots 1 & 2 on RP73072 Concept Planning and Development Consultants ABN 99 789 542 467 26 Seafarer Drive, River Heads QLD 4655 : 0418531673 : [email protected] [OCR of page images] G: KOC Yl Attachment A — Analysis of floorplan requirements for Gold Standard Liveable Housing Design Material Change of Use for Multiple Dwellings (8 Dwellings) 25 & 27 Toolar Street, TEWANTIN QLD 4656 Lots 1 & 2 on RP73072 Concept Planning and Development Consultants ABN 99 789 542 467 26 Seafarer Drive, River Heads QLD 4655 @: 0418531673 : [email protected]
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalFull text of the other 6 pages
Page 2
2 Bedroom Standard Build Gold Standard Total Additional
Villa
Master B/R 3.2 Master 3 x 3.1 = 9.3sqm Bedroom minimum 4.18sqm
x 3.2 = of 10sqm exclusive
10.24sqm of robe
Minor 2.8 x 2.5 = 7sqm
Minor B/R 3.2 x i. is of at least 10m2
3.2 = 10.24 (note: no required size for bedroom clearance exclusive
sqm in BCA standard sourced from build of wardrobes;
search) skirtings and wall
lining;
ii. provides for a
https://buildsearch.com.au/average- minimum path of
room-size travel of at least
Total 20.48 Total 16.3sqm 1000mm on at least
sqm one side of the bed.
Bathroom 2.1 x No standard size only requirement is Shower 2.46sqm
2.6 = 5.46sqm to have a door opening of 820mm ii. provide minimum
dimensions of
900 x 900 Common Size 1.5 x2 = 3sqm 900mm (width) x
shower 900mm (length);
and
500mm vanity iii. provide a clear
space of at least
1200 clear in 1200mm (width) x
front of 1200mm (length)
shower, vanity,
toilet, laundry Toilet
ii. a minimum
Total 5.46sqm Total 3sqm 1200mm clear
circulation space
forward of the toilet
pan exclusive of
swing of the door.
iii. The toilet pan
should be in the
corner of the room
(if the toilet is
located in a
combined toilet /
bathroom) to enable
installation of
grabrails at a future
date.
Kitchen No Standard but assume that a. The kitchen space 0.74
1000mm would be utilised as a should be designed
3.6 x 1.2 = normal width in residential homes to support ease of
4.32sqm and the kitchen would likely include movement and
an island bench on the other side. adaptation with:
[OCR of page images]
2 Bedroom
Villa
Standard Build
Gold Standard
Total Additional
Master B/R 3.2 | Master 3 x 3.1 = 9.3sqm Bedroom minimum 4.18sqm
x3.2= of 10sqm exclusive
10.24sqm of robe
Minor 2.8 x 2.5 = 7sqm
Minor B/R 3.2 x i. is of at least 10m2
3.2 =10.24 (note: no required size for bedroom | clearance exclusive
sqm in BCA standard sourced from build of wardrobes;
search) skirtings and wall
lining;
ii. provides for a
https://buildsearch.com.au/average- | minimum path of
room-size travel of at least
Total 20.48 Total 16.3sqm 1000mm on at least
sqm one side of the bed.
Bathroom 2.1 x | No standard size only requirement is | Shower 2.46sqm
2.6 = 5.46sqm
900 x 900
shower
500mm vanity
1200 clear in
front of
shower, vanity,
toilet, laundry
to have a door opening of 820mm
Common Size 1.5 x2 = 3sqm
Total 5.46sqm
Total 3sqm
ii. provide minimum
dimensions of
900mm (width) x
900mm (length);
and
iii. provide a clear
space of at least
1200mm (width) x
1200mm (length)
Toilet
ii. a minimum
1200mm clear
circulation space
forward of the toilet
pan exclusive of
swing of the door.
iii. The toilet pan
should be in the
corner of the room
(if the toilet is
located ina
combined toilet /
bathroom) to enable
installation of
grabrails at a future
date.
Kitchen
3.6x1.2=
4.32sqm
No Standard but assume that
1000mm would be utilised as a
normal width in residential homes
and the kitchen would likely include
an island bench on the other side.
a. The kitchen space
should be designed
to support ease of
movement and
adaptation with:
0.74
Page 3
(kitchen length 3.6 x 1 = 3.6sqm i. at least 1200mm 3600mm and clearance in front of at least fixed benches and 1200mm appliances clearance in (excluding handles); front of fixed and benches and ii. slip resistant appliances flooring.6 (excluding handles) Total 4.32sqm Total 3.6sqm Based on the additional spatial requirement for bathroom and bedroom alone each of the 2 bed units requires 7.38 sqm of floor area to meet the minimum Gold Standard Requirements. [OCR of page images] (kitchen length | 3.6x 1=3.6sqm i. at least 1200mm 3600mm and clearance in front of at least fixed benches and 1200mm appliances clearance in (excluding handles); front of fixed and benches and ii. slip resistant appliances flooring.6 (excluding handles) Total 4.32sqm_ | Total 3.6sqm Based on the additional spatial requirement for bathroom and bedroom alone each of the 2 bed units requires 7.38 sqm of floor area to meet the minimum Gold Standard Requirements.
Page 4
Bathroom:
Toilet.
i. a minimum clear width of 900mm between the walls of the bathroom if located in a separate
room; and
ii. a minimum 1200mm clear circulation space forward of the toilet pan exclusive of the swing of
the door in accordance with Figure 3(a).
iii. The toilet pan should be located in the corner of the room (if the toilet is located in a combined
toilet / bathroom) to enable installation of grabrails at a future time
Shower
i. One bathroom should feature a slip resistant, hobless shower recess. Shower screens are
permitted provided they can be easily removed at a later date.
ii. The shower recess should be located in the corner of the room to enable the installation of
grabrails at a future date.
iii. be located in a bathroom on the ground (or entry) level;
iv. provide minimum dimensions of 900mm (width) x 900mm (length); and iii. provide a clear space
of at least 1200mm (width) x 1200mm (length) forward of the shower recess entry
[OCR of page images]
Bathroom:
Toilet.
a minimum clear width of 900mm between the walls of the bathroom if located in a separate
room; and
a minimum 1200mm clear circulation space forward of the toilet pan exclusive of the swing of
the door in accordance with Figure 3(a).
The toilet pan should be located in the corner of the room (if the toilet is located in a combined
toilet / bathroom) to enable installation of grabrails at a future time
Shower
One bathroom should feature a slip resistant, hobless shower recess. Shower screens are
permitted provided they can be easily removed at a later date.
The shower recess should be located in the corner of the room to enable the installation of
grabrails at a future date.
iii. be located in a bathroom on the ground (or entry) level;
provide minimum dimensions of 900mm (width) x 900mm (length); and iii. provide a clear space
of at least 1200mm (width) x 1200mm (length) forward of the shower recess entry
Page 5
Kitchen layout Kitchen space designed to support ease of movement and adaptation with: i. at least 1200mm clearance in front of fixed benches and appliances (excluding handles); ii. slip resistant flooring. [OCR of page images] Kitchen layout Kitchen space designed to support ease of movement and adaptation with: i. at least 1200mm clearance in front of fixed benches and appliances (excluding handles); ii. slip resistant flooring. | aD | | | rieitin | naTiT | TT A LL ! | | al Io i LIVI ! 1! 38x38m ! L iy & b--=, KIT, ATL Ii | CT IRE MAL Mt | coe L S38 x 3.0n0 LLL} | | LL
Page 6
Bedroom The dwelling should feature a space (or room) on the ground (or entry) level that: i. is at least 10m2 clearance exclusive of wardrobes; skirtings and wall lining; ii. provides for a minimum path of travel of at least 1000mm on at least one side of the bed. [OCR of page images] Bedroom The dwelling should feature a space (or room) on the ground (or entry) level that: i. is at least 10m? clearance exclusive of wardrobes; skirtings and wall lining; ii. provides for a minimum path of travel of at least 1000mm on at least one side of the bed. BED (4 (io ~ ~ < - | - 35K 341m7
Page 7
Living/Dining No Gold Requirement. Universal design guidelines recommend circulation through different spaces must be well planned for easy manoeuvrability, especially for people with limited mobility and people who use a wheelchair. Living spaces should be designed and furnished for maximum comfort and ease of use provide spaces large enough to allow for easy manoeuvrability reduce the need for doors that are difficult to open and close, avoid hazardous features, design internal spaces that are larger, rather than smaller, to allow for easy accessibility (for example, combine dining and living areas). [OCR of page images] Living/Dining No Gold Requirement. Universal design guidelines recommend circulation through different spaces must be well planned for easy manoeuvrability, especially for people with limited mobility and people who use a wheelchair. Living spaces should be designed and furnished for maximum comfort and ease of use provide spaces large enough to allow for easy manoeuvrability reduce the need for doors that are difficult to open and close, avoid hazardous features, design internal spaces that are larger, rather than smaller, to allow for easy accessibility (for example, combine dining and living areas). wv 4 Yy Ww | | bath zs PTT Thy Wa eR I | \ Wire! t] | | 1 LIVI PORT LEELA ul | Lot 38x38 +I} ) TAL | t--=, KIT. eo BED. ie rn -7 | \ I CT IB Lie | \ UBO BOTs RH 3 bx 7am TT | Uf aA Y Hl | WILI Tee IN g TAT AT F ROBE 1 Zonet D | ISe8x30m LL 8 [| wm | | VOID | r-E'BRY | ENTRY over | -| BATH | ea teenrs PP - WS N\q 42h thy TSIEN AR . | Wain it | Bi 141111 1 f | A) a —T eee it at rrarTa