OVERHEAD WORKS SCHEDULE
LV OVERHEAD SERVICE CONDUCTOR SCHEDULE
POLES CONSTRUCTIONS (Note: KBS is top KB to top KB)
STN SITE I.D
LOCATION EDT EDT SST LST COMP REMARKS SAG(m) TOTAL FITTINGS
No. (POLE No) EXISTING RECOVER ERECT SINK FOOT ALIGN LCC EXISTING RECOVER ERECT No KBS ANG LCC
ANG kN Kn Kn ID No OF
LOCATION STN No. HOUSE No EXISTING TRANSFER RECOVER ERECT DIST (m) SAG SPAN CONDUCTOR REMARKS
PAVILION ST 14 P7871 328° 0.81 2.26 3.93 P12.5/8-14 P12.5/8-14 EX EX EX EX 11TD/N 11TD/N 1 EX SPANS CHANGE SERVICE FITTING
15° 30° LENGTH (m) MAINS BOX FUSE SIZE φ
I2B25AW I2B25AW 3 EX P.O.A. CODE or IIN
LVABC/SU3 LVABC/SU3 1 EX PAVILION ST 14 32 1-2B25 1-2B25 1 14.9 1 15 EX EX EX EX T2B25CBB80
SP12742334 328° 0.96 2.66 4.62 P14/12-24C MDCF 2.4 PO1 EX 11TD/N 1 150 14 34 1-2B25 1-2B25 1 6.8 1 7 EX EX EX EX T2B25CBB80
PAGE7-53-3 1 14/16 27A 1-2B25 1-2B25 1 20+8 1 0.1 0.19 28 EX EX E EX T2B25CBB80
11EDO3 3 1000
S21652 1 2150
11PT/315C 1
LVABC/PTSU 1 1000
T2B25CBB80 3 100
FS315/315 1 150
SC0010604 1
LVBR240/ABC 1
LVT4C240 1 150
LVABC/DS2T 1 250
PTSMNC 1 1425
PTCOMC 1
CGECROD 1
15 P7870 0 0 1.2 2.16 P11/12-22 EX EX EX EX 11TD/N EX 150
I2B25AW EX 1650
LVABC/SU3 LVABC/SU3 LVABC/S 1 150
LVABC/DS2 1 150
16 P305784 145 1.08 1.91 3.29 P9.5/12-22 EX EX EX EX LVABC/T EX 150
17 P7872 99° 1.97 4.31 8.96 P12.5/8-14 EX EX EX EX 11TD/N EX 150
LVT EX 1650
I2B25AW EX 100
SC15568D EX
LVBR240/AOH EX
LVT240 EX 150
LVABC/SU3 EX 150
LVABC/DS2 EX 250
SWPBMI1B EX 100
TREE ST 18 P80392 EX EX EX EX P11/12-22 EX EX EX EX LVP LVP LVS EX 150
I2B25AW EX 100
IS95 1 250
SWPBMI3L EX 900
PROPOSED OVERHEAD PROFILE
OVERHEAD CONDUCTOR SCHEDULE
SAG (m) CONDUCTOR LENGTH (m)
STATIONS No. OF SAG SPAN
LOCATION VOLTS EXISTING TRANSFER RECOVER ERECT DIST (m) STRING M.E.S LCC REMARKS
FROM-TO SPANS TABLE FROM - TO
15° 30° NEW REC
PAVILION ST 14 - 15 11kV 3-7/4.75 3-7/4.75 2 25 660 41.735 11-13 0.4 0.5
- LV 1-95ABC 1-95ABC 2 25 660 41.735 11-13 0.4 0.5
14 - 16 LV 1-2B25 1-2B25 1 20 <1kN 20 11-12 0.1 0.4
14 - 17 11kV 3-7/4.75 3-7/4.75 2 48 660 48.233 11-12 1.5 1.6
- LV 1-95ABC 1-95ABC 2 48 660 48.233 11-12 1.5 1.7 PROPOSED PT SP12741729
ENERGEX FUNDED OVERHEAD WORKS SCHEDULE
POLES CONSTRUCTIONS (Note: KBS is top KB to top KB)
STN SITE I.D RATE 2 STREETLIGHT SCHEDULE
LOCATION EDT EDT SST LST COMP REMARKS
No. (POLE No) EXISTING RECOVER ERECT SINK FOOT ALIGN LCC EXISTING RECOVER ERECT No KBS ANG LCC
ANG kN Kn Kn ID ST POLE or COMPONENTS LANTERN OUTREACH BRACKET MOUNT
SITE ID
PAVILION ST 19 X305952 EX EX EX EX P14/8-14 EX EX PO1 EX 11P/N 1 150 LOCATION N COM EXIST REC ERECT ALIGN COM RECOVER DATE DE- ERECT DATE EXIST REC EREC UP/C HEIGHT REMARKS
(POLE No) SLM or IIN EX SLM or IIN SLM or IIN
No P ID (m) (m) (m) (m) P ID LUMIN CUST ENERG LUMIN CUST ENERG (m) (m) T (m) (°) (m)
S0015567 6
11LBSMPFFIS 1 350 ROAD 1 3L P12742377 PO 1 4.5BPM SLNOS1CI 0.8BoK PO 1 L18 NOOS SLEDSY01791 0° 5.1
LVA 1 1450 9L P12742378 PO 1 4.5BPM SLNOS1CI 0.8BoK PO 1 L18 NOOS SLEDSY01791 0° 5.1
HVE MAJESTIC DR 12L P12533472 PO 1 4.5BPM SLNOS1CI 0.8BoK PO 1 L17 22.07.22 NOOS SLEDGL01711 0° 5.1
CGESROD
CERTIFICATE OF COMPLIANCE
DESIGN DOCUMENTATION IN ACCORDANCE WITH THE REQUIREMENTS OF
COMPLIANCE OF AS/NZS 1158
* Refer AS1158.1.1:2022 Appendix D for information regarding V category
* Refer AS1158.3.1:2020 Appendix C for information regarding P category
* PerfectLite 5.06 computer software used
* AGI32 computer software used
ITEM PROJECT SPECIFICATION MAINTENANCE REGIME
LIGHTING CATEGORY
Maintenance Factor Assumed: The maintenance factor assumed in the calculations is as
Road Name ROAD 1 follows:
Nominated Lighting Category PR5 * Luminaire Maintenance Factor (refer AS 1158 1.1:2022 APPENDIX E).
* Lamp Lumen Depreciation Factor (Refer Lamp Manufacturer's "Lamp
Road Surface Reflection Characteristic R3 Lumen Deprectiation Curves").
INSTALLATION GEOMETRY
Road Reserve Lighting Design Width 15 Maintenance Factor Calculated 0.75
Mounting Height 5.1
Overhang -0.3
Lighting Arrangement ARR1 Schedule of Maintenance: This road lighting design is based on the following
maintenance schedule:
Pole Setback 0.5 BoK
Upcast Angle 0° *LED lamp replacement carried out at 88000 hrs intervals. Cleaning regime every 48
months.
LUMINAIRE/LAMP 1 DETAILS
*All other luminaires lamp replacement & cleaning carried out at 36 month intervals.
Lamp Type / Wattage L18 (Nostalgia Type 1)
At this time the following shall also occur:
Sylvania Schréder
Luminaire Identification
AVENUE GEN2 18W 4K * All optical surfaces, both internal and external, of the luminarie
shall be cleaned.
Lamp Flux (Lumens) 2523 * All gaskets shall be checked for deterioration and replaced
where necessary.
I-Table Number (.cie) AVENUE II 4K 18W V2 210730PH * Damaged/weathered visors shall be replaced.
* All accessible screws, nuts etc. shall be checked for tightness.
Lighting Tariff 2 * A visual check shall be made of the electrical components and
HPF (≥ 0.9) wiring for signs of overheating.
Power Factor
* If required, the luminaire shall be realigned/adjusted to the
Start/Run Currents (Amps) 0.08 design specification.
IP Rating IP66
CATEGORY PR5 LUMINAIRE/LAMP 1 MAXIMUM SPACING CALCS
WORKS AREA #2 - ENERGEX FUNDED
Average Horizontal Illuminance (Ē h) ≥0.85 lx
ISSUE FOR COUNCIL Minimum Point Horizontal Illuminance (E Ph) ≥0.14 lx
ACCEPTANCE ONLY Illuminance Uniformity (U E2) ≤10
Upward wasted light ratio (UWLR) % ≤0%
NOT FOR CONSTRUCTION Road Reserve Lighting Design Width (m) Maximum Spacing (m)
15 60.5
This drawing is to be considered preliminary until this
disclaimer is removed by Peter Eustace Pty. Ltd.
DATE 12.11.25 SITE CONTACT DETAILS COUNCIL STANDARD ALIGNMENTS WORKS COORDINATOR PECE WORKSPLAN VERSION 5.5
APPROVED KRIS BOVEINIS PECE
CONSULTING NAME Energex OH 3.0m RP PARENT PROJECT NO. SCALE: 1:500@A1
A ACCEPTANCE ONLY. NOT
TBC Energex UG 0-0.9m RP WORK REQUEST NO. PROJECT / SUB PROJECT NO.
ISSUED FOR COUNCIL
FOR CONSTRUCTION.
CHECKED KRIS BOVEINIS
ENGINEERS COMPANY
-
NBN
GAS
REFER NBN
REFER GAS
LOTS 2-8, 601
DESIGNER LUKE ARACE
INSTALL HV & LV EQUIPMENT, CABLE, CONDUIT & STREETLIGHT
R DESCRIPTION
STREET ADDRESS U14, 39 Lawrence Dr, Nerang QLD 4211
PHONE - HP GAS REFER GAS CANCELLING LOTS LOT 7 ON SP337814 PHONE (07) 5596 1425
8 LOT SUBDIVISION
S1302554
POSTAL ADDRESS PO Box 2835, Nerang DC QLD 4211 MOBILE - WATER REFER CIVIL PLANNER KRIS BOVEINIS
TELEPHONE (07) 5596 1425 FAX - STORMWATER REFER CIVIL LOCAL AUTHORITY NOOSA COUNCIL PHONE (07) 5596 1425 33a PAVILION ST
EMAIL [email protected]
WEB pece.com.au SEWERAGE REFER CIVIL UBD REF POMONA, QLD, 4568 Sheet 2 of 4
25-0316- EGX- 02 OTHER REFER CIVIL PEGGED?
ISSUE DATE 12 NOVEMBER 2025