Att 2- Engineering · MCU23/0038.02
IF IN DOUBT, ASK.
DO NOT SCALE THIS DRAWING. USE FIGURED DIMENSIONS ONLY. ALL DIMENSIONS TO BE VERIFIED ON SITE.
2 2
2 7
9000 (SIDEWALL)
4500 4500
1 2
C1 C2 C1
3
3000
6000 (ENDWALL)
ROOF FALL
4 4 1 3 3
7 C3 2 3 2 C3 7
DK3
DK1
5 4
3000
Y
4
C1 C4 C1
6 7
1 1
2 7
1 FOUNDATION PLAN AND MEMBER LAYOUT
1 SCALE: 1 = 100
MEMBER LEGEND
C1 C15019
C2 2C15024
ROOF STRAP BRACING TO BE CONNECTED TO THE PURLIN CLOSEST TO THE LINE OF THE END WALL MULLION C3 C15012
ROOF STRAP BRACING CAN BE PLACED FROM EITHER END OF THE BUILDING PROVIDING THE STRAP PATTERN REMAINS AS PER PLANS C4 2C15019
STEEL BUILDING BY (CONTACT) Mr Timothy Roy Messer BE MIEAust RPEQ
Civil & Structural Engineers
JUST SHEDS SUNSHINE COAST & GYMPIE
1
50 Punari Street
CSTS66660
Currajong, Qld 4812
23/9/2025
FOR 07 5445 8532 Fax: 07 4725 5850 Signature ............................................................
STR
TM
AT
ENAYET KHAN Email: [email protected]
ABN 341 008 173 56 Date ......................................
23/9/2025
7
Registered Chartered Professional Engineer Regn. No. 2558980
Registered on the NPER in the areas of practice
14-16 ACTION ST, Registered Professional Engineer (Civil & Structural) QLD
Registered Certifying Engineer (Structural) N.T.
Regn. No. 9985
Regn. No. 116373ES of Civil & Structural National Professional
NOOSAVILLE Registered Engineer - (Civil) VIC
Registered Engineer - (Civil) TAS
Regn. No. PE0002216
Regn. No. CC5648M Engineers Register
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalFull text of the other 11 pages
Page 2
ROOF PURLINS PER
MEMBER SCHEDULE ON
SHEET 5
6 7 2 1
1 SIDEWALL EXTERIOR ELEVATION 2 SIDEWALL EXTERIOR ELEVATION
2 SCALE: 1 = 100 2 SCALE: 1 = 100
ROOF PURLINS
PER SCHEDULE
ROOF PURLINS
PER SCHEDULE
DK2
C TO PEAK C TO PEAK
5 5
525
TO EAVE
3525
3525
3000
5 4
E E 3
5 5
T.O. CONCRETE T.O. CONCRETE
4 ENDWALL INTERIOR ELEVATION 3 ENDWALL INTERIOR ELEVATION
2 SCALE: 1 = 100 2 SCALE: 1 = 100
X BRACING IS REQUIRED IN 1 SIDE BAY, 1 END BAY, 1 ROOF BAY.
SEE LAYOUT OR PLANS FOR PLACEMENT. FLY BRACING IS INCLUDED TO BE PLACED ON EVERY SECOND PURLIN AND GIRT ON ENDWALL MULLIONS, INTERNAL COLUMNS AND INTERNAL RAFTERS.
STEEL BUILDING BY (CONTACT) Mr Timothy Roy Messer BE MIEAust RPEQ
Civil & Structural Engineers
JUST SHEDS SUNSHINE COAST & GYMPIE
2
50 Punari Street
CSTS66660
Currajong, Qld 4812
23/9/2025
FOR 07 5445 8532 Fax: 07 4725 5850 Signature ............................................................
STR
TM
AT
ENAYET KHAN Email: [email protected]
ABN 341 008 173 56 Date ......................................
23/9/2025
7
Registered Chartered Professional Engineer Regn. No. 2558980
Registered on the NPER in the areas of practice
14-16 ACTION ST, Registered Professional Engineer (Civil & Structural) QLD
Registered Certifying Engineer (Structural) N.T.
Regn. No. 9985
Regn. No. 116373ES of Civil & Structural National Professional
NOOSAVILLE Registered Engineer - (Civil) VIC
Registered Engineer - (Civil) TAS
Regn. No. PE0002216
Regn. No. CC5648M Engineers Register
Page 3
COLUMN AND RAFTER SIZE
PER MEMBER SCHEDULE
ON SHEET 5
B
5 900
40
4
80
40
A
20
31
60
23
5
14
0
60
0
F
5
1 INTERNAL FRAME SECTION
3 SCALE: 1 = 50
Refer to Sheet #4 for concrete specification.
STEEL BUILDING BY (CONTACT) Mr Timothy Roy Messer BE MIEAust RPEQ
Civil & Structural Engineers
JUST SHEDS SUNSHINE COAST & GYMPIE
3
50 Punari Street
CSTS66660
Currajong, Qld 4812
23/9/2025
FOR 07 5445 8532 Fax: 07 4725 5850 Signature ............................................................
STR
TM
AT
ENAYET KHAN Email: [email protected]
ABN 341 008 173 56 Date ......................................
23/9/2025
7
Registered Chartered Professional Engineer Regn. No. 2558980
Registered on the NPER in the areas of practice
14-16 ACTION ST, Registered Professional Engineer (Civil & Structural) QLD
Registered Certifying Engineer (Structural) N.T.
Regn. No. 9985
Regn. No. 116373ES of Civil & Structural National Professional
NOOSAVILLE Registered Engineer - (Civil) VIC
Registered Engineer - (Civil) TAS
Regn. No. PE0002216
Regn. No. CC5648M Engineers Register
Page 4
STRUCTURAL GENERAL NOTES
1. GOVERNING CODE : NATIONAL CONSTRUCTION CODE (NCC), LOADING TO AS1170 - ALL SECTIONS. BUILDING SUITABLE AS
EITHER A PRIVATE GARAGE CLASS 10A, OR A FARM SHED (CLASS 7 OR 8),UNLESS OTHERWISE SPECIFICALLY NOTED.
FOR USE AS A FARM SHED, IT MUST MEET THE FOLLOWING REQUIREMENTS:
- BE LESS THAN 2000 SQM IN AREA (INCLUSIVE OF ANY MEZZANINE FLOOR AREA). PROJECT DESIGN CRITERIA
- MUST BE LOCATED ON A FARM AND USED IN CONNECTION WITH FARMING PURPOSES.
- BUILDING IS NOT TO BE OCCOUPIED FREQUENTLY NOR FOR EXTENDED PERIODS BY PEOPLE, WITH A MAXIMUM OF 1 0.25 kPa
PERSON PER 200 SQM OR 2 PERSONS MAXIMUM IN TOTAL WHICHEVER IS THE LESSER.
2. DRAWING OWNERSHIP : VR 57 m/s
THESE DRAWINGS REMAIN THE PROPERTY OF FBHS (AUST) PTY LIMITED. ENGINEERING SIGNATURE AND
CERTIFICATION IS ONLY VALID WHEN BUILDING IS SUPPLIED BY A DISTRIBUTOR OF FBHS. DRAWINGS ARE PROVIDED VsitB 41.3 m/s
FOR THE DUAL PURPOSE OF OBTAINING BUILDING PERMITS AND AIDING CONSTRUCTION. ANY OTHER USE OR
REPRODUCTION IS PROHIBITED WITHOUT WRITTEN APPROVAL FROM FBHS.
3. DRAWING SIGNATURE REQUIREMENTS : Reg B1
THESE DRAWINGS ARE NOT VALID UNLESS SIGNED BY THE ENGINEER. THE ENGINEER ACCEPTS NO LIABILITY OR
RESPONSIBILITY FOR DRAWINGS WITHOUT A SIGNATURE. EACH TITLE BLOCK CONTAINS A WATER MARK UNDER THE 1.08
CUSTOMERS NAME CONTAINING THE DATE OF PRODUCTION OF THE DRAWINGS; THE DRAWINGS ARE TO BE SUBMITTED TO
COUNCIL WITHIN 21 DAYS OF THIS DATE. THIS IS TO ENSURE THAT ONLY CURRENT DRAWINGS ARE IN CIRCULATION. 0.95
4. CONTRACTOR RESPONSIBILITIES :
CERTIFIER AND CONTRACTOR TO CONFIRM [ON SITE] THAT THE WIND LOADINGS APPLIED TO THIS DESIGN ARE TRUE N/A
AND CORRECT FOR THE ADDRESS STATED IN THE TITLE BLOCK.
CONTRACTOR SHALL VERIFY AND CONFIRM ALL EXISTING CONDITIONS AND DIMENSIONS. ENGINEER SHALL BE NOTIFIED N/A
OF ANY DISCREPANCIES BETWEEN DRAWINGS AND EXISTING CONDITIONS PRIOR TO START OF WORK.
CONTRACTOR MUST NOT MAKE ANY DEVIATION FROM THE PROVIDED PLANS WITHOUT FIRST OBTAINING WRITTEN APPROVAL
FROM ONE THE UNDERSIGNING ENGINEERS. THE ENGINEER / FBHS TAKE NO RESPONSIBILITY FOR CHANGES MADE N/A
WALL BASE CLEAT
WITHOUT WRITTEN APPROVAL.
CONTRACTOR IS RESPONSIBLE FOR ENSURING NO PART OF THE STRUCTURE BECOMES OVERSTRESSED DURING TCat 3
CONSTRUCTION.
CLADDING REINFORCING BUILDING IS NOT STRUCTURALLY ADEQUATE UNTIL THE INSTALLATION OF ALL COMPONENTS AND DETAILS SHOWN IS 100 kPa
2 SCREW COMPLETED IN ACCORDANCE WITH THESE DRAWINGS.
MESH THE INDICATED DRAWING SCALES ARE APPROXIMATE. DO NOT SCALE DRAWINGS FOR CONSTRUCTION PURPOSES.
FOR FUTHER DIRECTIONS ON CONSTRUCTION THE CONTRACTOR SHOULD CONSULT THE APPROPRIATE INSTRUCTION MANUAL.
1:500
ANCHORS 5. ENGINEERING : -0.61
PER COLUMN THE ENGINEER / FBHS ARE NOT ACTING AS PROJECT MANAGERS FOR THIS DEVELOPMENT, AND WILL NOT BE PRESENT
DURING CONSTRUCTION.
N.G.L THE UNDERSIGNING ENGINEERS HAVE REVIEWED THIS BUILDING FOR CONFORMITY ONLY TO THE STRUCTURAL DESIGN 0.58
PORTIONS OF THE GOVERNING CODE. THE PROJECT MANAGER IS RESPONSIBLE FOR ADDRESSING ANY OTHER CODE
REQUIREMENTS APPLICABLE TO THIS DEVELOPMENT. 2
THESE DOCUMENTS ARE STAMPED ONLY AS TO THE COMPONENTS SUPPLIED BY FBHS. IT IS THE RESPONSIBILITY OF THE
PURCHASER TO COORDINATE DRAWINGS PROVIDED BY FBHS WITH OTHER PLANS AND/OR OTHER COMPONENTS THAT ARE PART
OF THE OVERALL PROJECT. IN CASES OF DISCREPANCIES, THE LATEST DRAWINGS PROVIDED BY FBHS SHALL GOVERN.
NO ALTERATIONS TO THIS STRUCTURE (INCLUDING REMOVAL OF CLADDING) ARE TO BE UNDERTAKEN WITHOUT THE
CONSENT OF THE CERTIFYING ENGINEER.
DETAIL KEYS
OPENINGS SUCH AS WINDOWS AND DOORS NEED TO BE INSTALLED AS PER THE PRODUCT MANUFACTURER'S
INFORMATION/DETAILS.
THE BUILDING IS DESIGNED AS A STAND-ALONE BUILDING, NOT RELYING ON ANY ADJACENT BUILDING. IF THE DK1
PERMANENT OPENING IS OBSTRUCTED BY ANY ADJACENT BUILDING AND WITHIN A DISTANCE OF 0.5M OF SAID OPENING,
100
THE DESIGN SHOULD BE REFERRED TO THE DESIGN ENGINEER FOR REVIEW OF INTERNAL PRESSURES AND POSSIBLE
REDESIGN. DK2
6. INSPECTIONS :
NATURAL NO SPECIAL INSPECTIONS ARE REQUIRED BY THE GOVERNING CODE ON THIS JOB. ANY OTHER INSPECTIONS REQUESTED
DK3
BY THE LOCAL BUILDING DEPARTMENT SHALL BE CONDUCTED AT THE OWNER'S EXPENSE.
GROUND 7. SOIL REQUIREMENTS :
SITE CLASSIFICATION TO BE A, S OR M ONLY. SOIL SAFE BEARING CAPACITY VALUE INDICATED ON DRAWING SHEET 4 DK4
OCCURS AT 100mm BELOW FINISH GRADE, EXISTING NATURAL GRADE, OR AT FROST DEPTH SPECIFIED BY LOCAL
BUILDING DEPARTMENT, WHICHEVER IS THE LOWEST ELEVATION. REGARDLESS OF DETAIL Y ON SHEET 4 THE MINIMUM
FOUNDATION DEPTH SHOULD BE 100MM INTO NATURAL GROUND OR BELOW FROST DEPTH SPECIFIED BY LOCAL COUNCIL.
ROLLED OR COMPACTED FILL MAY BE USED UNDER SLAB, COMPACTED IN 150mm LAYERS TO A MAXIMUM DEPTH OF 900mm.
CONCRETE FOUNDATION EMBEDMENT DEPTHS DO NOT APPLY TO LOCATIONS WHERE ANY UNCOMPACTED FILL OR DISTURBED
SCHEDULE OF OPENINGS
GROUND EXISTS OR WHERE WALLS OF THE EXCAVATION WILL NOT STAND WITHOUT SUPPLEMENTAL SUPPORT, IN THIS
CASE SEEK FURTHER ENGINEERING ADVICE.
8. CLASS 10a or Class 7 FOOTING DESIGNS:
THE FOUNDATION DOCUMENTED IS ALSO APPROPRIATE FOR CLASS 10a or CLASS 7 BUILDING DESIGNS ON 'M-D', 'H', 2.80H X 3.40 CB
'H-D' OR 'E' CLASS SOILS, IF TOTAL SLAB AREA IS UNDER 100m SQUARE AND THE MAXIMUM SLAB DIMENSION (LENGTH 1 3340 2780* *SERIES A
SINGLE Z15012P NO
AND WIDTH) IS LESS THAN OR EQUAL TO 12m.
LENGTH x WIDTH PLEASE BE AWARE THAT THE SLAB DESIGN FOR H & E CLASS SOILS IN THESE INSTANCES ARE DESIGNED TO
EXPERIENCE SOME CRACKING. THIS CRACKING IS NOT CONSIDERED A STRUCTURAL FLAW OR DESIGN ISSUE, AND IS
2 3340 2780*
2.80H X 3.40 CB
*SERIES A
SINGLE Z15012P NO
SIMPLY COSMETIC IN NATURE. IF THIS IS A CONCERN TO THE CLIENT IT IS ADVISED THEY DISCUSS OTHER OPTIONS EXTERNAL PA DOOR
WITH THE RELEVANT DISTRIBUTOR PRIOR TO THE POURING OF THE SLAB. 3 920 2040 920 WIDE
SINGLE NO
9. CONCRETE REQUIREMENTS :
ALL CONCRETE DETAILS AND PLACEMENT SHALL BE PERFORMED IN ACCORDANCE WITH AS2870 AND AS3600.CONCRETE
SHALL HAVE A MIN. 28-DAY STRENGTH OF 20MPa FOR EXPOSURE A1, 25MPa FOR EXPOSURE A2, 32MPa FOR EXPOSURE 4 1510 790 WINDOW SINGLE YES
400 x 400 x 500 B1, 40MPa FOR EXPOSURE B2 AND 50MPa FOR EXPOSURE C, IN ACCORDANCE WITH SECTION 4, AS3600. CEMENT TO BE
TYPE A. MAX AGGREGATE SIZE OF 20mm. SLUMP TO BE 80mm +-15mm. SLABS TO BE CURED FOR 7 DAYS BY WATERING OR
COVERING WITH A PLASTIC MEMBRANE, AFTER WHICH CONSTRUCTION CAN BEGIN, DUE CARE GIVEN NOT TO OVER-TIGHTEN
5 1510 790 WINDOW SINGLE YES
HOLD DOWN BOLTS. GIVEN ALLOWABLE SOIL TYPES 1 LAYER OF SL72 REINFORCING MESH IS TO BE INSTALLED ON
6
Length x Width x Depth (mm) STANDARD SLABS WITH A MINIMUM 30MM COVER FROM CONCRETE SURFACE. CONCRETE REINFORCING TO CONFORM TO AS
1302, AS1303 & AS 1304. ALL REINFORCING COVER TO BE A MINIMUM OF 30mm.
1510 790 WINDOW SINGLE YES
10. STRUCTURAL STEEL REQUIREMENTS :
ALL STRUCTURAL STEEL, INCLUDING SHEETING THOUGH EXCLUDING CONCRETE REINFORCING, SHALL CONFORM TO AS 1397
7 1510 790 WINDOW SINGLE YES
(GAUGE <= 1mm fy = 550MPa, GAUGE > 1mm < 1.5mm fy = 500MPa, GAUGE >= 1.5mm fy = 450MPa). NOTES: 1) SEE SHEET 5 FOR DOOR OPENING FRAMING INFORMATION.
NO WELDING IS TO BE PERFORMED ON THIS BUILDING. 2) ALL DOOR SCHEDULE MEASUREMENTS ARE ACTUAL DOOR/WINDOW SIZE NOT
N.G.L - NATURAL GROUND LINE ALL STRUCTURAL MEMBERS AND CONNECTIONS DESIGNED TO AS4600. ALL BOLT HOLE DIAMETERS TO STRAMIT GENERAL OPENING SIZE.
PUNCHINGS.
DWG NO:
11. FOOT TRAFFIC :
* ROLLER DOOR OPENING HEIGHT DEPENDENT ON FINAL BUILD LOCATION.
Y BLOCK LOCAL THICKENING DETAIL SBLMA FOR ERECTION AND MAINTENANCE PLEASE NOTE THE FOLLOWING DEFINED FOOT TRAFFIC ZONES:
- CORRUGATED: WALK ONLY WITHIN 200MM OF SCREW LINES. FEET SPREAD OVER AT LEAST TWO RIBS.
- MONOCLAD: WALK ONLY IN PANS, OR ON RIBS AT SCREW LINES.
STEEL BUILDING BY (CONTACT) Mr Timothy Roy Messer BE MIEAust RPEQ
Civil & Structural Engineers
JUST SHEDS SUNSHINE COAST & GYMPIE
4
50 Punari Street
CSTS66660
Currajong, Qld 4812
23/9/2025
FOR 07 5445 8532 Fax: 07 4725 5850 Signature ............................................................
STR
TM
AT
ENAYET KHAN Email: [email protected]
ABN 341 008 173 56 Date ......................................
23/9/2025
7
Registered Chartered Professional Engineer Regn. No. 2558980
Registered on the NPER in the areas of practice
14-16 ACTION ST, Registered Professional Engineer (Civil & Structural) QLD
Registered Certifying Engineer (Structural) N.T.
Regn. No. 9985
Regn. No. 116373ES of Civil & Structural National Professional
NOOSAVILLE Registered Engineer - (Civil) VIC
Registered Engineer - (Civil) TAS
Regn. No. PE0002216
Regn. No. CC5648M Engineers Register
Page 5
MEMBER AND MATERIAL SCHEDULE
1 END WALL RAFTER Single C15019
2 C.S. FRAME RAFTER Double C15019
3 END FRAME COLUMN (C1) Single C15019
4 END FRAME MONO COLUMN (C1) Single C15019
5 C.S. FRAME COLUMN (C4) Double C15019
6 C.S. FRAME MONO COLUMN (C2) Double C15024
7 MULLION (C3) Single C15012
8 C.S. FRAME KNEE BRACE Single [email protected] LONG 4 bolts each end
9 KNEE BRACE HEIGHT UP COLUMN 2.18m
10 KNEE BRACE LENGTH UP RAFTER 0.76m
11 C.S. FRAME APEX BRACE Single [email protected] LONG 4 bolts each end
12 APEX POSITION FROM RAFTER END 0.84m
13 ANCHOR BOLTS (# PER DETS.) Screw Anchor 12mm x 100 Galv
14 LOWER EAVE PURLIN C10010 (Eave Purlin Bracket 0mm from top of column)
15 UPPER EAVE PURLIN C15012 (Eave Purlin Bracket 7mm down from top of column) ^
16 TYP. ROOF PURLIN SIZE Z10019
17 MAIN BLDG. PURLIN SPACING 0.860 m. (6 rows) (Max Allow. 1.000m)
18 MAIN BLDG. PURLIN LENGTH 4.95 m. (0.45m Overlap)
19 TYP. SIDEWALL GIRT SIZE Z10019
20 MAIN BLDG. SIDEWALL GIRT SPACING 0.916 m. (3 rows) (Max Allow. 1.299m)
21 MAIN BLDG. HIGH SIDEWALL GIRT SPACING 1.091 m. (3 rows)
22 MAIN BLDG. SIDEWALL GIRT LENGTH 4.95 m. (0.45m Overlap)
23 TYP. ENDWALL GIRT SIZE Z10019
24 MAIN BLDG. ENDWALL GIRT SPACING 0.972 m. (3 rows) (Max Allow. 1.299m)
25 MAIN BLDG. ENDWALL GIRT LENGTH 3.05 m. (0.3m Overlap)
26 FRAME SCREW FASTENERS 14-13x22 Hex C/S (SP HD 5/16' Hex Drive)
27 FRAME BOLT FASTENERS Purlin Assy M12x30 Z/P
28 PURLIN/GIRT FASTENERS Purlin Assy M16x30 Z/P
29 X-BRACING STRAP AND FASTENERS 32 x 1.6mm Strap with 4 x 14g Tek Screws Each End
30 WALL COLOUR SURFMIST
31 ROOF COLOUR SURFMIST
32 ROLLER DOOR COLOUR SURFMIST
33 P.A. DOOR COLOUR SURFMIST
34 WINDOW COLOUR SURFMIST
35 DOWNPIPE COLOUR SURFMIST
BAY WIDTH BAY WIDTH 36 GUTTER COLOUR SURFMIST
37 CORNER FLASHING COLOUR SURFMIST
38 BARGE FLASHING COLOUR SURFMIST
39 OPENING FLASHING COLOUR SURFMIST
40 OPEN BAY HEADER HEIGHT 0.5
C150 EAVE
PURLIN
RAFTER
MFA100
BRACKET EAVE PURLIN
BRACKET
"Z" JAMB
Z100 GIRT COLUMN
* Minimum 8x 14g Tek Screws
Per MFA Connection,
4 Screws Per Leg of Bracket
^ NOTE: Upper Eave Purlin Positioned with bottom lip against Eave Purlin Bracket.
STEEL BUILDING BY (CONTACT) Mr Timothy Roy Messer BE MIEAust RPEQ
Civil & Structural Engineers
JUST SHEDS SUNSHINE COAST & GYMPIE
5
50 Punari Street
CSTS66660
Currajong, Qld 4812
23/9/2025
FOR 07 5445 8532 Fax: 07 4725 5850 Signature ............................................................
STR
TM
AT
ENAYET KHAN Email: [email protected]
ABN 341 008 173 56 Date ......................................
23/9/2025
7
Registered Chartered Professional Engineer Regn. No. 2558980
Registered on the NPER in the areas of practice
14-16 ACTION ST, Registered Professional Engineer (Civil & Structural) QLD
Registered Certifying Engineer (Structural) N.T.
Regn. No. 9985
Regn. No. 116373ES of Civil & Structural National Professional
NOOSAVILLE Registered Engineer - (Civil) VIC
Registered Engineer - (Civil) TAS
Regn. No. PE0002216
Regn. No. CC5648M Engineers Register
Page 6
SBOBSRZDR SBOBSWZDC
StrapBracingRoof StrapBracingWall
STRAP BRACE STRAP
BRACE
Z-PURLIN DOUBLE
STRAP STRAP DOUBLE
COLUMN BRACE COLUMN
BRACE
Z-GIRT
Z-PURLIN
Z-GIRT
TEK SCREWS*
TEK SCREWS*
TEK SCREW
DOUBLE RAFTER
TEK SCREW
DOUBLE RAFTER
A SIDE VIEW B 3D VIEW
A ELEVATION VIEW B 3D VIEW
* 32mm STRAP TO HAVE MINIMUM 4-14G SCREWS 32mm STRAP TO HAVE MINIMUM 4-14G SCREWS
* 38mm & 50mm STRAP TO HAVE MINIMUM 5-14G SCREWS 38mm & 50mm STRAP TO HAVE MINIMUM 5-14G SCREWS
STRAP BRACE TEK SCREWED TO UNDERSIDE OF PURLIN.
ROOF STRAP BRACE DETAIL A STRAP BRACE IS BENT OVER GIRT AND TEK SCREWED TO FLANGE OF COLUMN. WALL STRAP BRACE DETAIL B
REFER TO MEMBER SCHEDULE ON THE ENGINEERING PLANS Z-PURLIN 6 REFER TO MEMBER SCHEDULE ON THE ENGINEERING PLANS FOR TEK SCREWS Z-GIRT 6
FOR TEK SCREWS AND STRAP BRACE SPECIFICATIONS. AND STRAP BRACE SPECIFICATIONS.
STEEL BUILDING BY (CONTACT) Mr Timothy Roy Messer BE MIEAust RPEQ
Civil & Structural Engineers
JUST SHEDS SUNSHINE COAST & GYMPIE
6
50 Punari Street
CSTS66660
Currajong, Qld 4812
23/9/2025
FOR 07 5445 8532 Fax: 07 4725 5850 Signature ............................................................
STR
TM
AT
ENAYET KHAN Email: [email protected]
ABN 341 008 173 56 Date ......................................
23/9/2025
7
Registered Chartered Professional Engineer Regn. No. 2558980
Registered on the NPER in the areas of practice
14-16 ACTION ST, Registered Professional Engineer (Civil & Structural) QLD
Registered Certifying Engineer (Structural) N.T.
Regn. No. 9985
Regn. No. 116373ES of Civil & Structural National Professional
NOOSAVILLE Registered Engineer - (Civil) VIC
Registered Engineer - (Civil) TAS
Regn. No. PE0002216
Regn. No. CC5648M Engineers Register
Page 7
CORRUGATED MONOCLAD
ROOF CLADDING. WALL CLADDING.
MONOCLAD
WALL CLADDING.
9000 9000
1 SIDEWALL EXTERIOR ELEVATION 2 SIDEWALL EXTERIOR ELEVATION
7 SCALE: 1 = 100 7 SCALE: 1 = 100
TO PEAK TO PEAK
525
TO EAVE
(NOMINAL)
3525
3525
3000
TO CONCRETE TO CONCRETE
6000 6000
4 ENDWALL EXTERIOR ELEVATION 3 ENDWALL EXTERIOR ELEVATION
7 SCALE: 1 = 100 7 SCALE: 1 = 100 BUILDING COLOURS
WALL SURFMIST
ROOF SURFMIST
ROLLER DOOR SURFMIST
P.A. DOOR SURFMIST
WINDOW SURFMIST
DOWNPIPE SURFMIST
GUTTER SURFMIST
CORNER FLASHING SURFMIST
BARGE FLASHING SURFMIST
OPENING FLASHING SURFMIST
STEEL BUILDING BY (CONTACT) Mr Timothy Roy Messer BE MIEAust RPEQ
Civil & Structural Engineers
JUST SHEDS SUNSHINE COAST & GYMPIE
7
50 Punari Street
CSTS66660
Currajong, Qld 4812
23/9/2025
FOR 07 5445 8532 Fax: 07 4725 5850 Signature ............................................................
STR
TM
AT
ENAYET KHAN Email: [email protected]
ABN 341 008 173 56 Date ......................................
23/9/2025
7
Registered Chartered Professional Engineer Regn. No. 2558980
Registered on the NPER in the areas of practice
14-16 ACTION ST, Registered Professional Engineer (Civil & Structural) QLD
Registered Certifying Engineer (Structural) N.T.
Regn. No. 9985
Regn. No. 116373ES of Civil & Structural National Professional
NOOSAVILLE Registered Engineer - (Civil) VIC
Registered Engineer - (Civil) TAS
Regn. No. PE0002216
Regn. No. CC5648M Engineers Register
Page 8
NOTES:
BRACING MATERIALS - THE SHED ERECTOR TO SUPPLY SPECIFIC BRACING.
GUIDE TO(REFER
THE INSTALLATION OF TEMPORARY BRACING
TO INSTALLATION GUIDE MANUAL FOR THE TWO METHODS OF CONSTRUCTION)
SUITABLE RIGID MEMBERS CAPABLE OF TENSION AND COMPRESSION OR OPPOSING CHAINS OR
OPPOSING LOAD RATED RATCHET STRAPS TO BE USED. (RIGID BRACING AS SHOWN ON
DIAGRAM) ROPE BRACING SUITABLE ONLY FOR SMALLER STRUCTURES IN IDEAL CONDITIONS.
BRACING LOCATION - TEMPORARY BRACING TO BE ERECTED AS CLOSE
TO 45 DEGREE ANGLE AND FIXED TO THE TOP OF THE COLUMN OR MULLION TO
ACHIEVE THE OPTIMUM EFFECTIVENESS. IF THERE IS NOT ENOUGH SPACE FOR A
45 DEGREE ANGLE, THEN 20 DEGREE ANGLE IS TO BE THE MINIMUM ANGLE
ALLOWED (REFER TO DIAGRAM). RIGID TEMPORARY BRACING MEMBER TO BE BOLTED
TO HEAVY ANGLE PEGS HAMMERED INTO THE GROUND OR TO A BRACKET, MASONRY
ANCHORED TO THE SLAB.
BRACING REMOVAL - TEMPORARY BRACING TO REMAIN IN PLACE UNTIL
CLADDING IS FULLY INSTALLED WHERE POSSIBLE. IN NO CASE SHOULD TEMPORARY
BRACING BE REMOVED UNTIL ALL PURLINS, GIRTS (AND PERMANENT CROSS BRACING
WHERE USED) ARE FIXED.
SITE SAFETY - DUE CONSIDERATION TO BE GIVEN TO SITE SAFETY IN REGARD
TO LOCATIONS OF BRACING AND PEGS.
GUIDE APPLICATION - TEMPORARY BRACING AS DESCRIBED IS A MINIMUM
REQUIREMENT FOR AN AVERAGE, STANDARD SITE CONDITION. PROVIDE ADDITIONAL
BRACING FOR MORE SEVERE AND/OR HIGH EXPOSURE SITE CONDITIONS.
ADDITIONAL BRACING TO BE USED AS AND WHERE NECESSARY TO ENSURE THAT
ENTIRE FRAME IS RIGID THROUGHOUT CONSTRUCTION.
RESPONSIBILITY FOR ENSURING STABILITY OF STRUCTURE REMAINS WITH THE BUILDER.
1C TILT UP METHOD DIAGRAM
1 TEMPORARY BRACING LOCATION
TILT UP METHOD
FOR STRUCTURES UNDER 9M SPAN, LESS THAN 3M HIGH AND LESS THAN 12M LONG
1 TILT UP METHOD DIAGRAM
A. ASSEMBLE THE FIRST SIDEWALL FRAME (COMPLETE WITH WALL SHEETING, BRACING 1
AND GUTTER) ON THE GROUND AND LIFT ASSEMBLED SIDEWALL FRAME INTO POSITION.
FIX OFF TEMPORARY SIDE BRACING TO EACH END (REFER TO DIAGRAM). FIX BASE CLEATS.
B. ASSEMBLE THE SECOND SIDEWALL FRAME AS PER FIRST SIDEWALL FRAME.
LIFT INTO POSITION. FIX OFF TEMPORARY WALL BRACING TO EACH END (REFER TO DIAGRAM)
FIX BASE CLEATS.
C. FIX GABLE END RAFTERS TO COLUMNS TO TIE WALLS. PROP APEX UNTIL ENDWALL MULLION
AND APEX TEMPORARY BRACE ARE FIXED OFF. IF NO MULLION IS REQUIRED THEN PROP AND
BRACE APEX UNTIL CLADDING IS COMPLETE.
D. INSTALL REMAINING RAFTERS. AS EACH RAFTER PAIR IS INSTALLED, AT LEAST ONE PURLIN
PER 3M OF RAFTER LENGTH IS TO BE INSTALLED TO SECURE RAFTERS.
E. INSTALL REMAINING PURLINS
F. INSTALL KNEE AND APEX BRACES IF AND WHERE APPLICABLE.
G. REPEAT FOR LEANTO'S.
FRAME FIRST METHOD
FOR STRUCTURES OVER 9M SPAN, GREATER THAN 3M HIGH AND GREATER THAN 12M LONG
A. ASSEMBLE PORTAL FRAMES ON THE GROUND (WITH KNEE AND APEX BRACES IF AND
WHERE APPLICABLE). LIFT THE FIRST PORTAL FRAME ASSEMBLY INTO POSITION.
FIX OFF TEMPORARY END BRACING (REFER TO DIAGRAM). FIX BASE CLEATS.
B. PROP APEX UNTIL ENDWALL MULLION AND APEX TEMPORARY BRACE ARE FIXED OFF.
IF NO MULLION IS REQUIRED THEN PROP AND BRACE APEX UNTIL CLADDING IS COMPLETE.
C. THE SECOND PORTAL FRAME ASSEMBLY TO BE LIFTED INTO POSITION. FIX EAVE PURLINS
AND AT LEAST ONE PURLIN PER 3M OF RAFTER TO SECURE FRAME ASSEMBLY.
FIX BASE CLEATS. FIX TEMPORARY SIDEWALL BRACING.
D. STAND REMAINING PORTAL FRAME ASSEMBLY AS PER STEP C, FIXING TEMPORARY SIDE WALL
2C FRAME FIRST METHOD DIAGRAM
BRACING TO EVERY SECOND BAY. BRACE OTHER END PORTAL FRAME AS PER FIRST PORTAL
1 TEMPORARY BRACING LOCATION
FRAME.
E. INSTALL REMAINING PURLINS AND GIRTS.
F. REPEAT FOR LEANTO'S. 2 FRAME FIRST METHOD DIAGRAM
NOT PART OF COUNCIL APPLICATION DOCUMENTATION 1
STEEL BUILDING BY
JUST SHEDS SUNSHINE COAST & GYMPIE
CSTS66660
23/9/2025
07 5445 8532
TEMP BRACING
FOR
STR
TM
AT
ENAYET KHAN
14-16 ACTION ST,
NOOSAVILLE
Page 9
90
BASE PLATE
SLAB EDGE
208
148
102
COLUMN
DETAIL B
SLAB EDGE
COLUMN
58
9000
BASE PLATE
4500 4500
102
148
208
DETAIL C
CL FRAME
56
3000
3000
BASE PLATE
208
C
148
102
6000
6000
COLUMN
DETAIL D SLAB EDGE
3000
3000
D B
1 BOLT LAYOUT PLAN
1 SCALE: 1 = 100
IF YOU HAVE A ROLLER DOOR IN THE GABLE END OF YOUR SHED, CONTACT YOUR
NOT PART OF COUNCIL APPLICATION DOCUMENTATION DISTRIBUTOR TO SEE IF MULLION NEEDS TO BE ROTATED FOR USE AS A DOOR JAMB.
STEEL BUILDING BY
JUST SHEDS SUNSHINE COAST & GYMPIE
CSTS66660
23/9/2025
07 5445 8532
BOLT LAYOUT PLAN
FOR
STR
TM
AT
ENAYET KHAN
14-16 ACTION ST,
NOOSAVILLE
Page 10
Compliance certificate for
Form 15 building design or specification
This form is to be used by an appointed competent person for the purposes of section 10 of the Building Act 1975 and sections 73
and 77 of the Building Regulation 2021 (Design-specification certificate) stating that an aspect of building work or specification will, if
installed or carried out as stated in this form, comply with the building assessment provisions.
Additional explanatory information is included in the Appendix at the end of this form.
1. Property description Street address (include number,street, suburb / locality and postcode)
This section need only be completed if
details of street address and property
description are applicable.
State: Postcode :
E.g. In the case of (standard/generic)
pool design/shell manufacture and/or
patio and carport systems this section
Lot and plan details (attach list if necessary)
may not be applicable.
Lot No: SP/RP :
The description must identify all land the
subject of the application Local government area the land is situated in?
.
The lot & plan details (eg. SP / RP) are
shown on the title documents or a rates notice.
If the plan is not registered by title, provide
previous lot and plan details.
2. Description of aspect/s
certified
Clearly describe the extent of work covered by
this certificate. e.g all structural aspects of the
steel roof beams.
3. Basis of certification
Australian Standards (list) AS/NZS 4600-2018, AS/NZS 1170.0,.1-2002, 1170.2-2021, 1170.3-2003,
Detail the basis for giving the certificate and the
extent to which tests, specifications, rules,
standards, codes of practice and other
1170.4-2007, AS2870-2011, AS3600-2018, AS5216-2021
publications were relied upon.
National Construction Code of Australia NCC Building Classification =
Region AS1170.2 = Annual Probability Exceedance wind =
NCC Importance Level = NCC Equivalent Wind class =
Factor for Region =
Regional 3 s Gust Wind Speed for annual probability of exceedance V R= m/s
Wind directional multipliers for the 8 cardinal directions Md =
Terrain/Height multiplier (Mz, Cat) = Shielding Multiplier M s=
Topographic multiplier Mt = Design Wind Speed = m/s
External Pressure Coefficent cpe =
Internal Pressure Coefficent cpi =
Design Roof Live Load =
Building Regulation 2021 * Section 73 and 77 * Form 15 * Version 2 * March 2023 Page 1 of 3
Page 11
4. Reference documentation
Clearly identify any relevant documentation, Drawing Nos:
e.g. numbered structural engineering plans.
TO BE READ IN CONJUNCTION WITH PAGES 1 TO
FOR JOB NO. DATED :
Specifications:
Computations:
Test Reports:
Other Documentation:
5. Building certifier reference Building certifier reference number
number and building
development application
number
Building development application number (if available)
6. Appointed competent Name (in full)
person details
Under Part 6 of the Building Regulation, a
Timothy Roy Messer
person must be assessed as a competent for
the type of work (design specification) by the
Company name (if applicable) Contact person
relevant building certifier. Northern Consulting Engineers Timothy Roy Messer
Business phone number Mobile number
(07) 47 25 55 50 (07) 47 25 55 50
Email address
[email protected]
Postal address
50 Punari Street, Currajong, QLD
State QLD Postcode: 4812
Licence class or registration type (if applicable)
Structural and Civil
Licence or registration number (if applicable)
RPEQ 9985
7. Signature of appointed Signature Date
competent person
This certificate must be signed by the individual
assessed and appointed by the building certifier
as competent to give design specification help. Mr Timothy Roy Messer
LOCAL GOVERNMENT USE ONLY
Date received Reference Number/s
Building Regulation 2021 * Section 73 and 77 * Form 15 * Version 2 * March 2023 Page 2 of 3
Page 12
Appendix - explanatory information
IMPORTANT NOTE: It is an offence for a competent person to give a building certifier a document, including this form, that the person knows
or reasonably suspects, is false or misleading.
Who can complete this certificate? (section 10 of the Building Act 1975 (Building Act) and 73 and 77 of the Building Regulation 2021 (BR
2021).
A building certifier can accept from a competent person (design-specification) a certificate stating that the competent person has assessed the
building design or specification for the aspect of building work, and it will, if installed or carried out under the certificate, comply with the building
assessment provisions, including any relevant standards and codes.
Schedule 10 of the BR 2021 defines building design or specification as any material, system, method of building or other thing related to the
design of or specifications for building work.
When completing the certificate, a competent person is required under section 77 of the BR 2021 to include the basis for giving the certificate
and state the extent to which the competent person has relied on tests, specifications, rules, standards, codes of practice or other publications.
What is the purpose of this form? (section 10 of the Building Act and sections 73 and 77 of the BR2 2021)
The information in this form informs the building certifier's decision making when they are assessing a building development application, issuing
the building development approval for the building work the subject of the certificate (form) and when amending the building development
approval due to the receipt of updated aspect information such as glazing or truss specifications or revised excavation drawings.
Can a manufacturer or supplier give this Form 15 ?
A building certifier can accept this form from a manufacturer or supplier who the certifier has decided is a competent person
(design-specification).
A manufacturer or supplier of building materials can give this form if they have undertaken the design component for the product. For example a
window manufacturer who designs, constructs and supplies the windows to industry could give this form.
Competent person (section 10 of the Building Act 1975 and Part 6 of the BR 2021)
A building certifier must assess and decide to appoint an individual as a competent person before they can accept design-specification help.
When deciding whether a person can be a competent person, the building certifier must assess the person having regard to their experience,
qualifications and skills and ensure the person holds a licence or registration if required.
The building certifier is required to keep detailed records about what was considered when appointing a competent person.
For further information about assessment of someone as a competent person refer to the Guideline for the assessment of competent
persons.
What is required if a manufacturer or supplier did not do the design work for the product?
A manufacturer or supplier who is not part of the design process may give the construction contractor, builder, competent person or the building
certifier evidence of suitability such as a product technical statement under Part A5 of the Building Code of Australia (BCA), for an aspect or
material stating that it is compliant with the relevant reference documents in the BCA i.e. the applicable Australian Standard/s.
What if there is not enough space for all the supporting material/documents?
Items 2, 3 and 4 requires the competent person to clearly identify the extent of the assessment that was undertaken for aspect/s of work
identified in this form.
For instance, there is provision for material such as specifications, standards, codes or other relevant publications to be referenced in the form.
However, if the space in the form is not sufficient to accommodate all of this material, you can create and refer to additional material in an
addendum or attachment to the form.
The form is the Microsoft Word version, that you can download and edited to include additional material in the relevant parts of the form. Note:
that editing the form in the Microsoft Word version may cause the relevant boxes to expand and increase the length of the document. This is
acceptable and does not change the approved form, provided the section text (description on the left-hand side of the page) is not altered.
Appointed competent person (design-specification) - (sections 34 and 36 of the BR 2021 )
A building certifier must assess and decide to appoint an individual as a competent person before they can, as a competent person, give
design-specification help. The building certifier is required to keep detailed records about what was considered when appointing a competent
person.
A building certifier must be satisfied that an individual is competent to give the type of help having regard to the individual's experience,
qualifications and skills and if required by law to hold a licence or registration, that the individual is appropriately registered or licensed.
An individual is appointed as competent to give design-specification help on or from a particular day.
For further information about assessment of someone as a competent person refer to the Guideline for the assessment of competent
persons.
PRIVACY NOTICE
The Department of Energy and Public Works is collecting personal information as required under the Building Act 1975. This information may
be stored by the Department, and will be used for administration, compliance, statistical research and evaluation of building laws. Your personal
information will be disclosed to other government agencies, local government authorities and third parties for purposes relating to administering
and monitoring compliance with the Building Act 1975. Personal information will otherwise only be disclosed to third parties with your consent or
unless authorised or required by law.
Building Regulation 2021 * Section 73 and 77 * Form 15 * Version 2 * March 2023 Page 3 of 3