                                                                                                                                       STRUCTURAL GENERAL NOTES
                                                                                                          1.   GOVERNING CODE   : NATIONAL CONSTRUCTION CODE (NCC), LOADING TO AS1170 - ALL SECTIONS. BUILDING SUITABLE AS
                                                                                                              EITHER A PRIVATE GARAGE CLASS 10A, OR A FARM SHED (CLASS 7 OR 8),UNLESS OTHERWISE SPECIFICALLY NOTED.
                                                                                                              FOR USE AS A FARM SHED, IT MUST MEET THE FOLLOWING REQUIREMENTS:
                                                                                                                  - BE LESS THAN 2000 SQM IN AREA (INCLUSIVE OF ANY MEZZANINE FLOOR AREA).                                                                                    PROJECT DESIGN CRITERIA
                                                                                                                  - MUST BE LOCATED ON A FARM AND USED IN CONNECTION WITH FARMING PURPOSES.
                                                                                                                  - BUILDING IS NOT TO BE OCCOUPIED FREQUENTLY NOR FOR EXTENDED PERIODS BY PEOPLE, WITH A MAXIMUM OF 1                                                                               0.25 kPa
                                                                                                                     PERSON PER 200 SQM OR 2 PERSONS MAXIMUM IN TOTAL WHICHEVER IS THE LESSER.
                                                                                                          2. DRAWING OWNERSHIP      :                                                                                                                                                                     VR 57 m/s
                                                                                                              THESE DRAWINGS REMAIN THE PROPERTY OF FBHS (AUST) PTY LIMITED. ENGINEERING SIGNATURE AND
                                                                                                               CERTIFICATION IS ONLY VALID WHEN BUILDING IS SUPPLIED BY A DISTRIBUTOR OF FBHS. DRAWINGS ARE PROVIDED                                                                                   VsitB 41.3 m/s
                                                                                                              FOR THE DUAL PURPOSE OF OBTAINING BUILDING PERMITS AND AIDING CONSTRUCTION. ANY OTHER USE OR
                                                                                                               REPRODUCTION IS PROHIBITED WITHOUT WRITTEN APPROVAL FROM FBHS.
                                                                                                          3. DRAWING SIGNATURE REQUIREMENTS         :                                                                                                                                          Reg B1
                                                                                                              THESE DRAWINGS ARE NOT VALID UNLESS SIGNED BY THE ENGINEER. THE ENGINEER ACCEPTS NO LIABILITY OR
                                                                                                               RESPONSIBILITY FOR DRAWINGS WITHOUT A SIGNATURE. EACH TITLE BLOCK CONTAINS A WATER MARK UNDER THE                                                                                                     1.08
                                                                                                               CUSTOMERS NAME CONTAINING THE DATE OF PRODUCTION OF THE DRAWINGS; THE DRAWINGS ARE TO BE SUBMITTED TO
                                                                                                               COUNCIL WITHIN 21 DAYS OF THIS DATE. THIS IS TO ENSURE THAT ONLY CURRENT DRAWINGS ARE IN CIRCULATION.                                                                                              0.95
                                                                                                          4. CONTRACTOR RESPONSIBILITIES       :
                                                                                                              CERTIFIER AND CONTRACTOR TO CONFIRM [ON SITE] THAT THE WIND LOADINGS APPLIED TO THIS DESIGN ARE TRUE                                                                                                    N/A
                                                                                                              AND CORRECT FOR THE ADDRESS STATED IN THE TITLE BLOCK.
                                                                                                              CONTRACTOR SHALL VERIFY AND CONFIRM ALL EXISTING CONDITIONS AND DIMENSIONS. ENGINEER SHALL BE NOTIFIED                                                                                              N/A
                                                                                                               OF ANY DISCREPANCIES BETWEEN DRAWINGS AND EXISTING CONDITIONS PRIOR TO START OF WORK.
                                                                                                               CONTRACTOR MUST NOT MAKE ANY DEVIATION FROM THE PROVIDED PLANS WITHOUT FIRST OBTAINING WRITTEN APPROVAL
                                                                                                              FROM ONE THE UNDERSIGNING ENGINEERS. THE ENGINEER / FBHS TAKE NO RESPONSIBILITY FOR CHANGES MADE                                                                                  N/A
                                     WALL                           BASE CLEAT
                                                                                                               WITHOUT WRITTEN APPROVAL.
                                                                                                               CONTRACTOR IS RESPONSIBLE FOR ENSURING NO PART OF THE STRUCTURE BECOMES OVERSTRESSED DURING                                                                                                TCat 3
                                                                                                               CONSTRUCTION.
                                 CLADDING                                                  REINFORCING         BUILDING IS NOT STRUCTURALLY ADEQUATE UNTIL THE INSTALLATION OF ALL COMPONENTS AND DETAILS SHOWN IS                                                                                                           100 kPa
                                                                       2 SCREW                                 COMPLETED IN ACCORDANCE WITH THESE DRAWINGS.
                                                                                           MESH               THE INDICATED DRAWING SCALES ARE APPROXIMATE. DO NOT SCALE DRAWINGS FOR CONSTRUCTION PURPOSES.
                                                                                                              FOR FUTHER DIRECTIONS ON CONSTRUCTION THE CONTRACTOR SHOULD CONSULT THE APPROPRIATE INSTRUCTION MANUAL.
                                                                                                                                                                                                                                                                                                    1:500
                                                                       ANCHORS                            5. ENGINEERING :                                                                                                                                                                       -0.61
                                                                       PER COLUMN                             THE ENGINEER / FBHS ARE NOT ACTING AS PROJECT MANAGERS FOR THIS DEVELOPMENT, AND WILL NOT BE PRESENT
                                                                                                              DURING CONSTRUCTION.
                                  N.G.L                                                                       THE UNDERSIGNING ENGINEERS HAVE REVIEWED THIS BUILDING FOR CONFORMITY ONLY TO THE STRUCTURAL DESIGN                                                                                 0.58
                                                                                                              PORTIONS OF THE GOVERNING CODE. THE PROJECT MANAGER IS RESPONSIBLE FOR ADDRESSING ANY OTHER CODE
                                                                                                               REQUIREMENTS APPLICABLE TO THIS DEVELOPMENT.                                                                                                                                               2
                                                                                                              THESE DOCUMENTS ARE STAMPED ONLY AS TO THE COMPONENTS SUPPLIED BY FBHS. IT IS THE RESPONSIBILITY OF THE
                                                                                                              PURCHASER TO COORDINATE DRAWINGS PROVIDED BY FBHS WITH OTHER PLANS AND/OR OTHER COMPONENTS THAT ARE PART
                                                                                                               OF THE OVERALL PROJECT. IN CASES OF DISCREPANCIES, THE LATEST DRAWINGS PROVIDED BY FBHS SHALL GOVERN.
                                                                                                               NO ALTERATIONS TO THIS STRUCTURE (INCLUDING REMOVAL OF CLADDING) ARE TO BE UNDERTAKEN WITHOUT THE
                                                                                                               CONSENT OF THE CERTIFYING ENGINEER.
                                                                                                                                                                                                                                                                                              DETAIL KEYS
                                                                                                               OPENINGS SUCH AS WINDOWS AND DOORS NEED TO BE INSTALLED AS PER THE PRODUCT MANUFACTURER'S
                                                                                                              INFORMATION/DETAILS.
                                                                                                              THE BUILDING IS DESIGNED AS A STAND-ALONE BUILDING, NOT RELYING ON ANY ADJACENT BUILDING. IF THE                                                       DK1
                                                                                                              PERMANENT OPENING IS OBSTRUCTED BY ANY ADJACENT BUILDING AND WITHIN A DISTANCE OF 0.5M OF SAID OPENING,




                                                                                                100
                                                                                                              THE DESIGN SHOULD BE REFERRED TO THE DESIGN ENGINEER FOR REVIEW OF INTERNAL PRESSURES AND POSSIBLE
                                                                                                               REDESIGN.                                                                                                                                             DK2
                                                                                                          6. INSPECTIONS :
                                                                                 NATURAL                       NO SPECIAL INSPECTIONS ARE REQUIRED BY THE GOVERNING CODE ON THIS JOB. ANY OTHER INSPECTIONS REQUESTED
                                                                                                                                                                                                                                                                     DK3
                                                                                                               BY THE LOCAL BUILDING DEPARTMENT SHALL BE CONDUCTED AT THE OWNER'S EXPENSE.
                                                                                 GROUND                   7. SOIL REQUIREMENTS      :
                                                                                                              SITE CLASSIFICATION TO BE A, S OR M ONLY. SOIL SAFE BEARING CAPACITY VALUE INDICATED ON DRAWING SHEET 4                                                DK4
                                                                                                               OCCURS AT 100mm BELOW FINISH GRADE, EXISTING NATURAL GRADE, OR AT FROST DEPTH SPECIFIED BY LOCAL
                                                                                                               BUILDING DEPARTMENT, WHICHEVER IS THE LOWEST ELEVATION. REGARDLESS OF DETAIL Y ON SHEET 4 THE MINIMUM
                                                                                                              FOUNDATION DEPTH SHOULD BE 100MM INTO NATURAL GROUND OR BELOW FROST DEPTH SPECIFIED BY LOCAL COUNCIL.
                                                                                                               ROLLED OR COMPACTED FILL MAY BE USED UNDER SLAB, COMPACTED IN 150mm LAYERS TO A MAXIMUM DEPTH OF 900mm.
                                                                                                               CONCRETE FOUNDATION EMBEDMENT DEPTHS DO NOT APPLY TO LOCATIONS WHERE ANY UNCOMPACTED FILL OR DISTURBED
                                                                                                                                                                                                                                                                               SCHEDULE OF OPENINGS
                                                                                                               GROUND EXISTS      OR WHERE WALLS OF THE EXCAVATION WILL NOT STAND WITHOUT SUPPLEMENTAL SUPPORT, IN THIS
                                                                                                               CASE SEEK FURTHER ENGINEERING ADVICE.
                                                                                                          8. CLASS 10a or Class 7 FOOTING DESIGNS:
                                                                                                               THE FOUNDATION DOCUMENTED IS ALSO APPROPRIATE FOR CLASS 10a or CLASS 7 BUILDING DESIGNS ON 'M-D', 'H',                                                                           2.80H X 3.40 CB
                                                                                                              'H-D' OR 'E' CLASS SOILS, IF TOTAL SLAB AREA IS UNDER 100m SQUARE AND THE MAXIMUM SLAB DIMENSION (LENGTH                                                    1   3340    2780*        *SERIES A
                                                                                                                                                                                                                                                                                                                  SINGLE     Z15012P     NO
                                                                                                               AND WIDTH) IS LESS THAN OR EQUAL TO 12m.
                                                      LENGTH x WIDTH                                          PLEASE BE AWARE THAT THE SLAB DESIGN FOR H & E CLASS SOILS IN THESE INSTANCES ARE DESIGNED TO
                                                                                                              EXPERIENCE SOME CRACKING. THIS CRACKING IS NOT CONSIDERED A STRUCTURAL FLAW OR DESIGN ISSUE, AND IS
                                                                                                                                                                                                                                                                          2   3340    2780*
                                                                                                                                                                                                                                                                                                2.80H X 3.40 CB
                                                                                                                                                                                                                                                                                                   *SERIES A
                                                                                                                                                                                                                                                                                                                  SINGLE     Z15012P     NO

                                                                                                              SIMPLY COSMETIC IN NATURE. IF THIS IS A CONCERN TO THE CLIENT IT IS ADVISED THEY DISCUSS OTHER OPTIONS                                                                          EXTERNAL PA DOOR
                                                                                                              WITH THE RELEVANT DISTRIBUTOR PRIOR TO THE POURING OF THE SLAB.                                                                                             3   920     2040        920 WIDE
                                                                                                                                                                                                                                                                                                                  SINGLE                 NO
                                                                                                          9. CONCRETE REQUIREMENTS      :
                                                                                                               ALL CONCRETE DETAILS AND PLACEMENT SHALL BE PERFORMED IN ACCORDANCE WITH AS2870 AND AS3600.CONCRETE
                                                                                                              SHALL HAVE A MIN. 28-DAY STRENGTH OF 20MPa FOR EXPOSURE A1, 25MPa FOR EXPOSURE A2, 32MPa FOR EXPOSURE                                                       4   1510     790         WINDOW         SINGLE               YES


                                                     400 x 400 x 500                                           B1, 40MPa FOR EXPOSURE B2 AND 50MPa FOR EXPOSURE C, IN ACCORDANCE WITH SECTION 4, AS3600. CEMENT TO BE
                                                                                                              TYPE A. MAX AGGREGATE SIZE OF 20mm. SLUMP TO BE 80mm +-15mm. SLABS TO BE CURED FOR 7 DAYS BY WATERING OR
                                                                                                               COVERING WITH A PLASTIC MEMBRANE, AFTER WHICH CONSTRUCTION CAN BEGIN, DUE CARE GIVEN NOT TO OVER-TIGHTEN
                                                                                                                                                                                                                                                                          5   1510     790         WINDOW         SINGLE               YES

                                                                                                               HOLD DOWN BOLTS. GIVEN ALLOWABLE SOIL TYPES 1 LAYER OF SL72 REINFORCING MESH IS TO BE INSTALLED ON
                                                                                                                                                                                                                                                                          6
                                                Length x Width x Depth (mm)                                   STANDARD SLABS WITH A MINIMUM 30MM COVER FROM CONCRETE SURFACE. CONCRETE REINFORCING TO CONFORM TO AS
                                                                                                              1302, AS1303 & AS 1304. ALL REINFORCING COVER TO BE A MINIMUM OF 30mm.
                                                                                                                                                                                                                                                                              1510     790         WINDOW         SINGLE               YES

                                                                                                          10. STRUCTURAL STEEL REQUIREMENTS       :
                                                                                                               ALL STRUCTURAL STEEL, INCLUDING SHEETING THOUGH EXCLUDING CONCRETE REINFORCING, SHALL CONFORM TO AS 1397
                                                                                                                                                                                                                                                                          7   1510     790         WINDOW         SINGLE               YES

                                                                                                              (GAUGE <= 1mm fy = 550MPa, GAUGE > 1mm < 1.5mm fy = 500MPa, GAUGE >= 1.5mm fy = 450MPa).                                                               NOTES: 1) SEE SHEET 5 FOR DOOR OPENING FRAMING INFORMATION.
                                                                                                               NO WELDING IS TO BE PERFORMED ON THIS BUILDING.                                                                                                       2) ALL DOOR SCHEDULE MEASUREMENTS ARE ACTUAL DOOR/WINDOW SIZE NOT
    N.G.L - NATURAL GROUND LINE                                                                                ALL STRUCTURAL MEMBERS AND CONNECTIONS DESIGNED TO AS4600. ALL BOLT HOLE DIAMETERS TO STRAMIT GENERAL                                                 OPENING SIZE.
                                                                                                              PUNCHINGS.
                                                                                             DWG NO:
                                                                                                          11. FOOT TRAFFIC :
                                                                                                                                                                                                                                                                     * ROLLER DOOR OPENING HEIGHT DEPENDENT ON FINAL BUILD LOCATION.

     Y                       BLOCK LOCAL THICKENING DETAIL                                        SBLMA       FOR ERECTION AND MAINTENANCE PLEASE NOTE THE FOLLOWING DEFINED FOOT TRAFFIC ZONES:
                                                                                                              - CORRUGATED: WALK ONLY WITHIN 200MM OF SCREW LINES. FEET SPREAD OVER AT LEAST TWO RIBS.
                                                                                                              - MONOCLAD: WALK ONLY IN PANS, OR ON RIBS AT SCREW LINES.




                                                STEEL BUILDING BY                     (CONTACT)                                                                                                                                                                               Mr Timothy Roy Messer BE MIEAust RPEQ
                                                                                                                                                                                                                                          Civil & Structural Engineers
                                                      JUST SHEDS SUNSHINE COAST & GYMPIE
4




                                                                                                                                                                                                                                                      50 Punari Street
         CSTS66660




                                                                                                                                                                                                                                                  Currajong, Qld 4812
                     23/9/2025




                                                FOR                                 07 5445 8532                                                                                                                                                   Fax: 07 4725 5850 Signature ............................................................
                                          STR
                                  TM




                                                AT
                                                                                 ENAYET KHAN                                                                                                                                            Email: [email protected]
                                                                                                                                                                                                                                                 ABN 341 008 173 56 Date ......................................
                                                                                                                                                                                                                                                                                     23/9/2025
7




                                                                                                                                                                                      Registered Chartered Professional Engineer                    Regn. No. 2558980
                                                                                                                                                                                                                                                                              Registered on the NPER in the areas of practice
                                                                                 14-16 ACTION ST,                                                                                     Registered Professional Engineer (Civil & Structural) QLD
                                                                                                                                                                                      Registered Certifying Engineer (Structural) N.T.
                                                                                                                                                                                                                                                    Regn. No. 9985
                                                                                                                                                                                                                                                    Regn. No. 116373ES           of Civil & Structural National Professional
                                                                                   NOOSAVILLE                                                                                         Registered Engineer - (Civil) VIC
                                                                                                                                                                                      Registered Engineer - (Civil) TAS
                                                                                                                                                                                                                                                    Regn. No. PE0002216
                                                                                                                                                                                                                                                    Regn. No. CC5648M                        Engineers Register

Used in these records

About this file

File size
2.0 MB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Att 2- Engineering.pdf · 2.0 MB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.