                                                                                                                                              BE ADVISED : SOME CLAUSES IN THIS SPECIFICATION MAY NOT BE RELEVANT TO THIS PROJECT

         1.0 GENERAL                                                                                                                                                                                                                                                                                                                                   11.0 CEILINGS
 1.1     ALL DIMENSIONS SHALL BE CHECKED ON SITE PRIOR TO COMMENCEMENT OF ANY WORK                      BUILD IN ALCOR/PGI FLASHINGS AS FOLLOWS:                                 5.11                                                                                                                                                           11.1     CEILINGS SHALL BE RECESSED EDGE, MINIMUM 8.0mm PLASTERGLASS OR GYPROCK.
 1.2     ALL MATERIALS SHALL COMPLY WITH RELEVANT CURRENT AUSTRALIAN STANDARDS AND                      ·    WHEREVER SHOWN ON DRAWINGS                                                                                                                                                                                                         11.2     FLUSH JOINTS, SCREW HEADS, AND OTHER BLEMISHES IN THE SHEETS USING APPROVED SYSTEMS TO
         UNLESS OTHERWISE STATED ON THE PLANS SHALL BE NEW AND THE BEST OF THE THEIR                    ·    CAVITY WALLS BUILT OF SLAB ON GROUND (WHERE NOT PARGED)                                                                                                                                                                                     PROVIDE FLUSH SMOOTH CONTINUOUS SURFACE
         RESPECTIVE KIND AND SUITABLE FOR THEIR INTENDED PURPOSES.                                      ·    OVER LINTELS TO EXPOSED OPENINGS - EXTEND THE FULL WIDTH OF OUTER LEAF CONTINUOUS                                                                                                                                                  11.3     PROVIDE AND FIX ALL FLUSH STOP BEADS & CASING BEADS TO ALL CORNERS & EDGES
 1.3     ALL WORKMANSHIP SHALL COMPLY WITH RELEVANT CURRENT AUSTRALIAN STANDARDS AND TO                      ACROSS CAVITY 50mm INTO INNER LEAF 2c ABOVE                                                                                                                                                                                        11.4     PROVIDE ALL SELECTED MOLDINGS AND CORNICES TO ALL CEILINGS AS SHOWN ON THE DRAWINGS.
         GOOD TRADE PRACTICES
                                                                                                        ·    OVER ROOF - EXTEND THE FULL WIDTH OF EXTERNAL LEAF, STEPPED TO ROOF SLOPE TURNED
 1.4     ALL WORK SHALL BE IN ACCORDANCE WITH REQUIREMENTS OF THE RESPECTIVE AUTHORITY                                                                                                                                                                                                                                                                   12.0 PLASTERING
         HAVING JURISDICTION OVER THE WORKS.                                                                 DOWN MIN. 50mm OVER BASE FLASHING. TURN UP IN CAVITY SLOPING INWARDS AND BUILT INTO                                                                                                                                                12.1     INTERNAL WALL FINISHES INCLUDING CUPBOARD, BIN & FRIDGE RECESSES ETC SHALL BE (OTHER THAN
 1.5     THE ARCHITECTURAL DRAWINGS SHOULD BE READ IN CONJUNCTION WITH THE SPECIFICATION,                    INNER LEAF 1c ABOVE.
                                                                                                                                                                                                                                                                                                                                                         FACE FINISHES OR WHERE COVERED BY FEATURE MATERIALS) FLOAT AND SET IN HARDWALL PLASTER
         SCHEDULES AND CONSULTANTS DRAWINGS THAT FORM PART OF THE CONSTRUCTION DOCUMENTS                ·    DOOR/WINDOW STILES - EXTEND THE FULL HEIGHT 150mm WIDE FIXED TO FRAMES INTERLEAVED
                                                                                                                                                                                                                                                                                                                                                         U.N.O.
         REFERRED TO IN THE "BUILDING CONTRACT".                                                             WITH SILL AND HEAD FLASHING AT EACH END.                                                                                                                                                                                           12.2     PLASTERED WALLS SHALL BE NOMINAL 12mm THICK CONSISTING OF 1:1:9, CEMENT:LIME:SAND RENDER,
 1.6     DO NOT SCALE FROM DRAWINGS. NOTIFY OF ANY ERRORS OR OMISSIONS BEFORE PROCEEDING WITH           ·    STRUCTURE OR SERVICES WITHIN 30mm OF OUTER BRICK LEAF IN CAVITY: VERTICAL FLASHING                                                                                                                                                          AND FINISHED WITH NOMINALLY 3mm HARDWALL PLASTER
         ANY WORKS                                                                                           CONTINUOUS 1c BELOW FL TO ABOVE STRUCTURE OR FRAME. NOMINAL 300m WIDE.                                                                                                                                                             12.3     SUPPLY AND FIX EXTERNAL CORNER BEADS TO ALL EXTERNAL CORNERS.
 1.7     ENSURE THAT SUBSTRATES ARE SUITABLE FOR THE INTENDED SUBSEQUENT FINISHES. COMMENCEMENT         ·    FOR HORIZONTAL STRUCTURES/SERVICES: CONTINUOUS FLASHING BUILT IN AS FOR OVER LINTELS                                                                                                                                               12.4     PROVIDE STOP BEADS WHERE PLASTER WORK ABUTS TIMBER FRAMES, OR FACEWORK
         OF WORK ON THE SUBSTRATES IMPLIES ACCEPTANCE BY THE SUBCONTRACTOR OF THE SUBSTRATES            ·    AT CAVITY WALLS WITH GLASS BLOCK 300mm WIDE FIXED TO GLASS BLOCK FRAME AND TURNED                                                                                                                                                  12.5     EXTERNAL RENDER WHEN APPLICABLE SHALL BE 2 COAT SAND FINISH. (FOR PAINTING).
         ON WHICH FINISHES ARE APPLIED.                                                                      AWAY IN CAVITY FROM INNER LEAF.                                                                                                                                                                                                    12.6     NIBS IN INTERNAL CORNERS ADJACENT TO DOOR FRAMES GREATER THAN 40mm SHALL NOT BE
                                                                                                   5.12 WHERE NECESSARY REINFORCE BELOW AND OVER OPENINGS WITH GALVANISED WOVEN WIRE FABRIC                                                                                                                                                              FLUSHED UP WITH FRAMES.
 1.8     CONTRACTOR IS TO SUPPLY ALL EQUIPMENT NECESSARY FOR THE COMPLETION OF THE RESPECTIVE
         WORKS.                                                                                         75mm    WIDE IN CENTRE OF EACH LEAF OPENING EXTENDING ALUMINIUM OF 600mm BEYOND THE                                                                                                                                                     12.7     PROVIDE V-JOINTS IN RENDER & FINISHING PLASTER WHERE BRICK WORK ABUTS OR JOINS ONTO
 1.9                                                                                                    OPENING.                                                                                                                                                                                                                                         CONCRETE WORK.
         CONTRACTOR IS RESPONSIBLE FOR THE PROGRESSIVE CLEAN UP DURING AND AFTER THE COMPLETION OF
         RESPECTIVE WORKS                                                                          5.13 UNLESS OTHERWISE SHOWN ON DRAWINGS
                                                                                                                                                                                                                                                                                                                                                         13.0 FLOORING FINISHES
         2.0 EARTHWORKS                                                                                 EXTERNAL FACE WORK: 230x110x76mm
                                                                                                        WINDOW SILLS: 2c FACE BRICK SPLAYED SILLS                                                                                                                                                                                               13.1     CARPET FLOOR COVERINGS TO NOMINATED AREAS COMPLETE WITH SELECTED UNDERLAY SMOOTH
 2.1     UNLESS OTHERWISE STATED, REMOVE TOPSOIL TO A MINIMUM DEPTH OF 200mm INCLUDING ALL
                                                                                                        WINDOW HEADS: SOLID FACEBRICK COURSE                                                                                                                                                                                                             EDGE, DIMINISHING STRIPS ETC, TO COMPLETE THE WORKS: REFER TO DRAWINGS AND FINISHES
         ROOTS, AND OTHER MATTER, AND REQUIRED BY THE SOIL CONDITION AND/OR BUILDER. PROVIDE            6.0 LINTELS                                                                                                                                                                                                                                      SCHEDULE
         SUITABLE CLEAN FILL AND COMPACT IN LAYERS NOT GREATER THAN 300mm TO REDUCE LEVELS AS                                                                                                                                                                                                                                                   13.2     PROVIDE TILED FLOOR FINISHES TO NOMINATED AREAS COMPLETE WITH ALL MATERIALS, ANGLE TRIMS
                                                                                                        MAX SPAN                       LINTELS SIZE              BEARING
         SHOWN.                                                                                                                                                                                                                                                                                                                                          ETC. TO COMPLETE THE WORKS: REFER TO DRAWINGS AND FINISHES SCHEDULE
                                                                                                        (mm)                         (VERT x HORIZ x THICK)        EACH END (mm)
 2.2     DO NOT EXCAVATE SERVICES TRENCHES WITHIN AN ANGLE OF 45 DEGREES DOWN FROM THE                                                                                                                                                                                                                                                          13.3     PROVIDE TIMBER FLOOR FINISHES TO NOMINATED AREAS COMPLETE WITH ALL MATERIALS, DIMINISHING
         BOTTOM EDGE OF THE FOOTING.                                                                      900                               75x10                   150
                                                                                                        1200                               75x75x8                  150                                                                                                                                                                                  BOARDS ETC TO COMPLETE THE WORKS: FLOOR BOARDS TO BE SANDED AND POLISHED TO HIGH
 2.3     ALL RETAINING WALLS TO BE TREATED WITH "BITKOTE" WATERPROOFING AGENT                           1500                               90x90x8                   150                                                                                                                                                                                 STANDARD WITH PREMIUM QUALITY SEALER (2 COATS). REFER TO DRAWINGS AND FINISHES SCHEDULE.
         3.0 CONCRETE                                                                                   1800                              100x75x8                  230                                                                                                                                                                                  14.0 SIGNAGE
 3.1     ALL CONCRETE REINFORCEMENT AND FORMWORK SHALL BE TO STRUCTURAL ENGINEERS DETAILS,              2100                              125x75x8                  230
                                                                                                                                                                                                                                                                                                                                                14.1     WHERE NECESSARY SUPPLY & FIX SELECTED UNIT AND HOUSE NUMBERS TO EACH UNIT AND TO
         RELEVANT BUILDING CODES AND STANDARDS                                                          2400                             125x75x10                  230
                                                                                                                                                                                                                                                                                                                                                         LETTERBOXES AS SCHEDULED.
                                                                                                        2500                             100x100x8                   230
 3.2     THE FOOTING AND SLAB CONSTRUCTION IS TO COMPLY WITH AS 2870                                    3000                             150x90x10                   230                                                                                                                                                                        14.2     "SUPERDRAFT" RESERVES THE RIGHT TO ERECT A BUILDERS SIGN ON THE PROPERTY FACING THE STREET
 3.3                                                                                                                                                                                                                                                                                                                                                     FRONTAGE IN COMPLIANCE WITH AUTHORITY REQUIREMENTS.
         PROVIDE A PROPRIETARY VAPOUR BARRIER WHICH CONSISTS OF HIGH IMPACT RESISTANT POLYTHENE         7.0 CARPENTRY WORK
         FILM MIN 0.2mm THICK WHICH HAS BEEN PIGMENTED AND BRANDED BY THE MANUFACTURER.                                                                                                                                                                                                                                                                  15.0 PAVING
                                                                                                   7.1  ROOF AND CEILING FRAMING SHOULD COMPLY WITH AS 1684 LIGHT TIMBER FRAMING CODE. DRAW
         4.0 TERMITE PROTECTION:                                                                                                                                                                                                                                                                                                                15.1     GENERALLY: WHEN PAVING IS INCLUDED IN THE BUILDING CONTRACT THE FOLLOWING SHALL APPLY AS
                                                                                                        STRAP FIRMLY OVER WALL PLATES AND SECURELY FIX TO TOP OF PLATE BY 2x30mm GALV.
                                                                                                                                                                                                                                                                                                                                                         A MINIMUM STANDARD
 4.1     PROVIDE ANTI-TERMITE TREATMENT UNDER THE BUILDING AREAS IN ACCORDANCE WITH AS 2057, AS         CLOUTS/STRAP.
                                                                                                   7.2 REFER TO AS 1684 FOR ROOF FRAMING SIZES UNLESS SPECIFIED ON DRAWINGS.
         3660.1 AND APPENDIX D, FOR RETICULATED SYSTEMS.
 4.2                                                                                               7.3 SUPPLY AND FIX ALL BULKHEADS & FALSE CEILINGS AS SHOWN ON THE DRAWINGS.                                                                                                                                                                           ·     SUPPLY AND LAY ALL PAVING TO EXTERNAL AREAS AS SHOWN ON WORKING DRAWINGS.
         BUILDER SHALL PROVIDE "BIFLEX" OR SIMILAR APPROVED ANTI-TERMITE TREATMENT IN ACCORDANCE
         WITH RELEVANT AUSTRALIAN STANDARD CODES                                                        8.0 ROOFING                                                                                                                                                                                                                                      ·     CUT, FILL & COMPACT SAND TO REQUIRED LEVELS. SCREED TO UNIFORM THINNESS AND LEVELS
         5.0 BRICKWORK                                                                             8.1                                                                                                                                                                                                                                                   ·     PROVIDE BRICK EDGE RETAINING FOOTING EMBEDDED IN MORTAR BENEATH THE PAVING BRICK
                                                                                                        SELECTED ROOFING MATERIAL SHALL BE INSTALLED AND FIXED IN ACCORDANCE WITH
                                                                                                        MANUFACTURERS SPECIFICATION AND RELEVANT BUILDING CODES                                                                                                                                                                                          ·     TO DRIVEWAY AREAS, PROVIDE NOMINAL 300x150mm CONCRETE FOOTING ALONG PERIMETER OF
 5.1     BRICK WORK SHALL COMPLY WITH :
                                                                                                                                                                                                                                                                                                                                                               DRIVEWAY AND BED EDGE BRICK IN MORTAR.
                                               AS 3700 MASONRY CODE                                8.2 GUTTER, FASCIA, DOWNPIPES, FLASHING SHALL BE IN LONGEST POSSIBLE LENGTHS
                                               AS A123 MASONRY CODE                                8.3 ALLOW FOR ALL JOINTS AND JOINING MATERIALS, COLLARS, STRAPS & FASTENINGS NECESSARY TO                                                                                                                                                    15.2     PROVIDE 100mm COMPACTED LIMESTONE BASE TO DRIVEWAY TOPPED WITH 50mm CLEAN SAND
                                                                                                        COMPLETE WORK.                                                                                                                                                                                                                                   AND GRADE TO FALLS.
 5.2     BRICK GAUGE 7 STANDARD COURSES = 600mm. MORTAR FOR MASONRY CONSTRUCTION                   8.4 ALLOW FOR ALL ROOF PENETRATIONS, ROOF COWLS, FLASHING, FLUMES THROUGH ROOF                                                                                                                                                               15.3     UNLESS NOTED PAVING PATTERN IS TO CLIENTS DETAIL
 5.3                                                                                                                                                                                                                                                                                                                                            15.4     BRICK PAVERS SHALL BE:
         TIES SHALL BE 3.5mm DIAMETER GALVANIZED WIRE KINKED FOR AND BUILT IN EVERY 5TH COURSE AT  8.5 FIX GUTTERS & FLASHING TO PERMIT THERMAL MOVEMENT IN THEIR FULL LENGTH                                                                                                                                                                            TRAFFICABLE AREAS: MIN. 65mm SOLID CLAY OR CONCRETE
         APPROXIMATELY 900mm CENTRES, WITH ADDITIONAL TIES AT THE RATE OF 1 TIE/300mm HEIGHT OF    8.6 SEAL BETWEEN OVERLAPPING FLASHING; FLASHING TURNED DOWN OVER BASE OR APRON FLASHING;                                                                                                                                                              PEDESTRIAN AREAS: MIN. 43mm SOLID CLAY OR CONCRETE
         OPENINGS AND VERTICAL CONTROL JOINTS AND WITHIN 150mm OF OPENINGS. BUILD TIES INTO EACH        FLASHING OVER METAL ROOF; FLASHING OVER SECRET GUTTERS; AROUND ROOF PENETRATIONS ETC.
         LEAF AT LEAST 50mm.                                                                                                                                                                                                                                                                                                                             16.0 ENERGY EFFICIENCY
                                                                                                        9.0 WINDOWS/GLAZING
 5.4     VERTICAL CONTROL JOINTS SHALL BE 12mm WIDE FILLED AT COMPLETION WITH A CONTINUOUS FILLER                                                                                                                                                                                                                                               16.1     INSULATION MUST FORM A CONTINUOUS BARRIER WITH CEILINGS, WALLS AND FLOORS BY ABUTTING
         STRIP.                                                                                    9.1  UNLESS OTHERWISE STATED ON THE DRAWINGS WINDOW FRAMES SHALL BE ALUMINIUM RESIDENTIAL                                                                                                                                                             OR OVERLAPPING ADJOINING INSULATION
 5.5     CAVITIES TO BE KEPT CLEAR OF MORTAR. PROVIDE CAVITY BOARDS. TEMPORARILY OMIT BRICKS TO         OR COMMERCIAL IN SECTION WITH POWDERCOAT FINISH AS SELECTED BY OWNER.                                                                                                                                                                   16.2     INSULATION MUST NOT ADVERSELY AFFECT DOMESTIC SERVICES OR FITTINGS
         PERMIT RAKING OUT OF CAVITY BOTTOMS.                                                      9.2 ALLOW FOR FLYSCREENS TO BE FITTED TO ALL WINDOWS.                                                                                                                                                                                        16.3     REFLECTIVE INSULATION IS TO BE PROVIDED WITH A MINIMUM 25mm AIRSPACE AND IS FITTED CLOSE
 5.6                                                                                               9.3 ANGLED WINDOW UNITS SHALL BE FACTORY MADE AND FIXED AND DELIVERED ON SITE AS A
         FORM WEEP HOLES EVERY FOURTH PERPEND ABOVE FLASHING AND CAVITY FILL KEEP CLEAR OF                                                                                                                                                                                                                                                               TO OPENINGS SUCH AS WINDOWS/DOORS ETC. AND IS PROVIDED WITH ADEQUATE SUPPORT.
         MORTAR. DO NOT LOCATE WEEPHOLES CLOSER THAN 500mm TO JOINTS IN DAMP PROOF COURSES              COMPLETE UNIT.
         OR FLASHING.                                                                              9.4 WHERE RELEVANT WINDOWS ARE TO COMPLY WITH THE SPECIFICATIONS PROVIDED BY THE THERMAL                                                                                                                                                     16.4     BULK INSULATION MUST MAINTAIN ITS POSITION, THICKNESS.
                                                                                                        PERFORMANCE ASSESSOR.                                                                                                                                                                                                                            ENSURE THAT CEILING INSULATION OVERLAPS UN-INSULATED WALLS
 5.7     PROVIDE DAMP PROOF COURSES (DPC) IN THE BOTTOM 3 COURSES OF BRICK WORK AND SLAB           9.5 CLEAR GLASS GENERALLY: OBSCURE GLASS TO BATHROOMS, REFER TO DRAWINGS.                                                                                                                                                                    16.5     CONSTRUCTION JOINTS, SUCH AS BETWEEN WALL AND FLOOR, ARE TO BE TIGHT FITTING OR SEALED
         AND/OR FOOTINGS. DPC ADDITIVE SHALL BE CLEAR IN ALL FACEWORK.                             9.6 WHERE GLASS BLOCKS HAVE BEEN NOMINATED, THEY SHALL BE IN FRAMES AND INSTALLED TO                                                                                                                                                                  USING CAULKING OR JOINERY ITEMS SUCH AS SKIRTING OR CORNICES
 5.8     SETOUT BRICKWORK ACCURATELY, PLUMP, LEVEL AND PROPERLY BONDED. RISING WORK TO BE RAKED         MANUFACTURERS SPECIFICATIONS                                                                                                                                                                                                            16.6  EXHAUST FANS ARE TO BE FITTED WITH A SELF CLOSING DAMPER
         BACK, JAMBS, REVEALS, CORNERS, PERPENDS, ETC TO BE TRUE, PLUMB AND IN LINE WITH PERPENDS                                                                                         10.0 JOINERY                                                                                                                                          16.7  ROOF LIGHTS MUST BE SEALED WITH WEATHERPROOF SEALS
         TRUE LINE. SETOUT DOOR FRAMES NEAR PERPENDICULAR WALL WITH A MERGIN OF 12mm OR GREATER                                                                                                                                                                                                                                                 16.8  HEATED WATER PIPING MUST BE THERMALLY INSULATED AND PROTECTED AGAINST THE WEATHER AND
                                                                                                                                                                                 10.1     ALL JOINERY SHALL BE OF HIGHEST QUALITY MATERIALS TO BEST TRADE PRACTICES AND HIGH QUALITY
         THAN 50mm                                                                                                                                                                                                                                                                                                                                    SUN
                                                                                                                                                                                          FINISH.
                                                                                                                                                                                                                                                                                                                                                16.9 INTERNAL HEATED WATER PIPING TO HAVE AN R VALUE OF 0.2
                                                                                                                                                                                 10.2     EXTERNAL DOOR FRAMES SHALL BE: 110x40 DOUBLE REBATED FRAME WITH 130x40 WEATHERED                                                                      16.10 ENCLOSED SUB-FLOOR AND ROOF SPACE TO HAVE AN R VALUE OF 0.45
 5.9 PROVIDE 12mm PLASTERING MARGIN BETWEEN WINDOW FRAME AND INTERNAL BRICKWORK TO BE
                                                                                                                                                                                          THRESHOLD U.N.O.
      PLASTERED.
 5.10 WHERE NECESSARY REINFORCE BELOW AND OVER OPENINGS WITH GALVANISED WOVEN WIRE FABRIC                                                                                        10.3     SUPPLY AND BUILD IN TIMBER DOOR FRAMES TO EXTERNAL LOCATIONS AS SHOWN ON
      75mm WIDE IN CENTRE OF EACH LEAF OPENING EXTENDING ALUMINIUM OF 600mm BEYOND THE                                                                                                    ARCHITECTURAL DRAWINGS.
      OPENING.

                                                                                                                                                NOTE:                                                                                                                                                                                                                                                            Job No.
                                                                                                                                                                                                                  ARCHITECTURAL SPECIFICATION
                                                                                                                                                                                                                                                                                                                                                                                                                               AD21-002
                                                                    antoniajayne Design                                                         ALL DESIGN, CONSTRUCTION & MATERIALS TO BE IN ACCORDANCE WITH:
                                                                                                                                                •THE NATIONAL CONSTRUCTION CODE (NCC)
                                                                                                                                                •THE BUILDING CODE OF AUSTRALIA (BCA)
                                                                                                                                                                                                                                                                                                                                                                                                                 Issue         DEVELOPMENT APPROVAL - client amendments
                                                                                                                    0409 366 854                •THE QUEENSLAND DEVELOPMENT CODE (QDC)
                                                                                                                                                                                                                                                                                                                                                                                                                 Rev           06
                                                                                                                                                •BUILDING REGULATIONS & LOCAL GOVERNMENT PLANS & POLICIES
                                                                                                     North Booval QLD 4304
                                                                                    [email protected]
                                                                                                                                                •CURRENT ISSUES OF AUSTRALIAN STANDARDS
                                                                                                                                                •CURRENT MANUFACTUERER'S SPECIFICATIONS & INSTALLATION DETAILS    AD21-001_13RECTORYSTREET                                                     Kate Mayne & Kent Mayne                                                                                           Date          18/2/22
                                                                                                                                                FOR MATERIALS USED

                                                                                                       www.ajdesigndp.com                       ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE NOTED
                                                                                                                                                                                                                                                                                                                                                                                                                 Page No.      A.00
                                                                                                                  QBCC: 15133061                                                                                  FOR APPROVAL                                                                  13 Rectory Street Pomona QLD 4568
                                                                                                                                                                                                                                                                                                                                                                                                                 Scale @ A3
Copyright: This drawings remains the property of antoniajayne Design and is provided for use as noted the recipient(s) of this document is/
are prohibited from disclosing such information, ideas and concepts to any person without prior written consent of the copyright holder.                                                                         /Users/antoniajayne/Library/Mobile Documents/com~apple~CloudDocs/OBRIEN & DOYLE GROUP_ICLOUD/ANTONIAJAYNEDESIGN_ICLOUD/JOBS/AD21-001_13RECTORYSTREET/ARCHICAD/AD21-001_13RECTORYSTREET_V2.pln   Designed By   ANTONIA O'BRIEN
Log in to download the original file

Appendix A - Amended Plans.pdf · 5.1 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.