                                                           Services Advice Notice

              South-East Queensland Water (Distribution and Retail Restructuring) Act 2009


                                                             Notice Details

             Development Application No:                              2023022849

             Street Address:                                          62 Lake Macdonald Drive, COOROY, QLD 4563.

             Property Description:                                    Lot 105 SP118458

             Proposal:                                                100 Dwellings development on 1 into 3 subdivision

             Local Government Area:                                   Noosa Shire Council

             Date of Issue:                                           15/05/2023

             Assessment Officer:                                      Don Jayasinghe

             Responsible officer:                                     Bruk Gebreselassie

             This notice is provided in accordance with Section 99BRAC of the South-East Queensland
             Water (Distribution and Retail Restructuring) Act 2009.

             Please note that the Service Advice Notice is advisory only and does not represent
             approval of the connection or any associated works. The Service Advice Notice is valid for
             6 months from the date of this notice.

             Application must be made to Unitywater for approval of the connection or associated works.

             • Proposed development lot is located within Unitywater’s current water supply connections
               area and outside future sewer connections area.

             • Demand generated by this development exceeds the Unitywater’s planning assumptions
               for the development lot/s. However, Unitywater may be amenable to approving water
               supply and sewerage connections for the development if the demand of the proposed
               development will not have a detrimental effect on any existing or future customers within
               Unitywater’s water supply and sewerage connection and future connection areas.

             • This will need to be demonstrated by the applicant via a network analysis by a competent
               and suitably qualified consultant who can carry out such analysis. As a part of this analysis,
               a viable sewer and water connection strategy will need to be produced.

             • The water supply network analysis shall cover the DMA-COORO and the sewerage
               analysis shall cover gravity mains from the connection point up to and including SPS-
               CRY020.
                                                                                                                                       Page 1 of 4
Unitywater is a statutory authority that provides water and sewerage services for the                             Unitywater has certification to
                                                                                                                  OH&S ISO 4801:2001 Reg No 4260
Moreton Bay, Sunshine Coast and Noosa Council areas.                                                              Environmental ISO 14001:2004 Reg No 4259
                                                                                                                  Quality Systems ISO 9001:2008 Reg No 4258

                                                     Revision No: 2                Effective Date: 19/02/2015              Next Review Date:19/02/2018
Full text of the other 3 pages

Page 2

             • A free copy of Unitywater’s network models for this location is available to the developer
               on request subject to conditions. Please contact Senior Engineer Network Modelling,
               Mathy Jegan at [email protected]

       Reconfiguration of a in to 3 subdivision
          • The developer will be required to provide reticulated water supply to all 3 lots within the
             subdivision and connection(s) to Unitywater’s existing water supply network. Water mains
             shall be provided along the full frontage/s of the development site for each stage to ensure
             future mains extension can occur without disturbing developed footpath and the need for
             council approval for works in roads.

             • The developer will be required to provide reticulated sewerage to all 3 lots within the
               development, including a property connection to each lot and connection(s) to Unitywater’s
               existing sewerage network.

       Community housing within the subdivision
          • Community housing within the subdivision will be required to provide;
             o Metered water service to all units within the subdivided lot with a primary meter and
                 sub- meters in accordance with Queensland Plumbing and Wastewater Code 2010
                 – Part 4 and Unitywater’s sub metering policy.
             o A single sewer connection to the community title lot from Unitywater’s existing
                 sewerage network and internal sewers with property connection to all units within
                 the development in accordance with SEQ design standards.
          • The connection application shall accompany plans indicating,
             o The location of any metered water connection/s and sewerage property connections
                 including offsets from boundaries and invert levels for new sewerage connections.
             o Any proposed large diameter water connections (greater than Ø25mm), above
                 ground master meter assembly (This shall be located within the development
                 property boundary) and proposed sub-meter installations.

       Fire Fighting Requirements (Commercial or Industrial and Units)
           • Direct connection of pressure boosting pumps to Unitywater network is not favoured by
              Unitywater. Sometimes the requests may be considered depending on the capacity,
              condition and sufficient connectivity of the reticulation system in the area. If there is any
              such proposal, details of the pumps (pump curves and design calculations) needs to
              be submitted to Unitywater’s Development Services for approval prior to installation.
              This request shall include a certification by the hydraulic consultant that the maximum
              flow rate of the installed pumps will be no greater than Unitywater’s standards of service,
              relevant for the site.

             • Unitywater’s level of service towards firefighting capacity is guided by SEQ Design &
               Construction Guidelines whereas the internal fire suppression systems of buildings shall
               comply with the requirements of AS 2419.Therefore it is the responsibility of the developer
               to design and install the necessary infrastructure such as pumps, break tanks etc, so that
               the internal fire suppression system complies with the relevant standards.

                                                                                                                                     Page 2 of 4
Unitywater is a statutory authority that provides water and sewerage services for the                           Unitywater has certification to
                                                                                                                OH&S ISO 4801:2001 Reg No 4260
Moreton Bay, Sunshine Coast and Noosa Council areas.                                                            Environmental ISO 14001:2004 Reg No 4259
                                                                                                                Quality Systems ISO 9001:2008 Reg No 4258

                                                     Revision No: 2                Effective Date: 19/02/2015           Next Review Date: 19/02/2018

Page 3

             • The Usage of street hydrants as standalone firefighting facility to a building will be entirely
               at the risk of the developer. Unitywater will not guarantee that the street hydrants will comply
               with the requirements of AS 2419 or of QFES. This applies to dry hydrant systems too.

             • It is strongly recommended that the developer submits an application for flow & pressure
               information about the water mains that the development is getting connected to. This
               information will provide details of the expected flow & pressure of Unitywater’s street
               watermain in the vicinity of the development from a hydraulic model prediction. The
               application       can    be      downloaded      from     Unitywater’s      web      site
               https://www.unitywater.com/faults-and-outages/water-supply-problems/water-pressure
               (Form 8578)

             • Unitywater, at its discretion, may change the operational regime of its water mains.
               However, it won’t be changed below Unitywater’s minimum level of service towards street
               hydrants. These values are shown in Table 1 below. For more details, please refer to the
               latest version of SEQ Design & Construction Code.

                                                                                              Flow available            Residual
                                                                                            from Unitywater             Head in Water
                                            Type of Use                                            Main                 main (meters)
                                                                                             (Litres/second)

                 Residential dwellings of less than 3 storey                                            15                        12

                 Commercial that is ancillary to residential use                                        15                        12

                 Multi Storey residential greater than 3 storeys                                        30                        12

                 Commercial and or Industrial                                                           30                        12


             • Location of existing Unitywater infrastructure can be viewed at Unitywater’s website.
               Precise details of infrastructure are available via Detailed Infrastructure Plan (DIP) on
               application. Further information on this process is available at Unitywater website
               http://www.unitywater.com/reference library.

             • This proposal would require the applicant to apply to Unitywater for a ‘Staged or Other
               Connection Application’ which includes application/s for ‘network works’. For further
               information on this process refer to Unitywater’s website at http://unitywater.com/Building-
               and-developing.

             • For current information in relation to all Unitywater’s fees applicable to connection
               applications and development related works please refer to Unitywater website at
               https://www.unitywater.com/Building-and-developing/pricing-fees-and-charges.

             • Should an approval for connection be provided by Unitywater, the developer will need to
               apply to Unitywater for a Private Works Quote in relation to the cost for new metered water
               supply service connections and live connections to existing water/sewer infrastructure by
                                                                                                                                     Page 3 of 4
Unitywater is a statutory authority that provides water and sewerage services for the                           Unitywater has certification to
                                                                                                                OH&S ISO 4801:2001 Reg No 4260
Moreton Bay, Sunshine Coast and Noosa Council areas.                                                            Environmental ISO 14001:2004 Reg No 4259
                                                                                                                Quality Systems ISO 9001:2008 Reg No 4258

                                                     Revision No: 2                Effective Date: 19/02/2015           Next Review Date: 19/02/2018

Page 4

                 Unitywater. A copy of the connection approval and associated approved plans detailing the
                 new connections must accompany the private works quotation application. Please refer
                 Unitywater’s website at http://www.unitywater.com/private-works. for further details.

             • It is the Applicant’s responsibility to ensure that it has all necessary consents and approvals
               to carry out any connection related works in a publicly controlled place (e.g. Council, DTMR)
               or property that is not owned or controlled by the Applicant prior to starting such works.

             • All water supply and sewerage works must be designed and constructed in accordance with
               the South-East Queensland Water Supply and Sewerage Design and Construction Code,
               Unitywater’s Connections Administration Manual and any other matter Unitywater considers
               to be relevant to the connection or supply of its water services or wastewater services.
             • Easements will be required in accordance with the South-East Queensland Water Supply
               and Sewerage Design and Construction Code over water/sewerage mains located in private
               property boundaries.

             • Payment of Levied Charges will be required in accordance with Unitywater’s Infrastructure
               Charges for water supply and sewerage.

                 If you have any queries about the advice, please contact                                                Unitywater            at
                 [email protected] or by phone on 1300 086 489.

                 Yours sincerely,
                 Development Services
                 Unitywater




                                                                                                                                     Page 4 of 4
Unitywater is a statutory authority that provides water and sewerage services for the                           Unitywater has certification to
                                                                                                                OH&S ISO 4801:2001 Reg No 4260
Moreton Bay, Sunshine Coast and Noosa Council areas.                                                            Environmental ISO 14001:2004 Reg No 4259
                                                                                                                Quality Systems ISO 9001:2008 Reg No 4258

                                                     Revision No: 2                Effective Date: 19/02/2015           Next Review Date: 19/02/2018

Used in these records

About this file

File size
661 KB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Appendix F Services Advice Notice.pdf · 661 KB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.