PLANNING & ORGANISATION COMMITTEE MEETING AGENDA 26 MAY 2015
iii. plan of premises showing location of tanks, essential site services
including fire services and isolation points of fuel and power, and all
drains.
iv. type of underground tanks and their identification number or code
v. type of fuels and capacities.
Fuel storage
52. The underground petroleum storage system (UPSS) must be designed by a suitably
qualified and experienced person, and a copy of the design certification must be
provided to Council prior to issue of development permit for operational works.
53. The underground storage tanks must be designed and constructed of a standard not
less than that required by AS1692 “Tanks for the storage of Flammable and
Combustible Liquids”. A certificate of compliance shall be provided by the
manufacturer of the tanks prior to use of the tanks.
54. The underground tanks must be installed in accordance with AS 1940 and AIP Code
of Practice CP4 Code of Practice for Design, Installation and Operation of
Underground Petroleum Storage Systems. A Certificate of Compliance from a
suitably qualified and experienced person must be provided to council prior to
operation of the service station.
55. All electrical wiring and equipment located in a hazardous zone including dispensers,
must comply with relevant Australian Standards. A Certificate of Compliance from an
approved electrical contractor must be provided to Council prior to operation of the
service station.
56. The underground tanks together with their anchorage and piping must be protected
from corrosion by one or more of the following methods:
a. approved long life protective coatings or wrappings
b. corrosion resistant materials of construction e.g. FRP.
Consideration must be given to the corrosion history of the area in the selection of
type of protection to be used.
57. Underground tanks must be separated from each other by not less than 150mm.
58. Secondary containment for product piping must be double-walled piping with an
interstitial space. The manufacturer is to provide a written specification and
performance warranty certifying compliance with AIP Code of Practice.
59. Monitoring of the interstitial space of the double walled tanks or product piping must
be capable of detecting a release through either wall of the tank or product piping. A
6-monthly inspection program conducted by a suitably qualified and experienced
person is required to monitor the following:
a. the system is active
b. leak detection measurements (e.g. liquid levels or pressure levels) are within
manufacturer’s tolerances
c. leak detection measurements are recorded
d. any loses outside the manufacturer’s leak detection tolerances are to be
reported to council in writing and the tank owner immediately.
60. All pipe work and equipment must be located so that it is protected against impact
damage from vehicles or mobile plant, and must not cause excessive stress where
connected to the tank.