Your Mates Bowlsy Pty Ltd                                                                             Reference: #1859d1-B
Your Mates Bowls Pub                                                                                    Date: 6 March 2025
Noise Impact Assessment

2025 to determine the existing noise impacts. Noise measurements were taken using a Nor139
sound level meter at the locations illustrated in the figure below. Noise survey instrumentation
information is provided in Table 3.




                                                             A




                                          B                        C




   Measurement Location



                     Figure 5. Attended measurement locations of mechanical plant noise



Measured noise levels from the mechanical plant assessment are presented below.

                                    Table 8. Measured mechanical plant noise levels

 Meas.              Description /        Duration         Level, dBA
                                                                                             Comments
  No.                Location           (min:sec)   Leq      L90       Lmin
                    Location A –
                Directly below
                                                                               Plant noise clearly audible. Continuous
    1        rooftop mechanical           1:00      57       57        56
                                                                                            noise source.
              plant, 3m from the
                 noise source
                    Location B –
                                                                               Plant noise clearly audible. Continuous
    2           1m from Patton            1:00      68       68        68
                                                                                            noise source.
               refrigeration unit
             Location C – At the
                                                                              Noise from refrigeration plant and kitchen
             eastern boundary of
    3                                     1:00      58       58        58      exhaust fan audible. Continuous noise
             the site, adjacent to
                                                                                               source.
               11 Opal Street




Live It Acoustics                                                                                                  Page 13
Log in to download the original file

Appendix B - Acoustic Report.pdf · 4.0 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.