Civil Plans_19660_20260213_OPW_[A-B]

of 25

Original PDF page 3, section 1. The text section number identifies this passage in the reader.

                                                                         CONCRETE:                                                                                                                                                CONCRETE BLOCK MASONRY:

                                                                         C1.     CONCRETE WORKS SHALL BE IN ACCORDANCE WITH: AS3600 CONCRETE STRUCTURES                                                                           CB1.    CONCRETE MASONRY SHALL BE IN ACCORDANCE WITH:
                                                                                                                                                                                                                                          AS3700 MASONRY STRUCTURES AND AS 4455 - CONCRETE BUILDING BLOCKS, WITH THE FOLLOWING MODIFICATIONS.
                                                                         C2.     CONCRETE STRENGTH, REINFORCEMENT COVER, SLUMP, SURFACE FINISH AND MATERIALS SHALL BE AS FOLLOWS:
                                                                                                                                                                                                                                  CB2.    MATERIALS SHALL BE AS FOLLOWS:
                                                                                                                                                                                                                                          - BLOCK THICKNESS: REFER DRAWINGS.
                                                                           MIX REQUIREMENTS
                                                                                                                                                                                                                                          - BLOCK TYPE: SHALL BE 20.48 SERIES 'H' (SINGLE WEB) BLOCKS FOR LONG LIFE.
                                                                           CAST INSITU CONCRETE SHALL BE BATCHED USING BLENDED CEMENT: 25% FLYASH & 75% PORTLAND CEMENT.
                                                                           ANY ALTERNATIVE PROPORTIONS SHALL BE SUBMITTED FOR APPROVAL.                                                                                                     DONT USE FULL BLOCKS AS THESE MAY BE REJECTED BY THE SUPERINTENDENT.
                                                                                                                                                                                                                                          - BLOCK STRENGTH: STRENGTH CLASSIFICATION 12.
                                                                                                                                 f'c (MPa) /         REO COVER                                      FINISH TO                             - LAYING PATTERN: SHALL BE STRETCHER BOND PATTERN, UNO.
                                                                                  ITEM                  EXPOSURE                                                          TARGET SLUMP
                                                                                                                              AGGREGATE SIZE          ALL FACES                                   TOP SURFACE                             - CLEANOUT BLOCKS SHALL BE USED AS THE BASE OF WALLS
                                                                                                                                                                                                                                          - VERTICAL MOVEMENT JOINTS SHALL BE PROVIDED AT 6.0m CENTRES, UNO.
                                                                                FOOTINGS                      B1                S40 / 20 mm            60 mm                   100 mm               BROOMED                               - BLOCKFILL: S32/10, SLUMP 150mm TO 200mm.
                                                                                BLOCKFILL                     B1                S32 / 10 mm            55 mm                   150 mm                  N/A                                  BLOCKFILL SHALL BE BATCHED USING BLENDED CEMENT: 25% FLYASH AND 75% PORTLAND CEMENT.
                                                                                                                                                                                                                                            ANY ALTERNATIVE PROPORTIONS SHALL BE SUBMITTED FOR APPROVAL.
                                                                                                                                                                                                                                            ALL BLOCKWORK CORES TO BE FILLED, UNO, FOR LONG LIFE AND WATER RESISTANCE.
                                                                                                                                                                                                                                          - FILL BLOCKWORK CORES SLOWLY (MAX 6 COURSE HEIGHT PLACED AT ONE TIME), FOR SAFETY REASONS.
                                                                         C3.     CONCRETE TEMPERATURE AT PLACEMENT                                                                                                                        - MORTAR PROPORTIONS = 1 CEMENT : 0.25 HYDRATED LIME : 3 SAND (OR EQUIV CEMENT - SAND MORTAR WITH
                                                                                 - NO CONCRETE SHALL BE PLACED IF THE TEMPERATURE OF THE CONCRETE IS LESS THAN 10°C OR EXCEEDS 35°C.                                                        PLASTICISER)
                                                                                 - CONCRETE SHALL BE PLACED AND COMPACTED WITHIN 1 HOUR OF CHARGING THE MIXER FOR CONCRETE                                                                - MORTAR 28 DAY COMPRESSIVE STRENGTH: 11MPa MINIMUM.
                                                                                   TEMPERATURES UP TO 32°C & WITHIN 45 MINUTES OF CHARGING THE MIXER FOR CONCRETE TEMPERATURES UP                                                         - REINFORCEMENT: SHALL BE 'N' GRADE D500N HOT ROLLED HIGH YIELD DEFORMED BARS TO AS 4671 UNO.
                                                                                   TO 35°C.                                                                                                                                               - REINFORCEMENT COVER: 50mm MINIMUM FROM OUTSIDE OF BLOCK, UNO.

                                                                         C4.     ALL CONCRETE SHALL BE VIBRATED UNO.                                                                                                              CB3.    CONTRACTOR TO ENSURE THE FOLLOWING:
                                                                                                                                                                                                                                          - TOP OF FOOTING SHALL BE SCABBLED.
                                                                         C5.     PROVIDE HOLES OR CHASES ONLY WHERE SHOWN ON STRUCTURAL DRAWINGS. RPEQ ENGINEER TO REVIEW AND                                                             - JOINT MORTAR SHALL BE TRIMMED FLUSH WITH THE INSIDE FACE OF THE CAVITY.
                                                                                 CERTIFY ANY ADDITIONAL HOLES OR CHASES BEFORE CONTRACTOR CARRIES OUT WORKS.                                                                              - CLEAN OUTS SHALL BE FORMED WITH TIMBER FORMS. AVOID BESSER BISCUITS, FOR SAFETY REASONS.
                                                                                                                                                                                                                                          - REINFORCING COVER SHALL BE MAINTAINED BY THE USE OF PLASTIC `BLOCKAID' REINFORCEMENT LOCATION
                                                                         C6.     PROVIDE 20mm FILLETS OR CHAMFERS FOR EXPOSED CONCRETE EDGES HAVING CONTAINED ANGLE OF LESS THAN                                                            BRACKETS OR EQUAL
                                                                                 120° UNO
                                                                                                                                                                                                                                         WALL - 20.48 BLOCKS
                                                                         C7.     SUPPORT REINFORCEMENT ON PLASTIC CHAIRS AND SPACERS TO GIVE CORRECT CONCRETE COVER.                                                                      - N16 AT 400 VERTICAL - 600 LAPS
                                                                                 WHERE PLASTIC CHAIRS ARE TO BE TEMPORARILY SUPPORTED BY SOIL:                                                                                            - N12 AT 400 HORIZONTAL - 600 LAPS (INCLUDING ' L ' BARS AT CORNERS UNLESS NOTED OTHERWISE)
                                                                                 - FOR MESH REINFORCEMENT, PROVIDE 'PIE PLATE' SUPPORT UNDER EACH CHAIR OR POUR 50mm MINIMUM
                                                                                    BLINDING CONCRETE
                                                                                                                                                                                                                                  RETAINING WALLS
                                                                         C8.     POUR JOINTS
                                                                                 - SCABBLE THE FACE OF POUR JOINTS AND CLEAN OFF DUST AND CONTAMINANTS BEFORE NEW POUR                                                            RW1. RETAINING WALLS SHALL BE SETOUT AS FOLLOWS:
                                                                                 - COAT FACE WITH BONDING AGENT                                                                                                                        - FACE OF WALL TO BE LOCATED AS PER PROJECT DRAWINGS. IN ADDITION FACE OF WALL SHALL BE MINIMUM OF
                                                                                                                                                                                                                                          100mm FROM PROPERTY BOUNDARY. FOR ANY CONFLICT REFER TO SUPERINTENDENT.
                                                                         C10.    CONCRETE SHALL BE CURED IN ACCORDANCE WITH THE FOLLOWING REQUIREMENTS AND THE STANDARD (REFER
                                                                                 NOTE C1):                                                                                                                                        RW2. NO ADDITIONAL LOADS SHOULD BE APPLIED TO THE RETAINING WALLS:
                                                                                                                                                                                                                                       - THIS WALL IS NOT DESIGNED TO SUPPORT HORIZONTAL OR VERTICAL PRESSURES IMPOSED BY BUILDINGS OR
                                                                                 PERFORMANCE CRITERIA:                                                                                                                                    LARGE VEHICLES
                                                                                 - CRACKS IN CONCRETE (90 DAYS AFTER PLACEMENT) SHOULD NOT EXCEED 0.3mm AT THE SURFACE.                                                                - LARGE VEHICLES SHALL BE KEPT 4 METRES BACK FROM THE WALL.
                                                                                    CONCRETE WITH CRACKS EXCEEDING LIMIT SHALL BE REPAIRED.                                                                                            - BUILDINGS SHALL BE DESIGNED BY AN RPEQ CERTIFIED STRUCTURAL ENGINEER, WITH SUITABLE FOOTINGS TO
                                                                                    OBTAIN SUPERINTENDENT APPROVAL FOR REPAIR METHODS PREFERRED CURING METHOD.                                                                            ENSURE NO VERTICAL OR HORIZONTAL LOAD IS IMPOSED AGAINST THIS WALL.
                                                                                 - WHILST PLACING, SPRAY CONCRETE WITH ALIPHATIC ALCOHOL AFTER FIRST SCREED & AGAIN DURING FINISHING                                                   - ADJACENT BUILDINGS ON LOW SIDE OF WALL SHALL BE POSITIONED WITH A MINIMUM CLEARANCE OF 100mm FROM
                                                                                    WORKS                                                                                                                                                 THE FACE OF THE WALL. THIS IS IMPORTANT TO AVOID LOAD TRANSFER BETWEEN THE BUILDING AND THE
                                                                                 - COMMENCE CURING TOP SURFACE OF SLABS ONCE FINISHING OPERATIONS COMPLETE. COMMENCE CURING ALL                                                           RETAINING WALL.
                                                                                    OTHER
                                                                                    SURFACES WITHIN 1 HOUR OF STRIPPING FORMWORK.                                                                                                 RW3. THE FOUNDATION MATERIAL ADJACENT THE BASE OF THE FOOTINGS MUST NOT BE EXCAVATED IN THE FUTURE, AND
                                                                                 - CURE FOR 7 DAYS MINIMUM.                                                                                                                            ANY EROSION MUST BE REPAIRED/REINSTATED IMMEDIATELY.

                                                                                                                                                                                                                                  RW4. THE FOOTINGS FOR THE RETAINING WALLS SHALL BE FOUNDED ON NATURAL SUBGRADE - COMPACTED TO MIN. 95%
                                                                                                                                                                                                                                       RDD TO ACHIEVE A MINIMUM ALLOWABLE BEARING CAPACITY OF 150kPA. THE FOUNDATION MATERIAL IS TO BE
                                                                                                                                                                                                                                       CHECKED BY A REGISTERED GEOTECHNICAL ENGINEER OR APPROVED EQUIVALENT (THE ARCHITECT OR ENGINEER)
                                                                         REINFORCEMENT:                                                                                                                                                BEFORE THE POURING OF THE FOUNDATIONS IS COMMENCED.

                                                                         R1.     REINFORCEMENT SHALL CONFORM WITH TMR MRTS71 'REINFORCEMENT STEEL'                                                                                RW5. PROVIDE ADEQUATE PROTECTION TO ALL ADJACENT IN-GROUND SERVICES.

                                                                         R2.     ALL REINFORCEMENT SHALL BE ACRS (AUSTRALIAN CERTIFICATION AUTHORITY FOR REINFORCING STEEL) CERTIFIED.                                            RW6. THE BACK OF RETAINING WALLS SHALL BE SEALED WITH BITUMEN BASED TANKING TO CONTROL STAINING OF THE
                                                                                                                                                                                                                                       CONCRETE WALL FACE. TANKING TO BE DAVCO “BITKOTE NO. 3” OR EQUAL.
                                                                         R3.     REINFORCEMENT SHALL BE 'N' GRADE D500N HOT ROLLED HIGH YIELD BARS TO AS 4671. U.N.O. WHERE 'R' BARS ARE
                                                                                 SPECIFIED, THESE SHALL BE ROUND BARS GRADE R250N                                                                                                 RW7. THE FINISHED SURFACE SLOPE ABOVE AND BELOW RETAINING WALLS MUST NOT EXCEED THE SLOPES & LEVELS
                                                                                                                                                                                                                                       SHOWN ON THE DRAWINGS. NO ADDITIONAL BACKFILL CAN BE ADDED ABOVE THE WALL.
                                                                         R4.     BAR SHAPES SHALL BE PER TMR STANDARD DRAWING 1043, U.N.O. HOOKS AND COGS SHALL BE DETAILED PER TMR
                                                                                 STANDARD DRAWING 1044.                                                                                                                           RW8. DO NOT USE LARGE COMPACTION EQUIPMENT CLOSE TO THE BACK OF RETAINING WALLS. BACKFILL BEHIND
                                                                                                                                                                                                                                       RETAINING WALLS SHALL BE COMPACTED IN 100mm LAYERS USING HANDHELD 'WACKER PACKER' EQUIPMENT OR
                                                                         R5.     DO NOT CUT REINFORCEMENT TO CLEAR PENETRATIONS, SLEEVES OR H.D BOLTS. DISPLACE REINFORCEMENT                                                          APPROVED EQUAL. PROTECT GEOTEXTILE FABRIC AND DRAINAGE AT ALL TIMES.
                                                                                 SLIGHTLY AS NECESSARY AND PROVIDE CORRECT COVER TO THE PENETRATIONS, SLEEVES OR H.D BOLTS.
                                                                                                                                                                                                                                  RW9. CONTRACTOR SHALL PROVIDE A SUITABLY DESIGNED BARRIER/FENCE TO THE TOP OF RETAINING WALLS EXCEEDING
                                                                         R6.     REINFORCEMENT LAP SPLICE LENGTHS (MILLIMETRES) (U.N.O ON DRAWINGS)                                                                                    1m HEIGHT
                                                                                                                                                                                                                                       - BARRIER/FENCE SHALL BE DESIGNED TO LOADING REQUIREMENTS OF AS1170.1\TABLE 3.3.
                                                                                                                                                                                                                                       - BARRIER/FEENCE GEOMETRY SHALL BE NON-CLIMBABLE AND COMPLY WITH B.C.A
                                                                                                                                                D500N BAR DIAMETER (mm)

                                                                               BAR LOCATION                            12             16              20                 24              28                32

                                                                                                                                                       LAP LENGTH (mm)

                                                                               ALL OTHER BARS                         450             600             850               1200            1400             1750

                                                                               WELDED MESH                                                                  225mm LAP
C:\Users\Ken\appdata\local\temp\AcPublish_7180\#19660_CI_OPW.dwg




                                                                   COPYRIGHT ©                                                                                                                Associated Consultants                         Client                                                                                                           Drawn        Verified              Project                                                       Drawing Title                                                 Scale             Sheet Size
                                                                                                                                                                                              SURVEYOR                                                                                                                                                        KL           DR
                                                                   This drawing is subject to
                                                                   copyright in accordance with                                                                                               Brian Naismith Development Consultant
                                                                                                                                                                                                                                             SURVEYOR PTY LTD                                                                                                                                    30 POTTERY STREET, POMONA                                     PROJECT NOTES                                                                       A1
                                                                   the agreement between TOD                                                                                                                                                                                                                                                                  Designed     Verified
                                                                   Consulting Pty Ltd (tc) and tc's                                                                                           T: 0477 925 871 E: [email protected]                                                                                                                    KL           DR                    PROPOSED RESIDENTIAL SUBDIVISION                              SHEET 2 OF 2                                                  Drawing Number
                                                                   client. This drawing shall only
                                                                   be used for this specific project.                                                                                                                                                                                                                                                         Approved     RPEQ No               RP DESCRIPTION    LOT 496 MCH 591                                                                                                    19660-C003
                                                                   This drawing shall not be used                                                                                                                                                                                                    Noosa: 07 5449 9600       Sunshine Coast: 07 5329 3190   D REYNOLDS   9072                  LOCAL AUTHORITY   NOOSA COUNCIL
                                                                                                                                                                                                                                                                                                                                                                                                 MCU APPROVAL      -                 HORIZ DATUM GDA2020 Z56                   0     10     20     30    40     50      60   Sheet              Revision
                                                                   for construction until marked as                                                                                                                                                                                                             PO Box 61, Noosaville, QLD 4566               Signed
                                                                                                          A        03.11.25   OPW SUBMISSION                                       KL                                                                                                                                                                                                            ROL APPROVAL      RAL19/0014        VERT DATUM AHD
                                                                   'Issued For Construction' in the
                                                                   revision description.                Rev         Date      Revision Description                               Drawn
                                                                                                                                                                                                                                                                                                     [email protected]     www.todconsulting.com
                                                                                                                                                                                                                                                                                                                     ABN 39 128 805 336                                               03.11.25   OPW APPROVAL                        RL DATUM                                      MEASUREMENT BAR - INCREMENTS IN mm                3 of 17       A

Log in to download the original (Civil Plans_19660_20260213_OPW_[A-B].pdf)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.