9. Recommendations
9.1     Road Traffic and Offsite Noise
Acoustic façade treatments are required to minimise noise from road traffic and offsite noise from
the neighbouring commercial premise. The dominant noise source, road traffic, is driving the
recommendation is listed for each noise-affected room.
9.1.1    Glazing
The minimum glazing treatments are presented in Table 13, with the installed glazing system to
comply with the following:

   •    The minimum glass thickness specified shall not be reduced regardless of the Rw
        performance of the glazing system.
   •    If compliance cannot be achieved with the minimum Rw ratings, the glass system shall be
        upgraded until compliance is achieved.
   •    Glazing specified with acoustic seals requires a Q-lon seal or an equivalent product, mohair
        seals are not acceptable.
   •    The glazier shall provide NATA test reports on request to verify compliance with the minimum
        Rw ratings. Generic reports are not acceptable.

                                   Table 13: Rw Ratings & Glazing Treatments

                            Location                               Rw Ratings




                                                                                                     Acoustic seals
                                                        QDC
                                                       Noise                              Glazing
                                                                               Glazing
                                                                        Roof
                                                                 Wall




            Unit    Level              Room           Category


              -      B              Restaurant           -       41      -     35        10.38 lam   yes
                              Kitchen/Living/Dining      1       41      -     35        10.38 lam   yes
              1      GF            Bedroom 1             1       41      -     35        10.38 lam   yes
                                   Bedroom 2             1       41      -     35        10.38 lam   yes
                              Kitchen/Living/Dining      1       41      -     35        10.38 lam   yes
              1                    Bedroom 1             1       41      -     35        10.38 lam   yes
                                   Bedroom 2             1       41      -     35        10.38 lam   yes
                              Kitchen/Living/Dining      2       41      -     35        10.38 lam   yes
              2      1             Bedroom 1             2       41      -     35        10.38 lam   yes
                                   Bedroom 2             2       41      -     35        10.38 lam   yes
                              Kitchen/Living/Dining      2       41      -     35        10.38 lam   yes
              3                    Bedroom 1             0       41      -     35        10.38 lam   yes
                                   Bedroom 2             0       41      -     35        10.38 lam   yes
                                  Kitchen/Living         1       41     38     35        10.38 lam   yes
             P1      2             Bedroom 1             1       41     38     35        10.38 lam   yes
                                   Bedroom 2             2       41     38     35        10.38 lam   yes
                                  Kitchen/Living         2       41     38     35        10.38 lam   yes
             P2      2             Bedroom 1             2       41     38     35        10.38 lam   yes
                                   Bedroom 2             2       41     38     35        10.38 lam   yes


9.1.2    Alternative Ventilation
We recommend that all locations nominated in Table 13 have the provision for an alternative
ventilation system similar to air-conditioning or mechanical ventilation to allow windows and doors
to be closed. Refer to National Construction Code (NCC) 2022 requirements and AS1668.2
Mechanical Ventilation in Buildings.




 2023121 R01M 2 Bottlebrush Avenue Noosa Heads RTN ENV.docx © Acoustic Works 2024                                     Page 17
Log in to download the original file

RFI - 7. Accoustic.pdf · 2.4 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.