Original source · versioned page text
Attachment 4B - Updated Bushfire Assessment and Mitigation Plan.pdf
22
Performance outcomes Acceptable outcomes Response
Water Supply for Fire Fighting Purposes
PO3 AO3.1 R3.1
Development provides an adequate water Premises are connected to the reticulated The subject site has access to a reticulated
supply for fire fighting purpose which is water supply. water supply/is in a water service area.
reliable, safely located and freely accessible. Editor's note—For reconfiguring a lot, water
supply needs to provide for a minimum flow and
pressure of 10 litres a second at 200kPa at all
times for fire fighting purposes.
OR
AO3.2
Where there is no available reticulated water
supply, the premises has:
1. an accessible dam, swimming pool or
water tank available for fire fighting
purposes with an onsite water volume of
not less than 5,000 litres; and
2. a water supply outlet pipe 50 millimetres in
diameter fitted with a standard fire brigade
fitting connected to the water supply (other
than where the water supply is in a
swimming pool or dam).
Editor’s Note—Water supply capacity for fire
fighting purposes is in addition to water supply
capacity for other uses and activities on the
premises.
Essential Community Infrastructure
RF17-040 – Boutique Hotel – Noosa Springs – Bushfire Hazard Assessment & Management Plan
Rob Friend & Associates Pty Ltd 10 February 2023
Preview the original
The page text is free to read. Previews and downloads of original files need an account.
Log in to previewSearchable page text hides email addresses. Original files are unchanged and may show email addresses.