                                                                                                                                                                                                                                                                                                                                                                                                  CONCRETE NOTES:                                                                        PAVEMENT PREPARATION NOTES:
                                                      STOP MESH 75mm
                                                                                225mm         225mm
                                                       SHORT OF JOINT                                            28mm DIA. 450mm LONG GRADE
                                                                                                                                                                                                                                                                                                                                                                                                  1.         ALL CONCRETE SUPPLY AND WORK SHALL MEET THE REQUIREMENTS OF                 1.      MATERIAL EXCAVATED FROM CUT AREAS SHALL NOT BE USED AS FILLING FOR
                                                                                                                 250R STEEL BARS AT 300 CTRS                                                                      5mm
                                                                                                                                                                                                                                                                                                                   2.4m-2.5m                                                                                 AS3600.                                                                             ROADS WITHOUT THE SUPERINTENDENTS APPROVAL.
                                                                                                                                                                                                                                                                                                                  AS INDICATED                                                                    2.         CONCRETE GRADE SHALL BE N32.                                                2.      SELECT FILL UNDER PAVEMENT TO BE PLACED AND COMPACTED IN 200mm
                                                                                                                                                                                                                                                                                                                                                                                                  3.         AGGREGATE FOR CONCRETE SHALL BE CLEAN AND FREE OF CLAY PARTICLES.                   DEEP LOOSE LAYERS TO SPECIFIED COMPACTION.
                                                                                                                                                                                                                                                                                                                                                                                                  4.         NO ADMIXTURES TO THE CONCRETE SHALL BE PERMITTED WITHOUT THE                3.      ALL WORKS ARE TO BE GRADED TO PROVIDE DRAINAGE DURING
                                                                                                                                                                                                                      ROADSEAL SL OR APPROVED EQUIVALENT JOINT
                                                                                                                                                                                                                      SEALENT RECESSED 3mm BELOW SURFACE LEVEL                                                                                                                                               PRIOR APPROVAL OF THE SUPERINTENDENT.                                               CONSTRUCTION.




                                                                                                                                                                                                  35mm
                                                                                                                                                                                                                                                                                                                                                                                                  5.         COMPLIANCE OF CONCRETE SUPPLY SHALL BE IN ACCORDANCE WITH THE               4.      MIN. DEPTH OF COURSES TO PAVEMENTS ARE DETAILED ON CROSS SECTIONS.
                                                                                                                                                                                                                                                                                                                                                                                                             REQUIREMENTS OF SECTION 20 OF AS3600.                                               ACTUAL PAVEMENT DEPTHS ARE TO BE DETERMINED FOLLOWING SOAKED CBR




                                                                                                                                                                                                                                                                                                                                           5.400
                                                                                              REFER DETAIL B                                                                                                                                                                                                                                                                                      6.         CONCRETE SURFACE SHALL BE BROOM FINISHED.                                           TESTS ON SUBGRADE.
                                                                                                                                                                                                                      CLOSED CELL POLYETHYLENE                                 100mm NOM HIGH WHEELSTOP                                                                                           7.         CONCRETE SHALL NOT BE PLACED WHEN HOT DRY WIND CONDITIONS                   5.      THE CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYING ALL RELEVANT
                                                                                                                                                                                                                      BACKING ROD                                            IN ACCORDANCE WITH AS2890.1                                                                                                     PREVAIL.                                                                            AUTHORITIES BEFORE COMMENCING WORK, FOR LOCATIONS OF SERVICES &
                                                                          DOWEL JOINT (DJ)                                                                                                                            6mm SAW CUT                                                     PLACED CENTRALLY                                                                                            8.         CONCRETE PLACED IN TEMPERATURES OVER 25 CENTIGRADE SHALL                            FOR REPAIR OF ANY DAMAGED SERVICES AS A RESULT OF THE WORK.




                                                                                                                                                                                                                                                                                                                                   1.100
                                                                                                                                                                                                                                                                                                                                                                                                             IMMEDIATELY AFTER PLACEMENT BE COATED WITH AN EVAPORATION                   6.      ALL WORK SHALL BE CARRIED OUT IN STRICT ACCORDANCE WITH THE
                                                                                        NTS
                                                                                                                                                                                                  DETAIL A                                                                                                                                                                                                   RETARDANT AND/OR CURING OIL APPROVED BY THE ARCHITECT.                              RELEVANT LOCAL AUTHORITY REQUIREMENTS.
                                                                                                                                                                                                         NTS                                                                                                                                                                                      9.         CONCRETE PAVEMENTS SHALL BE JOINTED AS DETAILED ON THE DRAWINGS.            7.      SIDE DRAINS ARE TO BE CONSTRUCTED UNDER ALL EXTERNAL KERB &
                                                                                                                                                                                                                                                                                                                                     EDGE OF KERB                                                            ALL SHRINKAGE CRACK CONTROL JOINTS SHALL BE SAWN WITHIN 24 HOURS                    CHANNEL IN ACCORDANCE WITH CURRENT BCC STANDARDS.
                                                                                                                                                                                                                                                                                                                                                                                                             OF CONCRETE PLACEMENT. ALL JOINTS SHALL BE SEALED WITH A PURPOSE            8.      REFER TO LOCAL AUTHORITY SPECIFICATIONS FOR COMPACTION
                                                                                                                                                                                                                                                                                          WHEELSTOP ARRANGEMENT DETAILS                                                                                      MADE PROPRIETARY SEALANT. JOINT SEALANT SHALL BE INSTALLED                          REQUIREMENTS AND TESTING FREQUENCIES.
                                                                                                                                                                                                                                                                                                                  SCALE 1:100                                                                                STRICTLY IN ACCORDANCE WITH THE MANUFACTURERS SPECIFICATIONS.               9.      REFER TO LOCAL AUTHORITY SPECIFICATIONS FOR TRENCH BACKFILL
                                                                                                                                                                                                         20mm




                                                                                                                                                                                    5mm
                                                                                                                                                                                                                                                                                                                                                                                                  10.        CONCRETE SHALL BE FULLY COMPACTED BEFORE SCREEDING WITH                             REQUIREMENTS IN ROADS.
                                                                                                                                                                                                                                                                                                                                                                                                             PARTICULAR CARE TAKEN AT EACH EXPANSION JOINT.
                                                                                                                                                                                                                                                                                                                                                                                                  11.        JOINT PREPARATION - BEFORE FRESH CONCRETE IS PLACED AT A
                                                                                                                                                                                                                         APPROVED MASTIC SEALANT
                                                                                                                                                                                                                                                                                                                                                                                                             CONSTRUCTION JOINT ROUGHEN AND CLEAN THE HARDENED CONCRETE                  PAVEMENT CONSTRUCTION NOTES:




                                                                                                                                                                                    10mm
                                                                                                                                                                                                                         (SIKAFLEX ROAD SEAL OR APPROVED EQUAL)
                                                                                                                                                                                                                                                                                                                                                                                                             SURFACE OF THE JOINT SO THAT ALL LOOSE OR SOFT FREE WATER, FOREIGN




                                                                                                                                                                                                                                                                                                                                                   150mm
                                                                     REFER DETAIL A                                                                                                                                      BOND BREAKER                                                                                                                                                                        MATTER IS REMOVED. ALL JOINTS HOWEVER MADE SHALL BE PROVIDED
                                                                                                                                                                                                                                                                                                                                                           R20mm                                                                                                                         1.      UNBOUND, SOFT OR OTHERWISE DELETERIOUS MATERIAL AT SUBGRADE SHALL
                                                                                                  SAW CUT JOINTS WITHIN 6 HOURS                                                                                                                                                                                                                                                                              WITH A GROOVE TO ACCOMMODATE SEALING MATERIAL.                                      BE EXCAVATED AND REPLACED WITH IMPORTED MATERIAL WITH A MINIMUM
                                                                                                                                                                                                                                                                                                                                                           Y12 TRIMMER
                                                   CUT 200mm LONG PIECE OUT                       OF CASTING SLAB                                                                                                        BACKING ROD                                                                                                                                                              12.        DIMENSIONAL TOLERANCES.
                                                                                                                                                                                                                                                                                                                                                           R10 @ 400mm CTRS                                                                                                                      CBR 10%.




                                                                                                                                                                                                                                                                                                                        200mm
                                                      OF EVERY SECOND WIRE




                                                                                                                                                                                                                                                                                                                         MAX.
                                                                                                                                                                                                                                                                                                                                                                                                              LENGTH SLAB (UP TO 18m):       +or- 6mm                                    2.      MATERIAL EXCAVATED FROM CUT AREAS SHALL NOT BE USED AS FILLING
                                                                                                                                                                                                                                                                                  REFER LANDSCAPE ARCHITECT
                                                                                                                                                                                                                         FILLER                                                   DETAIL FOR GARDEN BED AREA                                                                                                  WIDTH SLAB:                    +or- 6mm                                            WITHOUT THE CERTIFYING ENGINEERS APPROVAL.
                                                                                                                                                                                                                                                                                                                                                                                                              THICKNESS SLAB:                + 10mm - 3mm                                3.      SELECT FILL UNDER PAVEMENT TO BE PLACED AND COMPACTED IN 200mm
                                                                                                                                                                                                                                                                                                                                                                                                  13.        CURING. DURING THE CURING PERIOD MAINTAIN THE CONCRETE AT A                         MAXIMUM LOOSE THICKNESS LAYERS TO 95% MODIFIED COMPACTION.
                                                                                                                                                                                                                                                                                                                                                                                                             REASONABLY CONSTANT TEMPERATURE, NOT EXCESSIVELY HOT OR COLD,               4.      ALL COMPACTION TO BE SUBJECTED TO TESTING IN ACCORDANCE WITH THE
                                                                                                                                                                                                                                                                                                                                                                                                             TO MINIMISE MOISTURE LOSS, BY A SUITABLE METHOD WHICH MAY INCLUDE:




                                                                                                                                                                                                                                                                                                                                                                           REFER TO STRUCTURAL
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 RELEVANT S.A.A. CODE.




                                                                                                                                                                                                                                                                                                                                                                           ENGINEER'S DRAWINGS
                                                                                                                                                                                                                                                                                                                                                                                                              -     PONDING OR CONTINUOUS SPRINKLING WITH WATER (MOIST CURING)
                                                                                                                                                                                                  DETAIL B                                                                                                                                                                                                    -     AN IMPERMEABLE CLEAR MEMBRANE, TAPED AT JOINS AND SEALED
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                         5.      ALL WORKS ARE TO BE GRADED TO PROVIDE DRAINAGE DURING
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 CONSTRUCTION.
                                                                                                                                                                                                         NTS                                                                                                             NOTE: CONTINUE                                                                             AT THE EDGES                                                         6.      SUBGRADE IS TO BE COMPACTED AT OPTIMUM MOISTURE CONTENT TO ACHIEVE
                                                                        SAW CUT JOINT (SJ)                                                                                                                                                                                                                         CONSTRUCTION JOINT IN SLAB                                                                 -     AN ABSORPTIVE COVER KEPT CONTINUOUSLY WET                                    98% STANDARD FOR THE TOP 300mm & 95% STANDARD BELOW THE TOP
                                                                                        NTS                                                                                                                                                                                                                          THROUGH INTEGRAL KERB                                                                    -     AN APPROVED CURING COMPOUND (SUBMIT DETAILS FOR APPROVAL                     300mm.
                                                                                                                                                                                                                                                                                                                                                                                                                    PRIOR TO CONCRETING OPERATIONS TAKING PLACE, APPLIED IN              7.      ALL TRENCHES IN ROADWAYS ARE TO BE BACKFILLED TO BOX LEVEL USING
                                                                                                                                                                                            8mm
                                                                                                                                                                                                                7mm
                                                                                                                                                                                                                                                                                                                INTEGRAL KERB DETAIL                                                                                ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.                             APPROVED MATERIAL WITH A MINIMUM CBR 15. THIS BACKFILL SHALL BE

                                                                                      TRIMMERS ARE NOT TO EXTEND
                                                                                                                                                                                                                                                                                                                        (IK)                                                                                 CURING PERIOD: CURE CONTINUOUSLY UNTIL THE CUMULATIVE NUMBER OF
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 PLACED IN LAYERS NOT EXCEEDING 300mm LOOSE AND COMPACTED UNTIL THE
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 DRY DENSITY IS NOT LESS THAN 95% OF THE MATERIALS DRY DENSITY
                                                                                      ACROSS PROPOSED JOINTS.                                                                                                                                                                                                                   SCALE 1:10
                                                                                                                                                                                                                                                                                                                                                                                                             DAYS OR FRACTIONS THEREOF (NOT NECESSARILY CONSECUTIVE) DURING                      (MODIFIED COMPACTION). COMPACTION TESTS ARE TO BE CARRIED OUT IN EACH
                                                                                                                                                                                                                      SILICONE SEALANT                                                                                                                                                                       WHICH THE AIR TEMPERATURE IN CONTACT WITH THE CONCRETE IS ABOVE                     LAYER OF BACKFILL, ONE TEST EVERY 50m OR PART THEREOF. ONE IN FIVE
                                                                                                                                                                                                                      DEBONDING STRIP                                                                                                                                                                        10°, TOTALS NOT LESS THAN 7 DAYS.                                                   TESTS TO BE LOCATED BESIDE A MANHOLE OR GULLY.
                                                                                                                                                                                            7mm




                                                                                                                                                                                                                                                                                                       NOTE:                                                                                                                                                                             8.      SIDE DRAINS SHALL CONNECT TO A FREE DRAINAGE OUTLET SUCH AS
                                                                              2-N12 2.0m LONG TRIMMERS TO RE-ENTRANT                                                                                                                                                                                   REFER TO STRUCTURAL ENGINEER                                                                                                                                                              STORMWATER GULLY, KERB AND CHANNEL OR GROUND.
                                                                              CORNERS, PITS, COLUMNS AND THE LIKE.                                                                                                    JOINT FILLER                                                                     DETAILS FOR SUSPENDED CARPARK
                                                                                                                                                                                                                                                                                                       DESIGN.
                                                                                                                                                                                                                                                                                                                                                                                                  ROADWORKS GENERAL NOTES:
                                                                                                                                                                                                                                                                                                                                                           1 LAYER N32 SL82 MESH 50mm TOP COVER
                                                                                                                                                                                                                                                                                                                                                                                                       1.     ALL DIMENSIONS ARE IN METRES UNLESS NOTED OTHERWISE.                       JOINT NOTES
                                                            TRIMMER BAR DETAIL (TB)




                                                                                                                                                                                                                                                                                  180mm
                                                                                                                                                                                                                                                                                                                                                                                                       2.     ALL LEVELS ARE TO THE LIP OF KERB AND CHANNEL.
                                                                                  NTS                                                                                                                                                                                                                                                                                                                  3.     ROAD WIDTH DIMENSIONS REFER TO NOMINAL KERB LINE.                          1.      ALL DOWELS TO BE CONSTRUCTED AT MINIMUM SPACING SPECIFIED.
                                                                                                                                                                                                  DETAIL C                                                                                                                                                         UNBOUND GRANULAR SUB-BASE
                                                                                                                                                                                                                                                                                                                                                                                                       4.     CO-ORDINATES FOR KERB/KERB & CHANNEL REFER TO NOMINAL KERB                 2.      DOWELS TO BE CONSTRUCTED PERPENDICULAR TO JOINT.
                                                                                                                                                                                                         NTS




                                                                                                                                                                                                                                                                                  150mm
                                                                                                                                                                                                                                                                                                                                                                   CONSISTING OF CLASS 1                      LINE/LIP OF CHANNEL RESPECTIVELY.                                          3.      CONTRACTOR TO ENSURE MINIMUM 50mm COVER TO OUTER MOST REINFORCING
                                                                                                                                                                                                                                                                                                                                                                   GRANULAR MATERIAL                   5.     TOPSOIL IS TO BE STRIPPED AND REPLACED ON ALL DISTURBED                            BAR.
                                                                                                                                                                                                                                                                                                                                                                                                              EARTHWORKS AREAS WITHIN FOOTPATH AREA. EXCESS TOPSOIL SHALL                4.      REFER SITE CONDITIONS FOR LOCATIONS OF ISOLATION JOINTS (IJ's)
                                                                                                                                                                                                                                                                                                                                                                                                              BE DISPOSED OFF-SITE.                                                      5.      SPACING OF DOWEL JOINTS (CONCRETE POURS) TO BE NO GREATER THAN
                                            STOP MESH 75mm SHORT OF CONNECTION
                                                                                                                                                                                                                                                                                                                                                                                                       6.     ALL TEMPORARY AND PERMANENT SIGNAGE AND LINEMARKING TO BE IN                       24.00m
                                                        PROPOSED CONCRETE                                   REFER DETAIL C
                                                                                                                                                                                                                                                                                                                                                                                                              ACCORDANCE WITH MAIN ROADS STANDARDS (MANUAL OF UNIFORM                    6.      SAWN JOINTS TO BE EVENLY SPACED IN BETWEEN CONCRETE POURS AT
                                                                                                                CONCRETE STRUCTURE                                                                                                                                                                                                         TOP 150mm OF SUBGRADE TO BE COMPACTED TO                           TRAFFIC CONTROL DEVICES).                                                          NOMINAL 6.00m - 7.00m SPACINGS.
                                         SL92 STEEL MESH 50mm TOP COVER
                                                                                                                                                                                                                                                                                                                                           100% STD COMPACTION AS PER AS3798
                                                                                                                                                                                                                                                                                                                                                                                                       7.     ALL DIMENSIONS ARE TO BE CHECKED ON-SITE BEFORE WORK COMMENCES.            7.      CONTRACTOR TO PROVIDE TRIMMER BARS TO ALL SERVICES PITS,
                                                                                                                                                                                                                                                                                                 TRAFFICABLE CONCRETE                                                                                  8.     DIMENSIONS SHALL NOT BE OBTAINED BY SCALING THE DRAWING.                           RE-ENTRANT CORNERS, AND AS DIRECTED ON-SITE.
                                                                                                                                                                                                                                                                                                                                                                                                       9.     DURING CONSTRUCTION BARRIERS, LIGHTS & SIGNS SHALL BE MAINTAINED
                                                                                                                                                                                                                                                                                                   PAVEMENT DETAIL                                                                                            TO ENSURE SAFE PASSAGE OF TRAFFIC AND PEDESTRIANS IN ACCORDANCE
                                                                                                                                                                                                                                                                                                                  SCALE 1:10                                                                                  WITH THE REQUIREMENTS OF THE LOCAL AUTHORITY.
                                                                                                                                                                                                                                                                                                               ASSUMED CBR 5%                                                                          10.    ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH
                                                                                                                                                                                                                                                                                                                                                                                                              S.A.A. CODES & BY-LAWS AND ORDINANCES OF THE RELEVANT LOCAL
                                                                                                                                                                                                                                                                                                              SUBGRADE NOTE:                                                                                  AUTHORITY AND WORKPLACE HEALTH AND SAFETY REQUIREMENTS.
                                                                          ISOLATION JOINT                                                                                                                                         SAFETY FENCE TO BE FIXED TO TOP OF                              SUBGRADE TO BE TEST ROLLED PER AS 3798
                                                                                                                                                                                                                                                                                                  PRIOR TO CONSTRUCTING PAVEMENT LAYERS.
                                                                                                                                                                                                                                                                                                                                                                                                       11.    THE CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYING ALL RELEVANT
                                                                                        NTS                                                                                                                                       RETAINING WALL. TYPE TO BE                                                                                                                                                  AUTHORITIES AND PAYING ALL FEES NECESSARY BEFORE COMMENCING
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                         NOT FOR CONSTRUCTION
                                                                                                                                      BOUNDARY
                                                                                                                           PROPERTY




                                                                                                                                                                                                                                  CONFIRMED BY SUPERINTENDENT.
                                                                                                                                                                                                                                                                                                                                                                                                              WORK, FOR LOCATING ALL EXISTING SERVICES AND FOR REPAIR OF ANY
                                                                                                                                                                                                                                                                           PROPOSED CARPARK. REFER                                                                                                            SERVICES DAMAGED AS A RESULT OF THE WORKS.
                                                                                                                                                                                                                                                                           STRUCTURAL ENGINEERS DRAWING                                                                                                12.    DAMAGED FOOTPATHS AND PRIVATE PROPERTY SHALL BE REINSTATED
                                                                                                                                                                                                                                                                           FOR SUSPENDED CARPARK DESIGN.
                                                               SAFETY FENCE. TYPE AND FIXING                                                                                                                                                                                                                                                                                                                  TO THEIR ORIGINAL CONDITION.
                                                                                                                                                                                                                                     PROPOSED INTEGRAL KERB (IK).
                                                               LOCATION TO BE CONFIRMED BY                                                                                                                                                                                                                                                                                                             13.    CONTRACTOR TO VERIFY ALL INVERT LEVELS, SURFACE LEVELS, COVER
                                                               SUPERINTENDENT.                                                                                                             EXISTING
                                                                                                                                                                                                                                                                                                                                                                                                              OVER DRAINAGE LINES, AND MINIMUM FALLS ARE CORRECT & OBTAINABLE
                                                                                                                                                                                           SURFACE
                                                                                                                                                                                                                                                                                                                                                                                                              PRIOR TO COMMENCEMENT OF WORK.                                                  WORKPLACE HEALTH AND SAFETY NOTE:
                                                                           PROPOSED INTEGRAL                                                                                                                                                                                                                                                                                                           14.    THE CONTRACTOR'S ATTENTION IS DRAWN TO THE REQUIREMENTS OF THE                  ALL WORKS UNDERTAKEN BY THE CONTRACTOR SHALL COMPLY WITH THE
STRUCTURAL ENGINEERS DRAWING                                                        KERB (IK).                                                                                                                                                                                                                                                                                                                WORKPLACE HEALTH AND SAFETY ACT 2011. ALL WORK IS TO BE CARRIED                 REQUIREMENTS OF THE QUEENSLAND WORK HEALTH AND SAFETY ACT 2011.
FOR SUSPENDED CARPARK DESIGN.                                                                                                                                                                                                                                                                                                                                                                                 OUT IN ACCORDANCE WITH THIS ACT AND IN PARTICULAR THE CONTRACTOR                CONTACT THE NEAREST OFFICE OF THE DIVISION OF WORKPLACE HEALTH AND
                                                                     PROPOSED CARPARK                                                                                                             PROPOSED
                                                                                                                                                 EXISTING                                         SURFACE                                                                                                                                                                                                     IS TO ENSURE THE REQUIREMENTS OF THIS SPECIFICATION WITH REGARD TO              SAFETY FOR INFORMATION. PHONE No. 1300 362 128.
                                                                                                                                                 SURFACE                                                                    PROPOSED RETAINING WALL. REFER TO
                                                                                                                                                                                                                            STRUCTURAL DRAWINGS FOR DETAIL.                                                                                                                                                   'NOTIFICATION IN RELATION TO A NOTIFIABLE PROJECT' ARE FULFILLED.
                                                                                                                                                                                                                                                                                                                                                                                                       15.    ALL MANHOLE AND GULLIES DEEPER THAN 1.200m SHALL BE FITTED WITH                 DIAL BEFORE YOU DIG:
                                                                                                                                                                                                                                                                                                                                                                                                              STEP IRONS. REFER TO STANDARD DRAWINGS.                                         IT IS THE CONTRACTORS RESPONSIBILITY TO CONTACT 'DIAL BEFORE YOU DIG'
                                                                                                                                                                                                                                                                                                                                                                                                       16.    CONTRACTOR SHALL VERIFY THE LOCATION OF ALL EXISTING SERVICES                   PH.1100 FOR THE LOCATION OF EXISTING PUBLIC UTILITIES PRIOR TO EXCAVATION.
                                                                                                                                                                                                                                                                                                                                                                                                              PRIOR TO COMMENCEMENT OF WORK. ALL EXISTING SERVICES AND                        ANY DAMAGE CAUSED TO EXISTING PUBLIC UTILITIES BY THE CONTRACTOR WILL
                                                                                                                                                                                                                                                                                                                                                                                                              STRUCTURES ARE TO BE MAINTAINED IN GOOD ORDER FOR THE DURATION                  BE REPAIRED BY THE RELEVANT AUTHORITY AT THE CONTRACTOR'S EXPENSE.

                                                                                                                                                                                                                                                      BASEMENT LEVEL FFL 8.050                                                                                                                                OF THE CONTRACT. ANY COST ASSOCIATED WITH REPAIRING DAMAGE TO
                                                                                                                                                                                                                                                                                                                                                                                                              EXISTING SERVICES SHALL BE BORNE BY THE CONTRACTOR.                             EXISTING SERVICES NOTE:
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              THIS DESIGN HAS BEEN PREPARED BASED ON SERVICE AUTHORITY AS
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              CONSTRUCTED INFORMATION. NO POT HOLING HAS BEEN UNDERTAKEN TO VERIFY
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              EXISTING SERVICE LOCATIONS AND DEPTHS. IT IS THE CONTRACTORS


                                                                              SECTION                                  B                                                                                              SECTION                           A                                                                                                                                                                                                                                     RESPONSIBILITY TO UNDERTAKEN POT HOLING TO VERIFY THE DESIGN.


                                                                                                                                                                                                                      SCALE 1:50                                                                                                                                                                                                                                          0          2               4           6m
                                                                              SCALE 1:50                                                                                                                                                              CR01                                                                                                                                                                                             SCALE 1:100 (A1)
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          REAL PROPERTY DESCRIPTION
                                                                                                                CR01                                                                                                                                                                                                                                                                                                                                                                                                      LOT 59 ON RP228906




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                             © MILANOVIC NEALE CONSULTING ENGINEERS
                                                                                                                                                                                                                                                                                                                                                                                                                                                                          (SCALE BEFORE REDUCTION)
        ALL SCALES ARE AS SHOWN (A1)
        DO NOT SCALE FROM DRAWING




                                       REV.                 DESCRIPTION                           DATE         INIT.                                                                                                                       CONTACT DETAILS               CLIENT                                                                              PROJECT                                                                 TITLE                                                                            DRAWN              DESIGNED           DATE
                                        A FOR CLIENT REVIEW                                      23.02.21       SM                                                                                                                         E [email protected]                                                                                                                                                                                                                                                                 SM                SM                FEB 2021
                                        B FOR APPROVAL                                           09.04.21       SM                                                                                                                         W www.mnce.com.au

                                                                                                                                                                                                                                                                                                                                                                   STORE LOCAL - NOOSAVILLE                                                                                                                           CHECKED            APPROVED

                                                                                                                                                                                                                                                                                          STORELOCAL PTY LTD                                                                                                                          ROADWORKS NOTES AND DETAILS                                                             DH

                                                                                                                           BRISBANE                         IPSWICH
                                                                                                                                                                                                                                                                                                                                                                           STAGE 3                                                                                                                                    DRAWING No.                                   REV.
                                                                                                                                                                                       SYDNEY                     GOLD COAST
                                                                                                                           PH No. (07) 3255 1877            PH No. (07) 3281 6603      PH No. 1300 827 901        PH No. 1300 827 901                                                                                                                                                                                                                                                                                    S12884 - CR04                                 B
Log in to download the original file

S12884-210412-Store Local Stage 3 -For Approval.pdf · 7.3 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.