FACT SHEET
Effect of Fixing Plasterboard
Whilst a 150 thick precast concrete panel
has a Ctr value of -5, this value is made
more negative if a plasterboard wall on
furring channels is fixed to the precast
wall, giving a less favourable result
overall. The thinner the furring channel
and the lighter the plasterboard, the
more the Ctr factor is made negative.
This should be watched carefully. When
dealing with internal noise and furring
channels are applied to both sides of
the precast wall together with the use
of 10mm plasterboard the effect of the
two cladding systems is compounded
in respect to Ctr. If it is necessary to
provide cladding with airspace for the
running of services then it is important
that the plasterboard is either 16mm
or 13mm sound rated, that the furring
channels are no less than 28mm deep
and that effective insulation is applied to
both cavities.
It can be seen from Table 1 that a 150
mm precast concrete panel (which
weighs 360 kg/m2) would provide at
least 50 dB reduction of sound levels
from outside to inside when exposed
to road or rail traffic (or factory noise –
refer to the Handbook for more detailed
information).
Another simple rule of thumb that can
be applied to materials to calculate their
approximate transmission loss is the
‘mass law’ equation:
TL = 20 log 10 (mf) – B
Where: TL = transmission loss (dB)
m = surface mass (kg/m2)
f = frequency (Hz)
B = 48 dB (on average but can range
from 45-53).