Text shows just the words. Original shows the document exactly as it was published.

Officer:	Wilhelm Koschade
Direct Telephone:	07 53296215
Our Reference:	MCU16/0049
Your Reference	NA
26 May 2016

B Connan & Mr GA Connan & PR Knight
C/- Martoo Consulting Pty Ltd
C/- Nadine Gorton
PO Box 1684
NOOSA HEADS  QLD  4567

Dear Sir/Madam

Information Request
Sustainable Planning Act 2009

I refer to your application and advise that Council requires further information to satisfactorily assess the proposal.
application details
Application No:	MCU16/0049 & OPW16/0109
Proposal:	Development Permit for Material Change of Use of Premises - Multiple Housing Type 2 - Duplex
Street Address:	38 Elanda St SUNSHINE BEACH  QLD  4567
Real Property Description:	Lot 158 RP 48112
Planning Scheme:	The Noosa Plan (16 September 2013)
information required
The information requested is set out below:

Issue
The proposed stairs, porch and timber walkway of Residence No. 1 exceeds 1.0m relative to the natural ground level and is located well within the minimum side boundary setback. This allows users of the premises to overlook onto the adjoining lot and does not preserve the visual privacy of the neighboring residence.

Information Required
Please provide an amended landscaping plan which incorporates appropriate screening within the setback where the stairs, porch and timber walkway exceeds 1.0m relative to natural ground.

Issue
The submitted stormwater design is not acceptable as it has not been prepared by an RPEQ or qualified drainage consultant and is not supported by a geotechnical review for the proposed on-site infiltration. Council also has concerns with the discharge of runoff from the driveway area. The submitted plans indicate a number of pits with discharge directed to the kerb without any treatment.
Information Required
Provide a Stormwater Management Plan for the development that is prepared by an RPEQ or suitably qualified drainage consultant. The plan must include but not be limited to:
Detail on the type of infiltration system
Comment from an RPEQ or geotechnical engineer in regard to the soil types and the capacity to cater for the proposed infiltration
Detail on the drainage system for the driveway area demonstrating compliance with Specific Outcome O6 of the Driveways and Carparking Code
Discharges rates where stormwater is discharged into the kerb and channel. Please note that this rate must not exceed 25l/sec at any one location
Certification that there is no increase in runoff from the site from the predevelopment rates.

Issue
The proposal includes substantial earthworks to provide for the sub-floor (Garage) level. Council has concerns with the extent of earthworks proposed and the stability of the site and the adjoining properties during the construction and in the longer term.

Information Required
Provide an earthworks plan for the development that is prepared by an REPQ or suitably qualified geotechnical engineer. The plan must include but not be limited to:
An investigation of the soil types to determine if specialised construction methods are required to maintain the stability of the site and the adjoining properties during the construction phase and in the longer term

Issue
Council has a number of concerns with the proposed access and carparking arrangements:
The sectional drawings indicate that the intention is to cut up to 800mm-900mm in the road reserve (the maximum at the property boundary). The submitted plans do not indicate the extent of the cut or any retaining structures/batters. Earthworks of this extent will eliminate the potential for future footpaths and also have the potential to affect third party services in the road reserve.
The layout does not provide sufficient area to permit vehicles to manoeuvre on site in order to be able to enter and exit the site is a forward gear.

Information Required
Provide plans of the access driveway extending from the centre line of Elanda Street to the garage area. The plan must be prepared by an RPEQ and must include but not be limited to:
Minimising the excavation within the road reserve to provide the opportunity for future pedestrian paths
Any buried services that may be affected by the excavation and construction of the driveway. If third party services may be affected provide the necessary approval documents for the works
A longitudinal section that demonstrates that the grades are in accordance with Council’s standard drawings
An indication of any necessary retaining structures or batters. Please note that Council will not accept any design that creates a trip hazard within the road reserve.
Provide an amended design that provides for sufficient space within the site to permit vehicles accessing all carspaces to enter the site in a forward gear, manoeuvre on site and exit the site in a forward gear in a total of 3 movements. The vehicles and the manoeuvring areas must be in accordance with AS/NZS2890.1:2004
End of Information Request
Under the provisions of the Sustainable Planning Act 2009, you have three options available in response to this Information Request. You may give the referral agency (in this instance Council) and the assessment manager:

all of the information requested; or
part of the information requested together with a written notice asking the requesting authority to proceed with the assessment of the application; or
a written notice;
stating that you do not intend to supply any of the information requested; and
asking the requesting authority to proceed with the assessment of the application.
Please be aware that under Section 279 of the Sustainable Planning Act 2009, the applicant is to respond to any Information Request within 6 months of the request or otherwise, the application lapses.
Staff are available to meet to discuss the application and information this request.   If you have any further queries or would like to arrange a meeting in relation to the above, please contact me on the above number.

Yours faithfully,

Wilhelm Koschade

[word/footer1.xml]
Page 2 of 3

[word/footer2.xml]
PO Box 141		P. (07) 5329 6500	[email protected]	
	TEWANTIN  QLD  4565	F. (07) 5329 6501	www.noosa.qld.gov.au
				Page 1 of 3

[word/header1.xml]
MCU16/0049

Used in these records

About this file

File size
63 KB (small file)
File type
DOCX

No other editions are linked here.

Original file

Log in to download the original file

Info Request MCU16_0049.docx · 63 KB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.