Response to Information Request · OPW11/0177
TATE PROFESSIONAL ENGINEERS PTY LTD
ABN 28 086 262 035
5. Detail the RL of the overflow of the underground rainwater tanks and inlet to the Rapid
Infiltration Pits on the submitted drawings.
We note that proposed rainwater harvesting tanks as indicated on drawing D01 C occur above
proposed ground floor level of RL21.5m AHD and the tops of the proposed RIP's are to be at
RL18.45m AHD.
As such there will be no shortage of fall or gradient required to achieve adequate overflow of
tanks to the RIP's.
Building drainage, guttering, spouting, etc is beyond the scope of this Operational Works
application and hence details of such are not included at this time but will be addressed in future
hydraulic consultant's applications as appropriate.
6. Provide in situ hydro conductivity testing to confirm that the assumptions made on soil
permeability and infiltration rate of the insitu soils are accurate.
Infiltration rates applied to the RIP analysis spreadsheet are derived from in-situ prototype testing
carried out by Tate Professional Engineers (refer Appendix B of Stormwater Management Plan)
with a factor of safety of two (2) applied. Such results have been accepted for all previous
Operational Works applications and the higher order MCU approval and management plans
controlling development of the entire Settlers Cove site.
7. Demonstrate that scour along the downstream batter / weir of the turfed swale along
the rear boundary will not occur in a major storm event.
Rapid Infiltration Pits proposed along the site's northern frontage have been designed to infiltrate
stormwater runoff for events up to 100 year ARI without overtopping and with a factor of safety of
two (2) applied.
In addition to this a swale around 60m long x 2m wide and with a depth of 0.35m is proposed
above surcharge levels of the RIP's to contain and further infiltrate runoff from storms of "biblical
proportions".
By adopting a level Swale along the full length any discharge from the Swale during such
incredibly unlikely storm events would be dispersed along the full length of the swale so as not to
cause scour of the escarpment.
As such Condition 22 of the MCU decision notice is satisfied.
Weru7 this adequately addresses all issues raised and look forward to receipt of a decision notice.
Yours faithfully
Sted.HHarrison - Director
for AMTE. PROFESSIONAL ENGINEERS PTY LTD
Encl/ Dwg S3000/08/L5-6/D03D
Cc: Mr Gary Godfrey
S3000/111L5/Response to Information Request - Sunshine Coast Regional Council
SH/cw
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Response to Information RequestRelated documentApplication case desk ↗
About this file
- File size
- 1.9 MB (small file)
- File type
No other editions are linked here.