• The developer will be required to submit with any connection application, a water supply
network analysis by a suitably qualified and experienced consultant, outlining the impacts
on the existing network to demonstrate that no customer within the current service area is
disadvantaged by connecting this development to the network. The water supply network
analysis shall cover the DMA- VLSNR. The analysis shall include the identification of any
upgrading works required on the existing systems to accommodate the proposed
development and the route of any external mains identified in the analysis. The developer
is responsible for all costs associated with the installation of identified upgrades to the
network.
• This development will be required to provide;
o Metered water service to all units within the development and install a primary meter
and sub- meters in accordance with Queensland Plumbing and Wastewater Code
2010 – Part 4 and Unitywater’s sub metering policy.
o A single sewer connection to the community title lot in accordance with SEQ design
standards, with internal sewers to all units within the development.
• The connection application shall accompany plans indicating,
o The location of any metered water connection/s and sewerage property connections
including offsets from boundaries and invert levels for new sewerage connections.
o Any proposed large diameter water connections (greater than Ø25mm), above ground
master meter assembly (This shall be located within the development property
boundary) and proposed sub-meter installations.
• Direct connection of pressure boosting pumps to Unitywater network is not favoured by
Unitywater but sometimes the requests can be considered if the network in the area has
adequate capacity. If there is any such proposal, details of the pumps (pump curves and
design calculations) including certification by the hydraulic consultant that the installed
pumps will have a flow rate no greater than Unitywater’s standards of service for the site to
be submitted to Unitywater’s Development Services for approval prior to installation.
• Should an approval for connection be provided by Unitywater, the developer will need to
apply to Unitywater for a Private Works Quote in relation to the cost for new metered
water supply service connection, live connections to existing water/sewer infrastructure
and/or installation of large diameter water meter by Unitywater. A copy of the connection
approval and associated approved plans detailing the new connections must accompany
the private works quotation application. Please refer Unitywater’s website at
http://www.unitywater.com/private-works. for further details.
• All water supply and sewerage works must be designed and constructed in accordance
with the South-East Queensland Water Supply and Sewerage Design and Construction
Code, Unitywater’s Connections Administration Manual and any other matter Unitywater
considers to be relevant to the connection or supply of its water services or wastewater
services.
• Where works associated with the Connection Application results in works to be carried
out in a publicly controlled place e.g. roads, it is the Applicants responsibility to gain the
necessary approvals from the relevant authority e.g. council, Department of Transport
Page 2 of 3
Unitywater is a statutory authority that provides water and sewerage services for the Unitywater has certification to
OH&S ISO 4801:2001 Reg No 4260
Moreton Bay, Sunshine Coast and Noosa Council areas. Environmental ISO 14001:2004 Reg No 4259
Quality Systems ISO 9001:2008 Reg No 4258
Revision No: 2 Effective Date: 19/02/2015 Next Review Date: 19/02/2018
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Attachment C - Engineering Technical Note.pdfRelated documentApplication case desk ↗
About this file
- File size
- 11.5 MB (very large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.