Original source · versioned page text
S1301229_Lv-drop_040920
SYSTEM DIAGRAM 4/09/2020
0.000 VD
U761292
370m
Al UG:240A/4C
No Load
0.0000A
10m 5m
Al UG:240A/4C An Cu:185C
No Load No Load
0.00 00A 0.00 00A
LOIMP
CCT1 0.000 VD 0.00 0 VD
SC2220505
250V U761293 LP2220504
250.0000 A
0.00 0 VR
+0.000 A
135m
Al UG:240 A/4C
[email protected]
83.3333A
CCT2 1.645 VD
U2220500
0.942 VD 1.858 VD
U2220507 U2220508
45m 20m
Al UG:240A/4C Al UG:240A/4C
[email protected] [email protected]
83.3333A 83.3333A
15m 5m 95m 80m
Al UG:240 A/4C An Cu:185C Al UG:240A/4C Al UG:240A/4C
No Load [email protected] No Load No Load
197. 1688A 142.2589A 83.3333A 0.0000A
CCT3 0.442 VD 0.525 VD 1.618 VD 1.61 8 VD
U2220506 U2220503 U2220509 LP2 220510
SPARE
CCT4
LEGEND
Segment Name
Segment Length
LVDrop Version 8.0.3
Conductor
Loads @ POA
SC2220505 Drawn Date 4/09/2020
Current
Peter Eustace & Associates Checked Time 11:52 AM
Vdrop(V) Vdrop(V) Peter Eustace & Associates Approved Page 1 of 1
Node Name Node Name
Loads Loads C:\Users\aaronp\Peter Eustace & Associates\2019 PROJECTS - Documents\19-055
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalFull text of the other 4 pages
Page 2
SYSTEM DIAGRAM 7/09/2020
LOIMP
SPARE
CCT1
SC1405163
250V
648 A
0.000 VR
+0.000 A
300A
CCT2
DIRECT TO
CUSTOMER - 600A
MAXIMUM DEMAND
300A
CCT3
1.470 VD
U2220523
140m
Al UG:240A/4C
[email protected]
83A
50m 50m
Al UG:240A/4C Al UG:240A/4C
No Load No Load
83A 0A
CCT4 0.622 VD 0.622 VD
U2220522 LP2220521
LEGEND
Segment Name
Segment Length
LVDrop Version 8.0.3
Conductor
Loads @ POA
New Study Drawn Date 7/09/2020
Current
Peter Eustace & Associates Checked Time 9:52 AM
Vdrop(V) Vdrop(V) Peter Eustace & Associates Approved Page 1 of 1
Node Name Node Name
Loads Loads C:\Users\aaronp\Peter Eustace & Associates\2019 PROJECTS - Documents\19-055
Page 3
SYSTEM DIAGRAM 7/09/2020
1.597 VD
U2220520
140m
Al UG:240A/4C
[email protected]
142A
5m 180m
Al UG:240A/4C Al UG:240A/4C
No Load [email protected]
197A 83A
LOIMP
CCT1 0.159 VD 1.227 VD
SC846991
250V UnRated U2220518 LP2220529
451 A
0.000 VR
+0.000 A
SPARE
CCT2
OPEN
CCT3
302A
C AND I LOAD, 302A USED TO
DEMONSTRATE WORST
CCT4 CASE. ACTUAL LOAD
CURRENTLY MUCH LOWER
LEGEND
Segment Name
Segment Length
LVDrop Version 8.0.3
Conductor
Loads @ POA
New Study Drawn Date 7/09/2020
Current
Peter Eustace & Associates Checked Time 10:09 AM
Vdrop(V) Vdrop(V) Peter Eustace & Associates Approved Page 1 of 1
Node Name Node Name
Loads Loads C:\Users\aaronp\Peter Eustace & Associates\2019 PROJECTS - Documents\19-055
Page 4
SYSTEM DIAGRAM 4/09/2020
80m 35m
Al UG:240A/4C Al UG:240A/4C
[email protected] [email protected]
197.1688A 83.3333A
LOIMP
CCT1 1.972 VD 2.277 VD
SC761294
250V UnRated U761295 U2220515
596.5260 A
0.000 VR
+0.000 A
275m
Al UG:240A/4C
[email protected]
83.3333A
4.673 VD
U763852
480m
Al UG:240A/4C
No Load
0.0000A
CCT2 0.000 VD
STN12
95m 30m 210m
Al UG:240A/4C Al UG:240A/4C Al UG:240A/4C
No Load No Load [email protected]
197.1688A 142.2589A 83.3333A
CCT3 2.359 VD 2.886 VD 3.873 VD
U2220514 U2220512 LP2220510
35m 130m
Al UG:240A/4C Al UG:240A/4C
[email protected] [email protected]
83.3333A 83.3333A
2.668 VD 3.486 VD
U2220513 U2220516
120m 215m
Al UG:240A/4C Al UG:240A/4C
No Load [email protected]
301.5028A 250.0000A
CCT4 4.945 VD 8.687 VD
U2220524 LP2220529
25m
Al UG:240A/4C
[email protected]
83.3333A
5.160 VD
U2220525
LEGEND
Segment Name
Segment Length
LVDrop Version 8.0.3
Conductor
Loads @ POA
SC761294 Drawn Date 4/09/2020
Current
Peter Eustace & Associates Checked Time 12:01 PM
Vdrop(V) Vdrop(V) Peter Eustace & Associates Approved Page 1 of 1
Node Name Node Name
Loads Loads C:\Users\aaronp\Peter Eustace & Associates\2019 PROJECTS - Documents\19-055
Page 5
SYSTEM OPTIONS 4/09/2020
SYSTEM OPTIONS
Transformer : LOIMP
Source Voltage : 250 V
Nominal Voltage : 240 V
Default POA : 0.50
CF Set A : 2.00
CF Set B : 2.00
Load Data Entered As : 1 Phase
Unbalance Factor : 1.00
Analysis Method: Standard
Study Title : New Study
Load Details
No. Code : Name Mean Std. Dev P.F Description
(kVA) Ratio
1 T01 : 3.0 (2 or 3 Bedroom) 3.00 0.500 0.97 Retirement Village Units,Cluster
Housing,Duplex
Units,Relocatable,Units/Townhouses
2 T02 : 4.0 (3 or 4 Bedroom) 4.00 0.500 0.97 Middle/Upper Income Housing, High
rise residential (Majority of new
estates)
3 T03 : 7.0 (Large prestige and 7.00 0.500 0.97 Prestige Housing/ Units/ Townhouses
cluster developments)
4 T04 : 10.0 (C&I) 10.00 0.500 0.80 Commercial & Industrial
LVDrop Version 8.0.3
New Study Drawn Date 4/09/2020
Peter Eustace & Associates Checked Time 11:52 AM
Peter Eustace & Associates Approved Page 2 of 2
C:\Users\aaronp\Peter Eustace & Associates\2019 PROJECTS - Documents\19-055