Figure 3-3 Post-Development Split Catchment Plan
3.4.2 Characteristics of Detention System
Table 3-6 contains the dimensions and outlet configurations of the modelled detention system.
Table 3-6 Modelled Detention System
Detention Dimensions Outlet Configuration
A1_Rainwater tank - 2 x 3 kL = 6 kL - 80 mm diameter orifice at tank invert
- 0.98 m height - 4x300mm diameter pipes at 0.9m above the tank
invert to cater for surcharging from the tank when
full.
A_Rainwater tank - 5 x 3 kL = 15 - 100 mm diameter orifice at tank invert.
kL - 10x300mm diameter pipes at 0.89m above the
- 0.98 m height tank invert to cater for surcharging from the tank
when full.
Underground - 120 m2 - 50mm diameter orifice at tank invert.
detention tank - 0.5 m height - 4.0 m weir at 0.46m above the tank invert.
- 60 m 3
(a grate would also be provided in the car park to
allow for surcharging in extreme events).
With reference to the above table, it is noted that although Catchment A drains to the bioretention
basin, no detention is considered to occur within the basin.
R.30199.001.03_SMP.docx | 12
162