6 RECOMMENDATIONS – BUILDING SHELL AND EXTERNAL GLAZING
Impact from shopping center and loading dock areas have been addressed in a previous noise impact
assessment report (ref: 20191414.3/0607A/R7/OB), dated 6 July 2021). The recommendations in this report
are based on the assumption that the Shopping center achieves compliance as per Mediation Judgement.
Further, AL has been advised by Stockwell that loading dock impacts will be treated utilizing Acoustic Barriers
and operational controls measures as listed in the abovementioned report.
6.1 GLAZING
The glazing systems should be selected and installed to meet the noise criteria presented in this report.
Minimum requirements are presented to satisfy only the acoustic requirements for the façade and glazing
based on the current assessment methods. Where other requirements for the façade and glazing are
specified elsewhere in the glazing specification, the glazing shall be selected to meet all requirements and
may result in increased glass thicknesses over those specified in the acoustic specification but shall in no
cases fall below the minimum thicknesses and requirements set out in this specification.
The design of the window mullions, perimeter seals of openable and fixed glazing, and the installation of
the windows/doors in the building openings shall be selected so that the completed system reduces internal
noise levels to at or below the requirements in the abovementioned report and in any case shall meet or
exceed the minimum acceptable glazing requirements nominated below.
Thicker glazing may be required for structural, safety or other purposes. Where required to use thicker
glazing than that scheduled, this will also be acoustically acceptable.
It is recommended that only window systems having test results indicating compliance with the required
ratings obtained in a certified laboratory be used. The submitted glazing system acoustic performance and
thickness deviations from the requirements in this brief are to be approved by the acoustic consultant.
Refer to Appendix A for Glazing types. It is noted that the Type B has been applied for the Shopping
Centre side due to the likelihood of having limited acoustic treatments applied at the source (i.e. Noosa Civic
Plant). On the condition that the acoustic treatments in section 8 are fully implemented to achieve
compliance with the Mediation Judgement No. 765 of 2020 (dated 3 September 2020), the Type B
glazing facing the shopping centre) can be downgraded to Type C glazing systems with acoustic seals.
Table 11 – Minimum Installed Glazing Requirements
Minimum Acoustic
Examples of Typical Minimum
Glazing Performance (all must be
Glazing Thickness
complied with)
Refer to following Table
And
Type A 10.38mm thick laminated glass
Type A minimum acoustic
performance: Rw35
And
Type B minimum acoustic
performance: Rw32
Type B 6.38mm thick laminated glass
And
I:\Jobs\2021\20210208\20210208.3\20210816JJMA_R3_Development_Application_.docx 26
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Appendix L - Acoustic Report.pdfRelated documentApplication case desk ↗
About this file
- File size
- 6.1 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.