                                                    Foundation Design Report
                     Date :            2nd November 2018
      Project Job Number :             ES 173527 Amended 11/09/2019
             Site Address :            Lot 497 10 HILL STREET SUNSHINE BEACH 4567
          Local Authority :            SUNSHINE COAST REGIONAL COUNCIL
          SP/ RP Number :              RP 48112
The following client supplied information had been made avaliable to STA Consulting for the purpose of the soil test and foundation design :-

Property description and site address                            YES           Evidence to ensure site is correct                                               YES      2.0 Results of the Supplied Soil Test Report
The contours of the site                                         YES           The location of trees on the site and adjoining sites                            YES
Location and identification of existing overland flows                         The footprint of the proposed dwelling and platform levels                       YES      2.01 Site Classification
Location of proposed cut and fill line                           YES           All relevant land searches
                                                                                                                                                                         The following foundation design recommendations given have been determined based on the results of the supplied soil test report commissioned by others :-
                     STA Consulting Engineers have completed a review of all avaliable information as supplied at the time or writing this report.
1.0 Design Requirements and Specifications
1.01 Supplied Construction Details

                   Proposed Building Design Details                                                        Proposed Site Preparation Details
                        (supplied by our client)                                                                (stipulated by our client)
                        Double Storey Duplex                                                                 Removal of Existing Dwelling                                                                                                   This site has been classified:
                               Cladding                                                                                 Cut / Fill
                          Sheet Metal Roof                                                                 Compaction of Disturbed Ground                                                                                                            Class P/S
                       Concrete Ground Floor
                                                                                                                                                                                                                                              Refer Soil Test Report
1.02 Site preparation
                                                                                                                                                                                                                                                         By
The construction pad is to be cleared of vegetation and loose material. Organic material, highly reactive clays and large rocks are not suitable for use as fill. Fill
is to be spread in 150mm deep layers and extensively track-rolled with a drott. Where trees are removed from the building area, the voids created by their                                                                                 Core Consultants Pty Ltd
removal must be excavated, back filled and compacted with suitable material. All fill must be placed in a controlled manner. Any fill should be placed to a dry
density ratio of 95% Standard AS 1289.5.1.1 for cohesive materials, or a density index of no less than 70% relative to AS 1289 5.5.1 for non-cohesive
                                                                                                                                                                                                                                         Job No. J000594-001-R-Rev0
materials. All earthworks are to be undertaken in accordance with AS3798.

1.03 Edge Beam and Slab

                                                                                   Founding Material                            Embedment Depth
                                         Edge Beam and Slab :             Natural Medium Dense Sand                                   200 mm

    Where the depth to suitable founding material is significant, excavated or drilled piers can be adopted. Where the length of drilled footing piers exceeds           Note - This report can only be relied upon if accompanied by a complete copy of the soil test report undertaken by Core Consultants Pty Ltd and cannot be
    1500 mm, they are to be reinforced with 4/N12 bars tied to an R6 spiral @ 150 mm pitch or equivalent & tied into the Edge Beam Footing cage.                         used on its own.STA Consulting Engineers accepts no responsibility for the results of the field investigation undertaken and site classification g iven for the site
    Alternatively an equivalent pre-fabricated steel cage may be adopted.                                                                                                outlined within this report.

1.05 Masonry Articulation                                                                                                                                                Where any proposed or existing trees fall within the zone of influence of the proposed structure, root barriers are to be installed unless it is shown that the
                                                                                                                                                                         supplied soil test and nominated site classification as reported by Core Consultants Pty Ltd has taken into consideration the effects of trees.
    For all articulated masonry veneer and articulated full masonry, articulation joints (full height - footings to eaves) are to be placed at no more than 10 metre
    spacings (maximum) and shall comply with the requirements of Technical Note 61 (TN61) Articulated Walling August 2008 published by the Cement
    Concrete & Aggregates Australia. Website :- http://www.concrete.net.au/index.php




                                         STA CONSULTING ENGINEERS                                                                                                            Client                                                                              Site Address
                                      Brisbane North (Milton) (07) 3071 7444 Brisbane South (Rocklea) (07) 3071 7444 Gold Coast (07) 5522 1995 Mackay (07) 4960 4800         DJK Electrical Services                                                             Lot 497 10 HILL STREET SUNSHINE BEACH
                                                               Townsville (07) 4766 8741 Rockhampton (07) 4994 9810 Newcastle (02) 4032 6450                                                                                                                                                                                  Page 1 of 14
                                                                    email: [email protected] webpage: www.staconsulting.com.au                                   TBA SUNSHINE BEACH 4567                                                             4567
                                                                                                                                                                                                                                                              STDCON 2014 14 05
Full text of the other 13 pages

Page 2

                                                                                                                                                                                                                                                                                                                                                                           Project Job No. 173527
                                                                                                                                                                           (Not to Scale)                                                                                           Proposed Pool Piering Detail                                                              Legend :- S8
   Issue                 Issue Description                        Date
                                                                                                                                                                                         Starter                                                                                                                                                                Symbols         Descriptions
     A           Original Soil Test & Foundation Design         02/11/2018                                                                                                               Bars

                                                                                                                                                                                                                                                                                                                                                          'h'                 - Edge Beam Footing
                 Added Blocked Up Footing                                                                                                                                                      2 Extra                                                                                                                                                                          'd' = 400 mm
                                                                                                                                                          Slab
     B           Added Freestanding Block Wall                  10/07/2019                                                                                                                     N12 Bars                                                                                                                                                   'd'
                                                                                                                                                          Thickening                                                                                                                                                                                                            'w' = 300 mm
                 Amended Pool Layout                                                                                                                                                                                                                                                                                                                                            'h' = 300 mm
                                                                                                                                                                                                                                                                                                                                                                   'w'
     C                                                          11/09/2019                                                                                         Thickening
                Amended Pool Layout and Retaining Walls                                                                                                                                            Edge Beam
                                                                                                                                                                   Reinforcement
                                                                                                                                                                                                   Footing                                                                                                                                                                    - Edge Beam Reinforcement
                                                                                                                                                                         Edge Beam                                                                   Piers to be 300mm                                                                                                          3L12 TM
EARTHWORK DESIGN PARAMETERS                                                                                                                                                                                                                                                                                               Proposed
                                                                Note: It is the builders responsibility to                                                               Reinforcement                                                               Below the Invert
                                                                                                                                                                                                                                                     of the Pool                                                            Pool
 Nominated Site Works :               Cut / Fill                ensure the proposed retaining wall is not
                                                                undermined or disturbed during construction.                                                         2 extra N12 Starter Bars                                                                                                                                                                                 - Slab Thickening Beam
                                                                                                                                                                                                                                                                                                                                                          'd'                   'd' = 300 mm
 Platform Height :-               40.500 m AHD                                                                                                                     at Thickening - Edge Beam
                                                                                                                                                                                                                                     Freestanding Block Wall                                                                                                         'w'        'w' = 300 mm
                                                                                                                                                                         Intersections
 Additional Site CUT :-               0.500 m                                                                                                                                                               Boundary Line            Refer Details on Page 5                                                                                                                  - Slab Thickening Beam
                                                                   1.0 m                                        Existing Retaining Wall
                                                                                                                                                                                                                                                                                                                                                                                Reinforcement 3L12TM
 Additional Site FILL :-              1.000 m
                                                                                                                                                Cut Fill
                                                                                                                                                                                                                                                                                        300
Note : Final platform heights must be in accordance                                                                                                                                                                                                                                     Min                                                                                   - Slab Thickening
with the approved architectural drawings. Where heights/                                                                                                                                                                                                                                                                                                                        Location
levels nominated above differ to the approved architectural
                                                                                                                                                                                                                                2.5 m




                                                                                                                                                                                                                                             0.5 m
                                                                                                                                                                                                                                                                                                                                                                              - Slab Thickening required
drawings, STA Consulting must be notified for review prior to                                                                                                                                                                                                                                                      m
                                                                                                                                                                                                                                                                                                               0                                                                under Load Bearing Wall
any works.                                                                                           Patio                                                                                                                                                                                                . 00




                                                                                                                                                                                                                                                     3.344 m
                                                                                                                                                                                                                                                                                                      1
DESIGN PARAMETERS                                                                                                                                                                                                                                                                                                                                                             - 350 Dia. Edge Beam
                                                                                                     Slab
                                                                                                                                                                                                                                                                                                                                                                                Footing Piers




                                                                                                                                                                                                                                                                                                                                          Boundary Line
 Design Slab Length :-               19.540 m
                                                                                                                                                                                                                                                                                                      Piers to be founded 300mm
Note : It is the builders responsibility to                                                                                                                                                                                                                                                           below the invert level of                                               - 350 Dia. Slab Piers
accurately locate and mark the position                                                                                                                                                                                                                                                               the existing service lines




                                                                                                                                                                                                                                                               (As per Structural Design)
of the existing service lines prior to any
excavation.




                                                                                                                                                                                                                                                                    Swimming Pool
                                                                                                                                                                                                                                                                                                                                                                              - SL 82 Slab Mesh
Where conditions on site differ from                                                                                                                                                                                        Patio
those indicated in this report, STA                                                                                                                                                                                         Slab
Consulting Engineers is to be notified                                                                                                                                                                         Step                                                                                                                                                           - Re-Entry Steel
                                                                                                                                                                                                                                                                                                                                                                                3L12TM, 2.0m long
prior to construction.
The foundations have been designed                                                                                                                                                                                                                                                                                                                                            - Re-Entry Steel
                                                                                                                                                                                                                                                                                                                                                                                SL82 Mesh
to place no additional surcharge on
                                                                                                                                                                                                                                                                                                                                                                                6 Wires, 2.0 m long
the existing service lines.
                                                                                                                                                                                                                                                                                                              Proposed 300 series Blockwall
STA Consulting Engineers takes no                                                                                                                                                                                                                                                                                                                                             - Column Locations
                                                                                                                                                                                                                                                                                                                 (Refer Structural Design)
responsibility for the accuracy of the




                                                                                                                                                                                                                                                               (As per Structural Design)
supplied as-constructed information.
                                                                                                                                                                                                                                                                                                                                                                              - 450 x 450 Pad Footings




                                                                                                                                                                                                                                                                                                                             Sewer Line
                                                                                                                                                                                                                                                                    Swimming Pool
 10m
                                                                                                                                                                                                                                                                                                                                                                              - 450 Diameter Isolated
                                                                                                                                                                                                               Step                                                                                                                                                             Pad Footings
                                                                                                                                                                                                                             Patio
                                                                                                                                                                                                                             Slab
                                                                                                                                                                                                                                                                                                                        Articulation recommended here
                                                                                                                                                                                                                                                                                                                        to create separation between
                                                                                                                                                                                                                                                                                                                        pool shell and block wall
                                           Footings As Per
                                             Edge Beam
                                                                                                     Patio
                                                                                                                                                                                                                                                                                                              7.664 m
                                                                                                     Slab

                                                                                                                Existing Dwelling to be Removed

                                                                                                                                                              Cut Fill
                                                                                                                                                                                                          Edge Beam
                                                                                                                                                                                                                                2.5 m
                                                                                                                                                                                 Footings




                                                                                                                                                                                                                                                                                            3.344 m
   5m
                                                   1.0 m                                                                                               Estimated Cut / Fill Line
    4m                                                                                                                                                       Existing Retaining Wall                                                                                                                                                                      Retaining Wall Piering Detail
                                                                                                                                                                                                                                    Boundary Line

    3m                                     Piers to be founded 300mm                                                                                                                                                                       Piers to be founded 300mm
                                           below the zone of influence                                                                                                                                                                     below the invert level of
                                           of the existing retaining wall                                                                                                                                                                  the proposed pool.
    2m
                                                                                                                                                                                                                                                                                                                         Drilled Piers to extend                                               Retaining
                                                                                                                                                                                                                                                                                                                         300 mm below invert level
    1m                                                                                                                                                                                                                                                                                                                                                                                         Wall
                                                                                                                                                                                                                                                                                                                         of existing/ proposed Retaining
                                                                                                                                                                                                                                                                                                                         Walls.

                                                                                                                                                                                                                                                                                                                                                            300
                  1m       2m        3m       4m                                                                                                                                                                                                                                                                                                            Min
                                                       5m                                           10m


                                           STA CONSULTING ENGINEERS
                                        Brisbane North (Milton) (07) 3071 7444 Brisbane South (Rocklea) (07) 3071 7444 Gold Coast (07) 5522 1995 Mackay (07) 4960 4800
                                                                                                                                                                                               Client
                                                                                                                                                                                               DJK Electrical Services
                                                                                                                                                                                                                                                                                                               Site Address
                                                                                                                                                                                                                                                                                                               Lot 497 10 HILL STREET SUNSHINE BEACH
                                                                 Townsville (07) 4766 8741 Rockhampton (07) 4994 9810 Newcastle (02) 4032 6450                                                 TBA SUNSHINE BEACH 4567                                                                                         4567                                                                       Page 2 of 14
                                                                      email: [email protected] webpage: www.staconsulting.com.au

Page 3

                                                                                                                                                                                                                                                                                                                                        Project Job No. 173527




                              Edge Beam Footing Detail                                                             Slab Thickening Detail                                                               Step Down Details                                                          Step Down Details
                                       (Brick Veneer)                                                                                                                                                         (100 mm Maximum)                                                           (350 mm Maximum)



                                                                                                                                            Slab Mesh                                                                200 Min
                                           300                                                                                                                                                                                                                                                       200 Min
                                                                            Slab Mesh                                                                                        100                  Slab Mesh            Lap           100 Max                                 Slab Mesh                Lap

                                                                                                  100
                                                                                                                                                                             200
                    Starter                                                                                   Compacted Fill                                                                                                                                                                                                   350
         300                                                                                                                                                                                                                                            100
                    Bar                                                                           200                                                                                                                                                                                                                          Max
                                                         Compacted Fill
       G.L                                                                                                                                           Trench Mesh
                                                                                                                                                                                                                                                                                                                                                  100
                               150                                                  Bedding Sand                                      300
                                                              Vapour Barrier as      50 mm Min.
        400                     100                300                                                                                                                                                                                                                                                                                            200
                                                              per AS 2870



                                                     Trench Mesh                                                                                                                                                                                                                                               300
                    40

                                 300



          Drilled Pier
          where required
                                                          Edge Beam Footing Detail
                                                                    (External Clad Finish)                                                                                                                                                                                          Internal Footing Detail
                                 350                                                                                                        Typical Load Bearing Wall Detail
                                                                                                                                            Note : Slab thickening to be placed under or within                                                                                                300             300
                                                                                                                                                   1.0 m of load bearing wall                                 Load Bearing                                     Party Wall &
                                                                          300                                                                                                                                                                                                                                                            Slab Mesh
                                                                                                                                                                                                              Wall                                             Starter Bars by others
                                                                                                Slab Mesh                                                                   < = 1000


                                                                                                                                                                                                                                                                                                                          300
                                        300    Starter                                                                                                                                                             Slab Mesh                                    Compacted Fill                                                  Compacted Fill
                                               Bar                                                                                                                                                                                                                         G.L                                                 G.L
                                                                                         Compacted Fill
                                G.L                                                                                            100                                                                                                                                                       *Starter
                                                                                                                                                                                                                                                   Bedding Sand                                                                      Vapour Barrier as
                                                                                                                                                                                                                                                                                          Bar
                                                                            Vapour Barrier as      Bedding Sand                                                                                                                                                                                                                      per AS 2870
                                                                                                                               200                                                                                                                                                 400
                                                                            per AS 2870             50 mm Min.                                                                               Compacted Fill
                                        400                  100                                                                                                                                                                        * One starter bar per location with the
                                                                                                                                                                                                                                          next being in opposite direction
                                              40                                                                                                                              Trench Mesh
                                                                                                                                                                300                                                                                                                                              Trench Mesh
                                                                           Trench Mesh
                                                                                                                                                                                                                                                                                                      300
                                                              300




        Notes :-                                                                                          Design Specification Table :                                                                                                                               Concrete Strength Table :
        1. Bar Chairs are to be placed at 800 centres Maximum.
        2. Slab Mesh to have 25 mm Top Cover.                                                               Steel Reinforcement                                                    Product Code                              Steel Strength                                  Elements                Concrete Strength               Slump
                                                                                                                                                                                                                                                                                                         F'c MPa                     (mm)
        3. Slab Mesh to have 35 mm Edge Cover.
                                                                                                            Slab Fabric                                                        SL82                                            500 Grade
        4. Trench Mesh to have 40 mm Bottom Cover.                                                                                                                                                                                                                    Bored/ Drilled Piers                     20                    80 - 100
        5. Reinforcement bars to have 40 mm Cover (around entire bar).                                      Edge Beam & Thickening Reinforcement                               3 L12 TM                                        500 Grade                              Strip Footing                            20                    80 - 100
        6. Slab Edge and Internal ribs MUST be vibrated.
                                                                                                            Starter Bars                                                       N12 [email protected] m c/c                             500 Grade                              Slab On Ground
                                                                                                                                                                                                                                                                                                               20                    80 - 100
                                                                                                                                                                                                                                                                      Garage/ External
                                                                                                                                                                                   Slab Thickness                              100 mm                                 Slab On Ground
                                                                                                                                                                                                                                                                                                               20                    80 - 100
                                                                                                                                                                                                                                                                      Internal


Design Code : S8-27.6.2013


                                         STA CONSULTING ENGINEERS
                                      Brisbane North (Milton) (07) 3071 7444 Brisbane South (Rocklea) (07) 3071 7444 Gold Coast (07) 5522 1995 Mackay (07) 4960 4800
                                                                                                                                                                                           Client
                                                                                                                                                                                           DJK Electrical Services
                                                                                                                                                                                                                                                                                     Site Address
                                                                                                                                                                                                                                                                                     Lot 497 10 HILL STREET SUNSHINE BEACH 4567
                                                               Townsville (07) 4766 8741 Rockhampton (07) 4994 9810 Newcastle (02) 4032 6450                                               TBA SUNSHINE BEACH 4567
                                                                                                                                                                                                                                                                                  STDCON.2014-14-05                                                      Page 3 of 14
                                                                    email: [email protected] webpage: www.staconsulting.com.au

Page 4

                                                                                                                                                                                                                                                                                                            Project Job No. 173527



                                         Typical Slab Edge                                                      Edge Beam to Patio
              Post type indicative       Thickening Detail                                                      Connection Detail
              Only

                Post                                                                           Step                               300
                                                                        Slab Mesh as

        Stirrup &Fixing
                                                                        per main slab                                                                          Slab Mesh                                                                        Blocked-up Footing Detail
                                                                        25 mm top cover
        by others                      Patio Slab poured with                                                                                                                                                                                          (200 Series Blockwork)
                                       the main slab area                                                                                                                             As per
                                                                                                                                                                                      Main Slab
      200                                                                        100
                                                                                                                                              Compacted Fill                                                                                              500
      min.                                                                                                                                                                                                                   Form up Edge or
                                                                                                                                                                                                                                                                                Slab Fabric
                                                                                                                                                                                                                             Knock out Blocks
                                                                                                                                         Lap slab mesh
                                                                                                                       100               300 min.
 As per                                                                                                                                                          Vapour Barrier as   As per                                        200                                                        Slab As Per
              Starter                                                           Bedding Sand
 Edge Beam                                                                                                                                                       per AS 2870         Edge Beam                                     Min                                                        X-Section
              Bar                                                                50 mm Min.


                                                                                                                                          Trench Mesh

                           300                                    Strip Footing as per                                  300                                                                                                          30 Cover
                                                                  edge beam                                                                                                                                               1600
                                                                                                                                                                                                                          Max

     Drilled Pier                                                                                 Drilled Pier                                                                                                                                                  Reinforcement Bars (refer table below)
     (where required)                                                                             (where required)                                                                                                                                              Min. 300 mm embedment into footing

                                                                                                                                                                                                                                                                  Wall Height       Reinforcement
                                                                                                                                                                                                                                                                    0 - 600       N12's @ 1000 mm c/c
                           350                                                                                          350
                                                                Patio Option A                                                                                                                                                                                     600 - 1600     N12's @ 400 mm c/c




                                                                                                                                                                                                                                                                Reinforcement Bars
                                                                                                                                                                                                                             600                                500 Min Embedment
                                                                                                                                                                                                                                     400


                                        Typical Slab Edge                                                       Edge Beam to Patio
                                        Thickening Detail                                                       Connection Detail                                                                                                                               3L12TM Top & Bottom
        Post type indicative                                                                                                                                                                                                                                    R6 Ligatures at 900 Centres
        Only                                                                                      Ableflex or                                                                                                                 40 Cover
                                                                     Slab Mesh as
                                                                                                  similar                                                                                                                                        300
                                                                     per main slab                                               300
              Post                                                                         Step
                                                                     25 mm top cover
                                                                                                                                                               Slab Mesh                                                                                              Notes:
      Stirrup &Fixing
      by others                      Patio Slab poured seperate                                                                                                                                                     Drilled Piers
                                                                                                                                                                                                                    Where Required                                    - Retaining wall footings to be founded to the
                                     to the main slab area                                                                                                                           As per
                                                                                                                                                                                                                                                                        recommended founding material as per page
                                                                                100                                                                                                  Main Slab
     200                                                                                                                                      Compacted Fill
                                                                                                                                                                                                                                                                        1 of the report.
     min.
                                                                                                                                                                                                                                                                      - All excavations to be finished cleaned and
                                                                                                                                        Lap slab mesh                                                                                            350                    horizontal.
As per                                                                                                                                  300 min.                Vapour Barrier as
                                                                              Bedding Sand                                                                                            As per
Edge Beam     Starter                                                          50 mm Min.                                                                       per AS 2870                                                                                           - The retaining wall is not to be backfilled for
                                                                                                                                                                                      Edge Beam                                                                         a minimum of 1 week after concrete core filling.
              Bar
                                                                                                                                                                                                                                                                      - All cores to be infilled with concrete grout -
                                                                                                                                         Trench Mesh                                                                                                                    18MPa minimum.

                          300                                Strip Footing as per                                      300                                                                                                                                            - No surcharge is to be placed onto the wall
                                                             edge beam                                                                                                                                                                                                  during backfilling.


   Drilled Pier                                                                                   Drilled Pier
   (where required)                                                                               (where required)



                          350                                                                                          350


                                                                   Patio Option B




                                         STA CONSULTING ENGINEERS
                                      Brisbane North (Milton) (07) 3071 7444 Brisbane South (Rocklea) (07) 3071 7444 Gold Coast (07) 5522 1995 Mackay (07) 4960 4800
                                                                                                                                                                                          Client
                                                                                                                                                                                          DJK Electrical Services
                                                                                                                                                                                                                                                           Site Address
                                                                                                                                                                                                                                                           Lot 497 10 HILL STREET SUNSHINE BEACH 4567
                                                               Townsville (07) 4766 8741 Rockhampton (07) 4994 9810 Newcastle (02) 4032 6450                                              TBA SUNSHINE BEACH 4567
                                                                                                                                                                                                                                                           STDCON.2014-14-05                                             Page 4 of 14
                                                                    email: [email protected] webpage: www.staconsulting.com.au

Page 5

                                                                                                                                                                                                                                                                                                       Project Job No. 173527


                                                                                                                                         Freestanding Retaining Wall
                                                                                                                                               (200 Series Blockwork)


                                                                                                                                                                                                    Landscaping to prevent                    Spoon drain to
                                                                                                                                                                                                           surface erosion                suitable discharge

                                                                                                                                                                                                                               Compacted Low
                                                                                                                                                                                                                                                                   N12 in the Top course
                                                                                                                                                                                                                             Permeability Layer
                                                                                                                                                                                                                                                                   Below Top Block Line
                                                                                                                                                 Spoon drain to
                                                                                                              Landscaping to prevent         suitable discharge
                                                                                                                     surface erosion                                                                                   200mm
                                                                                                                                    Compacted Low
                                                                                                                                  Permeability Layer
                                                                                                                                                          N12 Bars at 1000 Centres


                                                                                                                           200mm
                                                                                                                                                                                                    Granular Non-Compressible
                                                                                                                                                                                                       Free - Draining Back Fill.
 Notes:                                                                                                              Geotextile                30 Cover
                                                                                                                                                                             600
                                                                                                                                                                             Max
- Retaining wall footings to be founded to the                                                        Granular Non-Compressible
                                                                                                         Free - Draining Back Fill.                                                                                 Geotextile
  recommended founding material as per page
                                                                                                                                                                                                                                                                                      1600
  1 of the report.
                                                                                                                           A.G. Drain to                                                                        Reinforcement Bars as                                                 Max
                                                                                                                                                                                     FSL
                                                                                                                       Efficient Outflow                                                                              per Table Below
- All excavations to be finished cleaned and
  horizontal.
                                                                                                                                                                                                                                                               30 Cover
- The retaining wall is not to be backfilled for                                                                       Reinforcement Bars
  a minimum of 1 week after concrete core filling.                                                                    500 Min Embedment                                      600
                                                                                                                                                                       400
- All cores to be infilled with concrete grout -
  18MPa minimum.                                                                                                                                                                                                          Clean Out Block

                                                                                                                  3L12TM Top & Bottom                                                                                     A.G. Drain to
                                                                                                             R6 Ligatures at 900 Centres                                                                              Efficient Outflow                                              FSL
                                                                                                                                                                        40 Cover
                                                                                                                                                          300

                                                                                                                                   WALLS up to 0.6m HIGH
                                                                                                                                                                                                                    Reinforcement Bars
       Step < 200mm                                                                                                                                                                                                500 Min Embedment                                                 600
                                                                                                                                                                                                                                                                          400

                                Beam
                      Footing
      D
                             1:10
                   Slope <                                                                                                                                                                                        3L12TM Top & Bottom
                                                                                                                                                                                                             R6 Ligatures at 900 Centres                                  40 Cover



Step > 200mm
but < 2D                                                                                               Retaining Wall Specifications
                                                                                                         Wall Height      Min Pier Depth               Reinforcement                                                                                                                 Drilled Piers Refer
 D    Footing Beam                                                                                                                                                                                                                                                                   to Table for Depth
                                                                                                           0 - 600                N/A            N12 Bars at 1000 Centres                                    450 Diameter Piers at 2.0m
                        1.5D                                                                                 800                  200                                                                      Centres, Reinforced with 4N12
                                                                                                                                                  N12 Bars at 400 Centres                          Bars with R6 Ligatures at 600 Centres.
                                                                                                            1000                  400
                                                                                                                                                   Horizontal and Vertical
     Stepping Strip Footing                                                                                 1200                  600

                                                                                                            1400                  800             N16 Bars at 400 Centres
                                                                                                            1600                  1000             Horizontal and Vertical

                                                                                                                                                                                                                                                        300
                                                                                                       Note* Footing & wall Cavity must be vibrated.
                                                                                                       * Trench Mesh and steel reinforcement must have a minimum 500mm lap.                                                                             450
                                                                                                       * All bottom steel must have 40mm bottom cover.

                                                                                                                                                                                                                       WALLS OVER 0.6m and up to 1.6m HIGH




                      STA CONSULTING ENGINEERS
                   Brisbane North (Milton) (07) 3071 7444 Brisbane South (Rocklea) (07) 3071 7444 Gold Coast (07) 5522 1995 Mackay (07) 4960 4800
                                                                                                                                                                         Client
                                                                                                                                                                         DJK Electrical Services
                                                                                                                                                                                                                                                     Site Address
                                                                                                                                                                                                                                                     Lot 497 10 HILL STREET SUNSHINE BEACH 4567
                                            Townsville (07) 4766 8741 Rockhampton (07) 4994 9810 Newcastle (02) 4032 6450                                                TBA SUNSHINE BEACH 4567
                                                                                                                                                                                                                                                     STDCON.2014-14-05                                             Page 5 of 14
                                                 email: [email protected] webpage: www.staconsulting.com.au

Page 6

                                                                                                                                                                                                                                                            Project Job No. 173527


                                                                                                                                  TYPICAL DETAILS




                                    Stepped Footing Detail
                                                                                                                                                                                             Typical Slab Edge
                                                                          Step > 200         Extensions 300                                                                                  Thickening Detail
                                                                          but < 2 D          or 25 bar diameters
 Step < 200                                                                                                                                                                Slab Mesh as
                                                                                                                                                                           per main slab
                                                                                                                                                                           25 mm top cover
                                                                                                                                                                                                      Slab Thickness 100 mm


                                                                                                                                                                      300 40
                                                                                                         Extensions 300
                                                                                                                                                                                                    Compacted Fill
                             1:10                                                                        or 25 bar diameters
                     Slope <
                                                                    D
D                                                                                             1.5 D                                                                                              3L12 TM              Bedding Sand
                                                                                                                                                                                     300                               50 mm Min.




                                       N12 Corner Bars
               Corner Bars                                                                                                                                                       Wet Area Recess Details
                                                                                                                                                                                                                                          Slab Mesh
                                                                                                                                                                                                                                          25 mm top cover
                                                 Reinforcement                                                                                                                                 50 mm (Max)        100 mm (Min)
                                                                                                                                                                                                 Recess

500
                     Require a lap of 500 mm
                     around outside corners of
                     footing reinforcement                                                                                                                                500                    Option A                           500

                                                                          Corner Bars
                                                        500



                                                                                                                                                                                                                                          Slab Mesh
                                                                                                                                                                                                                                          25 mm top cover
                                                                                                                                                                                               50 mm (Max)           100 mm (Min)
                                                                                                                                                                                                 Recess
                                                                             Require a lap of 500 mm
                                                                             around outside corners of
                                                                             footing reinforcement

                                                                                                                                                                           500                     Option B                         500




                                                                 Reinforcement




         STA CONSULTING ENGINEERS
      Brisbane North (Milton) (07) 3071 7444 Brisbane South (Rocklea) (07) 3071 7444 Gold Coast (07) 5522 1995 Mackay (07) 4960 4800
                                                                                                                                            Client
                                                                                                                                            DJK Electrical Services
                                                                                                                                                                                                                Site Address
                                                                                                                                                                                                                Lot 497 10 HILL STREET SUNSHINE BEACH 4567
                               Townsville (07) 4766 8741 Rockhampton (07) 4994 9810 Newcastle (02) 4032 6450                                TBA SUNSHINE BEACH 4567
                                    email: [email protected] webpage: www.staconsulting.com.au                                                                                                   STDWAF.2014.14.05                                           Page 6 of 14

Page 7

                                                                                                                                                                                                                                                                                            Project Job No. 173527

                                                                                                                                                                                                         Technical Notes
                                                                                                                                           Earth Works Specifications
                                                                                                                                           Batter Angles for Embankments:-
                         Typical Edge Beam Piering Details                                                                                 It is the builders responsibility to ensure that the site works do not undermine or place additional surcharge on any existing structures.
                                                                                                                                           If this can not be achieved STA Consulting Engineers must be contacted prior to any site works being undertaken.
                                                                                                                                           Batter angles must comply with local government requirements and are to conform as follows (Figure 1).                                  'L'
                                                                                                                                                                                                                                                                                                              Line
                                                                                                                                            Figure 1.                                                                                                                                                  Ground
                                                                                                                                                                                                                                                                                               Natural


                                  Option A - Bored Piers                                                                                                                      Fill Embankment                                                                                                        'H'
                                                                                                                                                                                                         Fill
                              Edge Beam Footing
                                                                                                                                                                                                                                                         Cut
       Slab                   Reinforcement
                                                                                   Slab Mesh                                                                       'H'                                                                                                   Cut Embankment
       Edge
                                                                                                                                                                       Line     'L'
                                                                                                                                                                Ground
                                                                                                                                                        Natural                            Fill, H = less than 2.0m


  Edge Beam
                                                                                                                                                                                           Material Type          Stable                                                   Clay
                                                                                                                                                                                                                                   Sand           Silt                                       Soft Soils
  Footing
                                                        Drilled Pier                                                                                                                      (Refer Bore Logs)        Rock                                        Firm Clay     Soft Clay

                                                                                                                                                             Embankment Slopes             Compacted Fill             2:3           1:2           1:4              1:2       Not Suitable    Not Suitable
                                                                                                                                                               (Height Length)
Refer page 1
                                                                                                                                                                                               Cutting                8:1           2:3           1:4              1:1            2:3        Not Suitable
                                                  Suitable Founding Material
of this report
                                                                                                                                                           Note: Retaining walls or other forms of soil retaining methods must be adopted where the slope ratio is greater than that
                                   350 Min.                                                                                                                indicated in the table above
                                                                                  350 Min.
                                                                                                                                           Fill Material and Compaction:-
                                                                                                                                           Organic material, highly reactive clays and large rocks are not suitable for use as fill. The fill is to be spread in 150 mm layers and extensively
                                                        1500 Max                                                                           track rolled with a drott. All earthworks to be carried out in accordance with the full requirements of AS3798, Guidelines for Earthworks for
                                                                                                                                           Commercial and Residential Developments.
                                                          Section                                                                          NOTE - In the instances where by significant levels of filling are observed, there will always remain the posibility of tilt as a result of differential
                                                                                                                                           settlement in the fill. Australian Standard (AS2870-2011) does not cater for tilting of the slab as a result of differential settlement within certified fil
                                                                                                                                           nor does the Australian Standard address the possible occurrence when shallow foundations are adopted.
                                                                                                                                           Drainage:-
                                                                                                                                           The external finished surface surrounding the dwelling must be drained to move surface water away from the building and graded to give a slope
                                                                                                                                           of not less than 50 mm over the first 1 m away from the building.


                                                                                                                                           Reinforcement Specifications
                                                                                                                                           Steel wire reinforcing fabric and bars to conform with AS1304 - Hard Drawn Steel Wire Reinforcing
                                                                                                                                           Fabric for Concrete) and AS1302 - Steel Reinforceing Bars For Concrete.
                                      Option B - Bulk Piers                                                                                Lap Lengths
                                                                                                                                           Trench Mesh - 500 mm in a straight line, or to the far face at "T" and "L" intersections
                                                                                                                                           Steel Bars - "N" Bars - 35 times the bar diameter.
                                                                                                                                           Corner Bars - required at all "T" and "L" intersections. Refer to the design drawings for
                                                                Edge Beam Footing                                                          the appropriate construction details.
                      Slab Mesh                                 Reinforcement
                                                                                                 Slab                                      Slab Fabric - One full panel of the fabric, so as the two outer-most transverse wires of each sheet
                                                                                                 Edge                                      are overlapped. As shown on the below detail (Figure 2).

                                                                                                                                                                              Figure 2.                          Slab Fabric Lap Details
                                                                                                                                                                                                                            or
                                                                                                                                                                                            200 x 200 Squares                              200 x 100 Edge Square
                                                                                                Edge Beam
                                                                                                Footing
                                              Bulk Pier                                                                                    Note :- Where external beams are wider than 300 mm, an extra equivalent bottom reinforcement bar
                                                                                                                                           is required for each 100 mm additional width. For example, a 400 mm wide edge beam will require a
                                       Suitable Founding Material
                                                                                                 Refer page 1                              minimum of 4 bar trench mesh (300 mm wide).
                                                                                                 of this report

                         1.0 m Min.                                  1.0 m Min.                                                            Concrete Specifications
                                              2.5 m Max.                                                                                   The concrete must have a strength at 28 days of not less than 20MPa unless otherwise specified on the foundation cross section, a 20 mm nominal
                                                                                                                                           aggregate size and have a nominal 80 -100 mm slump. Water must not be added to the mix to increase the slump to a value in excess of that specified.
                                                   Section                                                                                 Concrete must be placed and compacted/vibrated with good building practice. In hot and windy conditions concrete must be cured by covering with
                                                                                                                                           plastic sheeting, spraying with a liquid membrane curing compound or ponding water on the top surface. The concrete must be manufactured to
                                                                                                                                           comply with AS3600 - Concrete Structures.


                                                                                                                                           Shallow Rock, Boulders & Rock Outcrops
                                                                                                                                           The depth of strip footings may be reduced where refusal on shallow rock, on a boulder or partially over a small rock outcrop is encountered.
                                                                                                                                           Where this is less than 400 mm, top steel, corner bars and starter bars may be deleted. However before the beam depth becomes less than
                                                                                                                                           400 mm, top steel is to be lapped 500 mm with the bottom steel. It is also required that a minimum edge beam depth of 200 mm be maintained
                                                                                                                                           at all times. It is also recommended that the external walls are articulated at the start and end of the rock outcrop.




           STA CONSULTING ENGINEERS
       Brisbane North (Milton) (07) 3071 7444 Brisbane South (Rocklea) (07) 3071 7444 Gold Coast (07) 5522 1995 Mackay (07) 4960 4800
                                                                                                                                        Client
                                                                                                                                        DJK Electrical Services
                                                                                                                                                                                                                                      Site Address
                                                                                                                                                                                                                                      Lot 497 10 HILL STREET SUNSHINE BEACH
                                Townsville (07) 4766 8741 Rockhampton (07) 4994 9810 Newcastle (02) 4032 6450                           TBA SUNSHINE BEACH 4567                                                                       4567
                                                                                                                                                                                                                                                                                                               Page 7 of 14
                                     email: [email protected] webpage: www.staconsulting.com.au
                                                                                                                                                                                                                                 STDCON 2014-14-05

Page 8

                                                                                                                                                                                                                                                                                                    Project Job No. 173527
                                                                                 Note : The final location of articulation joints may be revised on site at the discretion
    Legend                                                                       of the builder. The final location however MUST NOT exceed the maximum spacing
                                                                                 as nominated in section 1.05 of this report.
        N.A.J               Natural Articulation Joints
Note: Natural Articulation Joints (N.A.J) shown on plan at side of openings,
should be replaced with Articulation Joints where brickwork occurs above
opening. Natural Articulation Joints apply only to full height openings or
locations where a change in cladding material occurs

          A.J               Articulation Joints

                            Spoon Drain


                            Gully Pit


                            Grated Drain
                                                                                                                         Note: Gully pit to be confirmed on site

                            Root Barrier
                                                                                                                                                                                        Grade ground surface
                                                                                                                                                                                         for free drainage
                            Door




                                                                                                                               1 : 20 Fall
                                                                                                                                 (min)
                                                                                                                                                                                                               1 : 20 Fall
                            Window                                                                                                                                                                               (min)

Notes:
1. Root barriers will be required where nominated on the
STA Consulting Engineers drainage / articulation plan.
Root barriers may also be required if future tree planting




                                                                                                                                                                                                                                                                       (As per Structural Design)
is to be undertaken.




                                                                                                                                                                                                                                                                            Swimming Pool
2. STA Consulting Engineers recommends that an arborist or
a professional specialising in root barriers is consulted before
installation of root barriers with relation to location and depth.
3. Root barriers are to be made from impervious, durable
material that can withstand burial in soil for extended periods.
                                                                                      STREET




The depth of the root barrier is greatly dependent on the tree
                                                                                                             Driveway
species.
4. Root barriers are not to be installed any closer than 2m from




                                                                                                                                                                                                                                                                       (As per Structural Design)
the proposed dwelling foundations.




                                                                                                                                                                                                                                                                            Swimming Pool
5. STA Consulting Engineers takes no responsibility for existing
trees being damaged or destabilized by the installation of
root barriers.
6. The ground beneath suspended floors must be graded
so that the area beneath the building is above the adjacent
external finished ground level.
7. Pipe dimensions, gully pit sizes are to be in accordance
with AS 3500.5.2000
8. It is NOT recommended that garden beds be located
                                                                                                                                                                                                                                              1 : 20 Fall
against the foundations of the proposed dwelling.
                                                                                                                                                                                                                                                (min)
9. The maintenance of the building and site is the responsibility
of the home owner, therefore he or she should be familiar with                                                                                                                                                 Gully Pits directed to
these requirements                                                                                                                                                                                             a suitable outflow
10. This drainage plan is a guide only and local government
by-laws and regulations take precedence. Please consult a
plumbing contractor specialising in drainage if in doubt.                                                                                                                                                                               No water is to pond between pool & dwelling
STA Consulting Engineers can be contacted if more detailed
drainage plans are required.
11. Local Government by-laws and regulations may require
changes to these recommendations. When this is the case,
STA Consulting Engineers is to be contacted immediately
for an amendment.
12. It is the builders/ home owners responsibility to ensure the
drainage system is extended/ adapted where additional structures
such as sheds, patios, swimming pools etc... are incorporated
after the dwelling construction and in the long term.




                                          STA CONSULTING ENGINEERS
                                       Brisbane North (Milton) (07) 3071 7444 Brisbane South (Rocklea) (07) 3071 7444 Gold Coast (07) 5522 1995 Mackay (07) 4960 4800
                                                                                                                                                                             Client
                                                                                                                                                                             DJK Electrical Services
                                                                                                                                                                                                                                               Site Address
                                                                                                                                                                                                                                               Lot 497 10 HILL STREET SUNSHINE BEACH
                                                                Townsville (07) 4766 8741 Rockhampton (07) 4994 9810 Newcastle (02) 4032 6450                                TBA SUNSHINE BEACH 4567                                           4567
                                                                                                                                                                                                                                                                                                                Page 8 of 14
                                                                     email: [email protected] webpage: www.staconsulting.com.au
                                                                                                                                                                                                                                          STDCON 2014 14 05

Page 9

                                                                                                                                                                                                                                                                                                                                                                                                                    Project Job No. 173527
                                                                                                                                                    Root Barriers

                                    TREES AND FOUNDATIONS                                                                                                                                                         Existing Tree




                                                                                                                                                                 Possible Cracking/ Rotation
                                                                                                                                                                 in masonry walls


1. Introduction                                                                                                                                                                                                                              Cracking in
                                                                                                                                                                                                                                             brick work


                                                                                                                                                                                                                                                                                                                                                                                                                                  Dwelling
                                                                                                                                                                                                                                                                             Dwelling
The potential effect of trees on house foundations is now widely documented, however the following                                                                           G.L                                                                                                                                             G.L
is a brief overview on the impacts trees can cause along with some comment in regards to possible
measures in reducing or mitigating these effects.
                                                                                                                                                                                                                                                                                                 Depth determined
                                                                                                                                                                                                                                                                                                 by H's Zone
                                                                                                                                                                                                                                                                                                                                                                                                                   Root Barrier
Trees and large shrubs typically require substantial volumes of water/ moisture to survive, some more so
than others. Therefore when designing or constructing a new dwelling where trees are located within the
vicinity, an allowance for the potential drying effect from trees must be considered.
Whilst still a problem, the concern when designing foundations is not so much the roots of trees passing under
the slab and lifting as most people have seen on pathways etc.. Rather trees in the vicinity drawing on the
extra moisture under the slab area, that would typically remain at a balance where trees do not exist.                                                                                                                                                                                        Figure 2. Case A - Existing tree managed on property.
                                                                                                                                                     Figure 1. Case A - Unmanaged tree on property


With the trees absorbing this additional moisture, the potential for clays to shrink is exacerbated, thus
imposing further stresses on the foundations and the potential for damage where allowances have not
been made.

                                                                                                                                                                                                                                                                                                                                                                                                                     Existing Tree
                                                                                                                                                                                                                                                                 Existing Tree



2. Site Classification & Trees
                                                                                                                                                                                                                                                                                                                                                                                      Boundary Fence
                                                                                                                                                                                                                                       Boundary Fence

In accordance with AS2870-2011, where trees are within the vicinity of a proposed new construction, extension etc..
Trees must be considered when determining the site classification. This can be done in two ways :-                                                                                                                       Cracking in
                                                                                                                                                                                                                         brick work
                                                                                                                                                                                                                                                                                                                                                                                              Adjoining Property
                                                                                                                                                                                                                                            Adjoining Property

a) The site is to be classified as class P (Problem Site) per Section 2.1.3 (e) & (f                                                                                                                                                                                                                                                       Dwelling

   - the site may be subject to moisture changes due to site conditions more severe than normal conditions.                                                                                          Dwelling
                                                                                                                                                                                                                                                                                                     G.L
                                                                                                                                                                    G.L
   - the site may be subject to other factors resulting in foundation movement beyond the reactive soil movements
     resulting from moisture changes due to the normal site conditions.
                                                                                                                                                                                                                                                                                                                                      Depth determined
                                                                                                                                                                                                                                                                                                                                      by H's Zone
or

b) The site is to be classified based on the potential characteristic surface movement of the soils identified (Ys),                                                                                                                                                                                                                                                           Root Barrier
   however the (Yt), potential surface movement due to tree induced suction change is also to be calculated and                                      Figure 3. Case B - Unmanaged tree on neighbouring property                                                                               Figure 4. Case B - Management of tree on neighbouring property using root barriers.
   effectively added to the determined (Ys) value. This clearly increases the (Ys) value, potentially increasing the
   nominated site classification by one or two classes.




3. Designing Foundations in Vicinity of Trees                                                                                                                                                                                                                                             Existing
                                                                                                                                                                                                                                                                                          Dwelling                                            Vacant
                                                                                                                                                                                                                                                           Vacant


The approach for designing foundations where trees are influencing the site conditions can be done in a number
of ways, such as, but not limited to the following :-                                                                                                                                                                                                                                       Root
                                                                                                                                                                                                                                                                                            Barrier
    Remove problem trees - this is the most cost effective option, however does come with limitations. The main being
     time. If trees are to be removed for the sake of reducing the site classification and potential costs associated, it is
     required the site be left for up to a minimum of two full seasonal changes to allow the moisture content within the soil
     to stabilise as the trees are no longer drawing on the moisture, thus potentially creating a rebound effect.

    Design extensively heavier foundations. By doing this you are simply designing foundations to accommodate the exacerbated
     Shrinkage movement caused by trees within the vicinity of the construction. This method can be fairly costly.                                                                                                                                                                                                                          Vacant
                                                                                                                                                                                                                                                            Existing
                                                                                                                                                                                                                                                            Dwelling
    Install an appropriately designed and recognised root barrier system. This is to be installed to a set minimum depth, typically
     2.0 metres or more depending on the sites regional locality. The barrier system is to be positioned between the proposed/ existing
     dwelling and the influence trees. It is not uncommon for the barrier system to be installed on at least three sides per fig.4.
     The root barrier system is to be installed by an appropriately qualified person/s providing Compliance Certification in the way of
     a Form 15 (Compliance Certificate for Building Design or Specification) and Form 16 (Inspection Certificate). Where the contractor
     Cannot provide the nominated certificates, an alternative contractor should be commissioned.
     Examples of typical case scenarios using root barrier systems are shown in the attached figures.




                                                                                                                                                                                                                                                                                        Street




                              STA CONSULTING ENGINEERS
                           Brisbane North (Milton) (07) 3071 7444 Brisbane South (Rocklea) (07) 3071 7444 Gold Coast (07) 5522 1995 Mackay (07) 4960 4800
                                                                                                                                                                                               Client
                                                                                                                                                                                               DJK Electrical Services
                                                                                                                                                                                                                                                                                                                              Site Address
                                                                                                                                                                                                                                                                                                                              Lot 497 10 HILL STREET SUNSHINE BEACH 4567
                                                    Townsville (07) 4766 8741 Rockhampton (07) 4994 9810 Newcastle (02) 4032 6450                                                              TBA SUNSHINE BEACH 4567
                                                         email: [email protected] webpage: www.staconsulting.com.au                                                                                                                                                                                                                                                                                                              Page 9 of 14

Page 10

                                                                                                                                                                                                                                                                                                     Project Job No. 173527



                                                                                                                                Plumbing Guidelines
                                                                                                                  Edge Beam and Slab Thickening Pipe Penetrations


                                Edge Beam Footing                                                       Slab Thickening




                                                                                                                                                                                                                                           Slab Surface

                                                                                                                                                           Not Allowed                                                                             Slab Fabric
         Not Allowed                                                                                                                                                                     D/3            Not Allowed

                                                                                                                                                           Refer Detail
                                                         Pipe and Lagging                                                               Pipe and Lagging   Below
         Allowed                                                                                                                                                                                                                                                       D = Depth of Footing + Slab
                                                                                                                                                                                         D/3            Allowed                        Pipe and Lagging
         Providing Min Footing Depth
         Maintained Below Pipe
                                                             Nominated Footing         Reinforcement
                                                             Depth Must be
         Refer Detail                                        Maintained Below                                                                              Allowed                                      Refer Detail
                                                                                                                                                                                         D/3
         Below                                               Pipe                                                                                                                                       Below

                                                                                 Notes:                                                                                                                                                    Base of Footing
         Allowed                                                                 The edge beam or slab thickening reinforcement shall not                                                                   Allowed
                                                                                 be cut to allow for the placement of pipes. If the pipe is to
                                                                                 be located in this area the footing must be excavated
          Where the Pipe                                                         deeper to allow for the placement of the reinforcement.
          Passes Beneath
                                                             300 Min             The edge beam must not be jackhammered for the
          the Footing, Piers
                                                                                 placement of pipes.
          are to be Placed
                                                                                 When the pipe penetrates the footings or
          in this Area
                                                                                 slab thickenings within the lower 1/3 they
                                                                                 must be excavated deeper to maintain
                                                                                 the cover as specified.




                                                                                                                                                                                          Local Deepening of Edge Beam Footing or Slab Thickening
                             Edge Beam Footing                                              Slab Thickening


                                                                                                                                                                                                                                                Slab Mesh



                                                                                                                                                                                        Trench Mesh
                                                                                                                                                                                                                                                  40 mm Min Cover
                                                                                                                                                                                                        40 mm Min Cover
                                                                                                                                                 Nominated Depth

                                                                                                                       Pipe and Lagging
                                                                                                                          40 mm Min Cover                                                                       1000 mm                             1000 mm
                                                                                                                                                 Extra Depth
                                                                       Reinforcement
Nominated Footing                                                                                                         40 mm Min Cover
                                                                                                                                                                                                                        When the pipe penetrates the footings or
Depth                                                                                                                                                                                                                   slab thickenings within the lower 1/3 they
                                                       Pipe and Lagging                                                                                                                                                 must be excavated deeper to maintain
                                                                                   When the pipe penetrates the footings or
                                                                                                                                                                                                                        the cover as specified.
                                                         40 mm Min Cover           slab thickenings within the lower 1/3 they
Extra Depth                                                                        must be excavated deeper to maintain
                                                         40 mm Min Cover           the cover as specified.

                                       Reinforcement
                                                                                                                                                                                                    Service Line Location and Piering

                                                               Minimum Pipe Lagging




                                                                                                                                                                            The service trenches must not
                                                                                                                                                                            be located within the zone of             Zone of
                                                                T                                                                                                           influence of the footings.                Influence
                                                                                                                                                                            Alternately the edge beam
                                                         CLASS         LAGGING THICKNESS (T)                                                                                be piered below the zone of                              45 Degrees for Clay Soils
                                                                                                                                                                            influence of any services.                               30 Degrees for Sand Soils and Fill
                                                           S, M                        20
                                                                                                                                                                                                                 300 Min
                                                        H1, H2, E                      40




   STA CONSULTING ENGINEERS
Brisbane North (Milton) (07) 3071 7444 Brisbane South (Rocklea) (07) 3071 7444 Gold Coast (07) 5522 1995 Mackay (07) 4960 4800
                                                                                                                                                                   Client
                                                                                                                                                                   DJK Electrical Services
                                                                                                                                                                                                                                                                     Site Address
                                                                                                                                                                                                                                                                     Lot 497 10 HILL STREET SUNSHINE BEACH
                         Townsville (07) 4766 8741 Rockhampton (07) 4994 9810 Newcastle (02) 4032 6450                                                             TBA SUNSHINE BEACH 4567                                                                           4567
                                                                                                                                                                                                                                                                                                                 Page 10 of 14
                              email: [email protected] webpage: www.staconsulting.com.au
                                                                                                                                                                                                                                                             STDCON 2014-14-05

Page 11

                                                                                                                                                                                                                                                                                                                                 Project Job No. 173527


                                                                                                                             Plumbing Guidelines

            Detail 1. Scale: 1:25                                                                                                                                                  Detail 2.                                                                             Minimum Heights of Slabs Above

            Services Under Slab                                                                                                                                                    Services Under Slab                                                                   Ground for Habitable Rooms
                                                                                                                                                                                                                                                                         - 150 For High Side of Well Drained Sites

            Edge Beam                                                                                                                                                              Relief Gully                                                                          - 300 For Level, Poorly Drained Sites

                                                                                                                                                                                                                                         Stainless Steel Strap and Bolts Fixed
          All Slab                                                                                                                                                                                                                       to Reinforcing Steel. Only to be                               Lowest
          Penetrations to                                                                                                                                                          Termite Protection to AS 3660.1                       Used Where Fill Material Depth                                 Fixture
          be Sealed to                                                                                                                                                                                                                   Exceeds 900 mm Under Wet Areas.
                                                                                                                                                                                       Relief Gully Trap to be Min.
          AS 3660.1
                                                                                                                                                                                       150 Below Lowest Fixture
                                                                                                                                                                                       FLOOR LEVEL
                                                                                                        Fall




                                                                                                                                                                                                                (min)
                                                                                                                                                                                                                 50
                                                                                                      Min 1:20
                                                                                                 (50 mm over 1.0 m)
                                                                                                                                                                                  75

                                                                                                                                              Ground Level
                                                                                                                                              to be 75 Below
                                                                                                                                              Top of Gully Trap




                                                                                                                                                                                                                                                                                                                  (max)
                                                                                                                                                                                                                                                                                                                   600
Stainless Steel Strap
and Bolts Fixed to
Reinforcing Steel.                                                                                                                                 Drainage Channel Must
Only to be Used                                                                                                                                    be Wide Enough to Take All
Where Fill Material                                                                                                                                Water Without Flooding the                                                                                             Spacing For Straps:
                                                                                                                                                   Dwelling                                                                       Pier                                    For Pipes > Ø 100 mm Max Spacing 1200 mm Max
Exceeds 900mm Under
                                                                                                 Pier
Wet Areas.                                                                                                                                                                                                                                                                For Pipes <= Ø 100 mm Max Spacing 1000 mm Max

Spacing For Straps:
For Pipes > Ø 100 mm Max Spacing 1200 mm Max
For Pipes <= Ø 100 mm Max Spacing 1000 mm Max



                                                                                                                                          Strap Spacings
                                                                                                                                          Strapping of under slab pipework is required where uncompacted fill                                                          Detail 3.
    Underslab Plumbing                                                                                                                    has been identified or as a result of cut / filling operation in the
                                                                                                                                                                                                                                                                       Downpipe Articulation For
                                                                                                                                          construction of the building pad. Strapping is to be placed where the
    Plumbing, sewage and drainage services shall be located and installed so as to ensure:
    - The functioning of the footings and slabs on-ground are not impared.
                                                                                                                                          fill depth excededs 900mm.
                                                                                                                                           Uncompacted fill being material that is not natural ground or having had
                                                                                                                                                                                                                                                                       "M' Soil Classification
    - The functioning of the services themselves are not impared.
    Water pipes must not be laid horizontally in slabs, but may be placed vertically as a
                                                                                                                                           compaction as AS 3798 (Level One Supervision)
    penetration, as detailed above.                                                                                                        1. For main drains Ø >100 mm strapping to be placed at the head and
                                                                                                                                              then at 1200mm max. spacing.

    Notes:                                                                                                                                 2. For smaller pipework Ø <100 mm (eg sink & floor waste), Strapping
                                                                                                                                              to be placed at the head and then at 1000 mm max. spacing.
    1. All plumbing (within & beyond the footprint of the slab & footings) to be constructed                                               3. For pipework passing under the footing, place strapping as                                                                     90 mm
                                                                                                                                                                                                                                                                             Downpipe
    in accordance with AS3500 - National Plumbing & Drainage code.                                                                            close as practicable to the inside edge of the footing.
    2. All PVC pipe work passing horizontally through concrete must have 20 mm for 'H' or
                                                                                                                                           4. For pipework passing through the footing, place strapping at                                                               Slip Joint
    40 mm lagging for 'E' sites. Sleeves allowing equivalent movement may be used as an
                                                                                                                                              1200 max. from inside edge of the footing.                                                                                 Coupling
    alternative.
    3. Corrugated flexible PVC pipe should not be used for sanitary (sewer) pipes as it is not                                                                                                                                                                      100 (min)
    able to expand to accommodate soil movement.
                                                                                                                                                                                                                                                                    100 (min)

    Advice to Plumbers                                                                                                                                    Typical Detail
     Ensure that no piers are accidentally dislodged during trench                                                                                      Backfilling of Trench
     excavation. If this happens, advise site supervisor immediately.
                                                                                                                                                              Backfill with compacted clay soils
                                                                                                                                                              or equivalent to form an impermeable
    Construction Sequence                                                                                                                                     layer to all trenches within 1500 mm of
                                                                                                                                                              the building
                                                                                                                                                                                                                                                               100 mm
                                                                                                                                                                                                                                                                                                                      Pier
                                                                                                                                                                                                                                                               Underground
     1.              Pad Leveled                                                                                                                                                                                                                               Stormwater Line                                       Note: The slip coupling joints may be
                                                                                                                                                                        Minimum




     2.              Slab Set Out                                                                                                                                                                               Natural Surface                                                                                      substituted for flexible sub-surface pipes
                                                                                                                                                             300




     3.              Under Slab Plumbing                                                                                                                                                                                                                                                                             which comply with AS/NZS3500.3 and
     4.              Piering                                                                                                                                                                                                                                                                                         and AS/NZS 2566.1
     5.              Steel Up
                                                                                                                                                                        Varies
                                                                                                                                                             Backfill

                                                                                                                                                                        Depth




     6.              Concrete Pour                                                                                                                                                                        Approved bedding
                                                                                                                                                                                                          materials to
                                                                                                                                                                                                          appropriate cover
                                                                                                                                                                                                                                                                                 Site Classification
                                                                                                                                                                                                                                                                                         P/S
                                                                                                                                                                                                           Clay Plug to full
                                                                                                                                                                                                           depth of bedding                                              Note: If the site is classified as a Class
                                                                                                                                                                                                           at footing zone
                                                                                                                                                                                         Width Varies
                                                                                                                                                                                                                                                                         P the plumbing it to be done as per the
                                                                                                                                                                                                                                                                         soils characteristic reactivity noted on
                                                                                                                                                                                  Typical Trench Detail                                                                             page 1 of the report.




                            STA CONSULTING ENGINEERS
                       Brisbane North (Milton) (07) 3071 7444 Brisbane South (Rocklea) (07) 3071 7444 Gold Coast (07) 5522 1995 Mackay (07) 4960 4800
                                                                                                                                                                                             Client
                                                                                                                                                                                             DJK Electrical Services
                                                                                                                                                                                                                                                                          Site Address
                                                                                                                                                                                                                                                                          Lot 497 10 HILL STREET SUNSHINE BEACH 4567
                                                Townsville (07) 4766 8741 Rockhampton (07) 4994 9810 Newcastle (02) 4032 6450                                                                TBA SUNSHINE BEACH 4567
                                                     email: [email protected] webpage: www.staconsulting.com.au                                                                                                                                                                                                                                Page 11 of 14
                                                                                                                                                                                                                                                                    STDCON.2014-14-05

Page 12

                                                                                                                                                                                                                                                                                                      Project Job No. 173527

Section 5 - Drainage & Articulation Requirements
                                                                                                                                                                                                                                  Wall /Eaves Junctions
                                             Typical Vertical Articulation Joint Details

                                  Single Skin Masonry                                                      Cavity Wall Extendible Anchors


                 Compressible foam joint
                 filler and mastic-backing                                                                                                                                         Eaves Detail - Roof Supported On External
                 built in by bricklayer                                                                                                                                                     Leaf of Masonry Wall
                                                                                                                                                                                                                                                     Boxed or (horizontal) soffit-lined eaves
                                                                                                                                                                                  External wall supports roof structure
                                                                                                                                                                              eaves supoort framing, fixed to roof
                                                                                                                                                                              framing and not masonry wall

                                                                                                                                                                                     Alternative raked
                                                                                                                                                                                     eaves lining




                                                                                                                                                                                 Horizontal eaves lining

                                                                                                                                                                                   Optional cover moulding fixed                            Eaves lining above external              External masonry wall
                                                                                                                                                                                   to supporting timber for                                 wall and window/door heads               stops under eaves lining
                                                       Mastic sealant                                                                                                              horizontal eaves or rafter/
                                                                                                                                                                                   top plate for raked eaves




                                                                    Alternative Articulation Joint Detail
                                                                        For External Masonry Wall
                                                          Masonry expansion                Gap formed by
                                                          (Sliding/extendable) tie         temporary filler



                                                                                                                                                                                                                              Wall /Ceiling Junctions
                                                                                             Backer rod*
                                                                                             Elastomeric sealant
                                                                             10mm
                                                                                                                                                                                     Perimeter Wall With Framed or Trused Roof
                                                                                             *Open-cell polyurethane or
                                                                                             closed-cell polyethylene                                                                (Internal wall with framed roof similar detail)
                                                                                             to ensure proper sealant                                                                        Cornice fixed to roof framing only                               Internal Wall With Trussed Roof
                                                                                10mm minimum
                                                                                             dimensions                                                                                      allowing movement of masonry wall                             Bottom chord of roof truses




                               Fixing of Window /Door Frames at Articulation Joints                                                                                                                                                                      Gap sufficient                  Cornice fixed to roof
                                                                                                                                                                                                                                                         to allow for                    truss only allowing
                                                                                                                                                                                                                                                         expected movement               movement of
                                                                                                                                                                                                                                                                                         masonry wall

           Note:
           Various tie types
           available
                                                                            Masonry expansion tie                    Architrave conceals join on inside
                                                                            screwed to window frame
                                                                                                                                  Window/Door frame




                                                                                                                           Cover moulding conceals
                                                                                                                           articulation joint on outside


                                                                                                               Gap




                                       STA CONSULTING ENGINEERS
                                    Brisbane North (Milton) (07) 3071 7444 Brisbane South (Rocklea) (07) 3071 7444 Gold Coast (07) 5522 1995 Mackay (07) 4960 4800
                                                                                                                                                                     Client
                                                                                                                                                                     DJK Electrical Services
                                                                                                                                                                                                                                               Site Address
                                                                                                                                                                                                                                               Lot 497 10 HILL STREET SUNSHINE BEACH 4567
                                                             Townsville (07) 4766 8741 Rockhampton (07) 4994 9810 Newcastle (02) 4032 6450                           TBA SUNSHINE BEACH 4567
                                                                                                                                                                                                                                           STDCON.2014-14-05
                                                                  email: [email protected] webpage: www.staconsulting.com.au                                                                                                                                                                          Page 12 of 14

Page 13

                                                                                                                                                                                                                                                                                                                                            Project Job No. 173527
                                                                                                                                                             Typical Pathway and Driveway Details
                                                                  Typical Joint Layout                                                                                                                                                                              Typical Joint Details

                                   IJ           CJ          CJ            CJ            CJ                CJ             CJ               CJ           IJ
               Path                     IJ             IJ         IJ              IJ          IJ               IJ               IJ             IJ           CJ                                                                                                                                                       Typical Control Joint
                                                                                                                                                                 Control joints to be place in                          Typical Construction Joint                                                 Crack-Induced Joint (Saw cut, Insert or Tooled)
                              CJ
                                                                                                                                                       IJ        concrete paving at a ratio                                                    Stop board to form joint and                                                       Saw cut, insert or tooled joint
                                   IJ                                                                                                                       CJ   no greater than 1:1.3                                                         allow compaction of concrete                                                       (No sealant required)
                                                                                                                                                                                                    Reinforcing mesh                                                                                                    50 mm 50 mm
                                                                                                                                                                                                    continuous across joint
                              CJ
                                                                                Existing Dwelling                                                      IJ
                                   IJ                                                                                                                       CJ                                                                                       30 mm cover to mesh                               0.25 to 0.33T                           30 mm cover to mesh

                              CJ                                                                                                                                                                                                                                                Slab Thick.
                                                                                                                                                       IJ
                                                                                                                                                                                                                                                                                100 mm
                                                                                                                                                            CJ                                                                                                                     (T)
                                   IJ                                                                                                                                                                                                                                                                                                     Induced crack
                                                                                                          IJ            IJ           IJ          IJ                                                                                            Roughest first-cast face
                                                                                                     IJ         CJ             CJ           CJ         IJ         Path
                              CJ
                                                                                                          CJ
                                        Note : Where 1:20 fall away from garage
                                        cannot be acheived a grate drain is to
                                   IJ   be installed
                                                                                                     IJ
                              CJ                                                                                                                                                                                         Typical Control Joint
  Potential crack
                                                               Double Garage                              IJ                                                                                                     Key Joint (Pressed-Metal or Formed)
  if CJ used                                   IJ                        IJ                                                  Potential crack
                                                                                                                                                                                                                                                Optional coloured cover strip                                   Typical Expansion Joint
  instead of IJ                    IJ                                                    CJ                                  if CJ used
                                                                                                                             instead of IJ                          LEGEND                                                                      (No sealant required)                                                                 Suitable silicon or
                                                             CJ                                                                                                                                                                                                                                                                       polyurethane sealant
                                                                                                                                                                     Isolation Joint                                                                                                                             0.5L
                                                                                                                                                                                                                                                                                                                                      to prevent ingress of dirt.
                                                                                                          Extend pavement here to                                    Expansion Joint                                     40 mm                   40 mm                                                        Dowel
                                               CJ                        CJ                               avoid acute angles                                                                                                                                                                                  300 mm
                                                                                                                                                                     Control Joint
                                                                                                                                                                                                                                                      30 mm cover to mesh                                                         40 mm       30 mm cover to mesh
                                             3 m Max         CJ        3 m Max

                                                                                                                                                                                                                                                                                Slab Thick.
                                               CJ                                             Joints perpendicular to slab edge                                                                                                                                                 100 mm
                                                                                              to avoid acute angles                                                                                                                                                                (T)                                                    Bond-breaking
                     3 m Max                                 CJ                                                                                                                                     Propriety pressed-metal                                                                            0.5T                               compound
                                                                                                                                                                                                    key joint to suit slab thickness                                                                                   25 mm
                                               CJ
                                                                                                                                                                                                                                                                                               10 mm minimum thickness                Cap required
                                                                                                                                                                                                                                                                                               compressible filler material           for expansion
                                                                                                                                                                                                                                                                                               for full depth of pavement
  EJ if length greater than
  15 m, Otherwise CJ                           EJ
                                                                                                                                                                          Residential Driveways
                                                                                                                                                                          Typically :-
                                                                                                                                                                          2700 - 5000 wide
                                                                         3 m Wide driveway

                                                                                                                                                                                                                                    Typical Isolation Joint
                                               CJ                                                                                                     Varies
                                                                                                                                                                                                                                                          Abuting structure or
                                                                                                                                                                                                                                                          other pavement                            Mininum Steel Requirements :-
                                                                                                                                                                                                                Height to allow clearance to
                                                                                                                                                                                                                weep holes, flashing,                                                                 Site Classification            Reinforcement
                                                                                                            900 mm                                                                                              damp-proofing course,                                                                 Class    'S'                  SL 62
                                               CJ                                                          Transition                                                                                           termite barriers etc                      Suitable silicon or
                                                                                                                                                                                                                                                          polyurethane sealant                        Class    'M'                  SL 72
                                                                                                                                                                                                                30 mm cover to mesh                       to prevent ingress of dirt                  Class    'H1'                 SL 82
                                                                                                                                                                                                  Slab Thick.                                                                                         Class    'H2'            Site specific design required
                               Note : Cross over to be in                                                                                                                                         100 mm                                                  10 mm thick compressible
                               accordance with local authority                                                                                                                                       (T)                                                  filler material for full depth              Class    'E'             Site specific design required
                               requirements                                                                                                                                                                                                               of pavement
                                                                                                                                                                                                                                                                                                      Class    'P'             Site specific design required
                                                                                                                                                 Lip of kerb
                                                                   Fall - 25 mm over the
                                                                   first 1 m from building
                                                                                                                                600 mm                               600 mm

                                                                                                                                 Kerb                                Kerb
                                                                                                                               Transition                          Transition
Floor level at least 150 mm                                               Floor level at least 75 mm
above finished ground                                                     above external sealed area
                                                                         Fall                Drain                           Typical Cross Over Plan View




                                             STA CONSULTING ENGINEERS
                                        Brisbane North (Milton) (07) 3071 7444 Brisbane South (Rocklea) (07) 3071 7444 Gold Coast (07) 5522 1995 Mackay (07) 4960 4800
                                                                                                                                                                                                  Client
                                                                                                                                                                                                  DJK Electrical Services
                                                                                                                                                                                                                                                                                           Site Address
                                                                                                                                                                                                                                                                                           Lot 497 10 HILL STREET SUNSHINE BEACH 4567
                                                                 Townsville (07) 4766 8741 Rockhampton (07) 4994 9810 Newcastle (02) 4032 6450                                                    TBA SUNSHINE BEACH 4567
                                                                                                                                                                                                                                                                                       STDCON.2014-14-05
                                                                      email: [email protected] webpage: www.staconsulting.com.au                                                                                                                                                                                                                   Page 13 of 14

Page 14

                                                                                                                                                                                                                                                                Project Job No. 173527
                                              Department of Housing and Public Works                                                6. Competent person details                       Name (in full)
                                                                                                                                    A competent person for building work,
                                              Form15—Compliance certificate for                                                     means a person who is assessed by the
                                                                                                                                    building certifier for the work as competent
                                                                                                                                                                                        Angelo Iancu
                                                                                                                                                                                      Company name (if applicable)                           Contact person
                                              building design or                                                                    to practice in an aspect of the building and
                                                                                                                                    specification design, of the building work          STA Consulting Engineers                             Nicole Strano
                                              specification                  Version 4 – July 2017                                  because of the individuals skill, experience
                                                                                                                                    and qualifications in the aspect. The
                                                                                                                                                                                      Phone no. business hours            Mobile no.                        Fax no.
                                                                                                                                    competent person must also be registered            (07) 3071 7444                     N/A                               (07) 3876 2763
                                                                                                                                    or licensed under a law applying in the           Email address
NOTE: This is to be used for the purposes of section 10 of the Building Act 1975 and/or section 46 of the Building                  State to practice the aspect.
Regulation 2006.                                                                                                                                                                        [email protected]
                                                                                                                                    If no relevant law requires the individual to
RESTRICTION: A building certifier (class B) can only give a compliance certificate about whether building work                      be licensed or registered to be able to give      Postal address
complies with the BCA or a provision of the Queensland Development Code (QDC). A building certifier (Class B)                       the help, the certifier must assess the
can not give a certificate regarding QDC boundary clearance and site cover provisions.                                              individual as having appropriate                    241 Milton Road, Milton
                                                                                                                                    experience, qualifications or skills to be
1. Property description                                                                                                                                                                                                                         Postcode 4064
                                              Street address (include no., street, suburb / locality & postcode)                    able to give the help.
This section need only be completed if          Lot 497 10 HILL STREET SUNSHINE BEACH 4567                                                                                            Licence or registration number (if applicable)
details of street address and property                                                                                              If the chief executive issues any guidelines
description are applicable.                                                                                                         for assessing a competent person, the
                                                                                                                                    building certifier must use the guidelines          Angelo - BSc PEng MIEAust (Civil, Structural) AGS RPEQ 4425
EG. In the case of (standard/generic)
                                                                                                                                    when assessing the person.
pool design/shell manufacture and/or          Lot & plan details (attach list if necessary)
patio and carport systems this section                                                                                              7. Signature of competent person                  Signature                                                      Date
may not be applicable.
                                                RP 48112                                                                            This certificate must be signed by the
The description must identify all land        In which local government area is the land situated?                                  individual assessed by the building certifier
the subject of the application.                                                                                                     as competent.
                                                SUNSHINE COAST REGIONAL
The lot & plan details (eg. SP / RP) are                                                                                                                                                                                                                12 September 2019
shown on title documents or a rates
notice.                                                                                                                            The Building Act 1975 is administered by the Department of Housing and Public Works
If the plan is not registered by title,
provide previous lot and plan details.                                                                                             Section 7 Certification of Soils and Design Report - Obligations of the Home Owner/ Occupier
2. Description of Component/s
Certified                                       Foundation Design (including Retaining Walls if incorporated within the report )      The performance of the footings and slab or both is largely depended upon a responsible approach by the builder and owner/occupier towards vegetation
Clearly describe the extent of work                                                                                                   and site drainage.
covered by this certificate, e.g. all
                                                Project Job Number ES 173527incorporating pages 1 through to 14.
structural aspects of the steel roof beams.                                                                                           THE DESIGN DOCUMENTATION REFERENCE GUIDE VERSION 6002 2.1. (Download PDF copy from www.staconsulting.com.au)

3. Basis of Certification                                                                                                             1.   Is part of this Foundation Design Report and this Foundation Design Report cannot be relied on without it;
Detail the basis for giving the certificate     Design Criteria -                                                                     2.   Must be read and understood by the builder;
and the extent to which tests,                   NCC - National Construction Code of Australia.                                      3.   Contains requirements and recommendations, and all requirements and recommendations must be complied with by the builder;
specifications, rules,
                                                 AS1170.2-2011 SAA Loading Code.
standards, codes of practice and other                                                                                                THE HOME OWNERS REFERENCE GUIDE VERSION 6002 1.1 (Download PDF copy from www.staconsulting.com.au)
publications, were relied upon.                  AS3600-2009,Concrete Structures.
                                                 SAA HB28-1997 The Design of Residential Slabs and Footings.                         1.   Is part of this Foundation Design Report for the use of the homeowner/occupier;
                                                 AS2870-2011 Residential Slabs & Footings.                                           2.   Must be read and understood where appropriate by the homeowner/occupier;
                                                 AS4055-2012 Wind Loads For Housing.                                                 3.   Contains requirements and recommendations, and all requirements and recommendations must be complied with by the homeowner/occupier;

                                                 AS1726-1993 Geotechnical Site Investigations.
                                                                                                                                      The home owner must also familiarise themselves with the information sheet Foundation Maintenance and Footing Performance : A Home Owners Guide
                                                                                                                                      Building Technology File 18 (Formerly known as Information Sheet 10-91), prepared by John Lewer FAIB, MIAMA, Partner, Construction Diagnosis and
                                                                                                                                      produced by the CSIRO. The following document can be viewed at the following link :-
4. Reference Documentation
Clearly identify any relevant                   Project Job Number ES 173527.
                                                                                                                                                                                       http://www.publish.csiro.au/Books/download.cfm?ID=3612
documentation, e.g. numbered structural
engineering plans.                              Reference Documents :-                                                                Where there is ANY FAILURE of the builder or homeowner/occupier to comply with the above obligations then the RESPONSIBILITY for ANY FAILURE
                                                 Geotechnical Investigation by Core Consulting Pty Ltd                               rests with the builder or homeowner/occupier.
                                                   Job Number J000594-001-R-Rev0
                                                                                                                                      Any concerns understanding the information provided within this document, please contact STA Consulting Engineers and a representative will assist in
                                                                                                                                      providing further clarification.


                                                                                                                                      I hereby certify STA Consulting Engineers Job Number ES173527 , incorporating pages 1 through to 14.

5. Building certifier reference number        Building certifier reference number                                                                                                                                                                                   Digitally signed by
                                                                                                                                                                                                                                                                    Structural Department
                                                                                                                                                                                                                                                                    DN: c=AU,
                                                                                                                                                                                                                                                                    st=QUEENSLAND, l=Milton,
                                                                                                                                      Angelo Iancu, BSc PEng MIEAust (Civil, Structural) AGS RPEQ 4425                                                              o=STA Consulting
                                                                                                                                                                                                                                                                    Engineers, cn=Structural
                                                                                                                                                                                                                                                                    Department,
                                                                                                                                                                                                                                                                    email=structural.dept@stac
                                                                                                                                                                                                                                                                    onsulting.com.au
                                                                                                                                                                                                                                                                    Date: 2019.09.12 09:55:50
                                                                                                                                                                                                                                                                    +10'00'


  LOCAL GOVERNMENT USE ONLY                                                                                                           Client
                                                                                                                                      DJK Electrical Services
         Date received                                                        Reference Number/s                                      TBA SUNSHINE BEACH 4567
                                                                                                                                                                                                                                                                               Page 14 of 14

Used in these records

About this file

File size
835 KB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

ES_173527_BR_1059006_Conv_Lot 497 10 HILL STREET SUNSHINE BEACH QLD(C).pdf · 835 KB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.