ES_173527_BR_1059006_Conv_Lot 497 10 HILL STREET SUNSHINE BEACH QLD(C) · MCU18/0006.02
Attached to the e-mail Hill Street .msg.
Attached to the e-mail Hill Street, .eml, inside Generally in Accordance Application MCU18/0006.02 - Cover email - Plans.
Project Job No. 173527
Edge Beam Footing Detail Slab Thickening Detail Step Down Details Step Down Details
(Brick Veneer) (100 mm Maximum) (350 mm Maximum)
Slab Mesh 200 Min
300 200 Min
Slab Mesh 100 Slab Mesh Lap 100 Max Slab Mesh Lap
100
200
Starter Compacted Fill 350
300 100
Bar 200 Max
Compacted Fill
G.L Trench Mesh
100
150 Bedding Sand 300
Vapour Barrier as 50 mm Min.
400 100 300 200
per AS 2870
Trench Mesh 300
40
300
Drilled Pier
where required
Edge Beam Footing Detail
(External Clad Finish) Internal Footing Detail
350 Typical Load Bearing Wall Detail
Note : Slab thickening to be placed under or within 300 300
1.0 m of load bearing wall Load Bearing Party Wall &
300 Slab Mesh
Wall Starter Bars by others
Slab Mesh < = 1000
300
300 Starter Slab Mesh Compacted Fill Compacted Fill
Bar G.L G.L
Compacted Fill
G.L 100 *Starter
Bedding Sand Vapour Barrier as
Bar
Vapour Barrier as Bedding Sand per AS 2870
200 400
per AS 2870 50 mm Min. Compacted Fill
400 100 * One starter bar per location with the
next being in opposite direction
40 Trench Mesh
300 Trench Mesh
Trench Mesh
300
300
Notes :- Design Specification Table : Concrete Strength Table :
1. Bar Chairs are to be placed at 800 centres Maximum.
2. Slab Mesh to have 25 mm Top Cover. Steel Reinforcement Product Code Steel Strength Elements Concrete Strength Slump
F'c MPa (mm)
3. Slab Mesh to have 35 mm Edge Cover.
Slab Fabric SL82 500 Grade
4. Trench Mesh to have 40 mm Bottom Cover. Bored/ Drilled Piers 20 80 - 100
5. Reinforcement bars to have 40 mm Cover (around entire bar). Edge Beam & Thickening Reinforcement 3 L12 TM 500 Grade Strip Footing 20 80 - 100
6. Slab Edge and Internal ribs MUST be vibrated.
Starter Bars N12 [email protected] m c/c 500 Grade Slab On Ground
20 80 - 100
Garage/ External
Slab Thickness 100 mm Slab On Ground
20 80 - 100
Internal
Design Code : S8-27.6.2013
STA CONSULTING ENGINEERS
Brisbane North (Milton) (07) 3071 7444 Brisbane South (Rocklea) (07) 3071 7444 Gold Coast (07) 5522 1995 Mackay (07) 4960 4800
Client
DJK Electrical Services
Site Address
Lot 497 10 HILL STREET SUNSHINE BEACH 4567
Townsville (07) 4766 8741 Rockhampton (07) 4994 9810 Newcastle (02) 4032 6450 TBA SUNSHINE BEACH 4567
STDCON.2014-14-05 Page 3 of 14
email: [email protected] webpage: www.staconsulting.com.au
See the original