#102 Line test report OBoats Noosaville
Attached to the e-mail MCU22/0048 & OPW22/0089 - Representations.
3rd Party Certified Testing of service lines: Test Results O Boats Noosaville
Service Line Test Results:
#1 ULP supply Line Test Results: PASS
Date Time Time finish Test time Test pressure Test pressure Result
start KPA Start KPA Finish
14/12/21 12.30 hrs 12.45 hrs 15 minutes 100 100 PASS
#2 Line Test Results:
#3 Line Test Results:
#4 Line Test Results:
#5 Line Test Results:
#6 Line Test Results:
#7 Line Test Results:
#8 Line Test Results:
#9 Line Test Results:
DGC technician reports:
#1 ULP line PASSED the line test criteria. Hydrostatic pressure test.
Observations:
The double wall UPP supply line was isolated at the tank turret and the 2 tri-flexers under each pump
(dual bowser). Then a hydrostatic pressure was conducted to 100kpa.
The line held target test pressure for 15 minutes and proved tight.
On conclusion of the test, the triflexers were reinstated with 2 new gaskets.
Other maintenance works;
Technician removed and checked the VR float valve for operation. All good.
Recommendations:
Maintain annual tank/ line integrity test maintenance schedule for indications of future
degradation.
Non‐compliance items shall be upgraded in accordance with current legislation & Standards:
• Work Health and Safety Act 2011 & Work Health and Safety Regulation 2011
• AS 1940-2017: The storage and handling of flammable and combustible liquids
• AS 4897-2008: The design, installation and operation of underground petroleum
storage systems.