Approved Plans OPW22-0104
The original of this document is very large (10.3 MB). Opening the original or downloading it may take a few minutes. Please be patient and don't click again. The page text is quick to read. If you are on mobile data, it is best to wait until you are on Wi-Fi.
Original PDF page 9, section 1. The text section number identifies this passage in the reader.
This document appears to be plans or drawings. Its page text below holds only the words printed on the drawings, without the drawings themselves, so it may be jumbled or hard to follow. To see the plans as drawn, choose Original above or download the file (both need you to log in).
Log in to see the plans as drawn LEGEND
GENERAL NOTES
EXISTING
1. NO OTHER SERVICES TO ENCROACH INTO THE STANDARD
OVERHEAD CABLE UNDERGROUND ELECTRICITY CORRIDOR OF 0mm - 900mm FROM RPA.
2. ALL CABLES TO BE INSTALLED IN CONDUIT WITHIN THE STANDARD
PROPOSED ELECTRICITY ALIGNMENT ALLOCATED BY THE LOCAL COUNCIL. WHERE
OVERHEAD CABLE CONDUITS VARY FROM THIS AND AT FOOTPATH CROSSING PROTECTIVE
STRIP IS TO BE INSTALLED. WHERE PRACTICAL ELECTRICITY CABLES
SHALL NOT BE CLOSER THAN 250mm TO THE REAL PROPERTY
EXISTING
UNDERGROUND BOUNDARY.
CABLE
3. A, B OR C WHEN SHOWN BESIDE LV PILLARS DENOTES SERVICE
PHASING.
25 PAVILION STREET, POMONA
PROPOSED
UNDERGROUND
CABLE
4. THE CONTRACTOR SHALL MEASURE ACTUAL CABLE LENGTHS
REQUIRED ON SITE AFTER INSTALLATION OF CONDUITS THEN NOTIFY
E ENERGEX/SUPPLIER WHEN CONFIRMING CABLE ORDER.
PROPOSED
ELECTRICAL 5. ALL BENDS INSTALLED ON 80mm,100mm AND 125mm RETICULATION
SERVICE CONDUIT
CONDUITS MUST BE 1830mm RADIUS UNLESS OTHERWISE SPECIFIED.
ET
PROPOSED
ELECTRICAL &
NOOSA COUNCIL 6. CONTRACTOR TO SUPPLY ALL LABELS AND SITE ID NUMBERS TO
ENERGEX SPECIFICATION.
COMMUNICATION
SERVICE CONDUITS APPROVED PLAN 7. WHEN CROSS ROAD CONDUIT FINISHES OPPOSITE A TRUNCATION PEG,
OPW22/0104 3 JUN 2022 TREE STREET PROPERTY SIDE OF TRENCH TO BE 300mm ALIGNMENT FROM PEG.
POLE 8. WHERE CROSS-ROAD ELECTRICITY CONDUITS RUN PARALLEL TO
TRANSFORMER OTHER SERVICES OR CONDUITS, A MINIMUM SEPARATION OF 1.0m MUST
BE MAINTAINED.
PADMOUNT 9. CIVIL CONTRACTOR TO INSTALL ALL CROSS ROAD CONDUITS.
TRANSFORMER
9 10. CO-ORDINATE CONDUIT INSTALLATION WITH COMMUNICATIONS
7 8 CARRIER CONTRACTORS.
PAVILION STREET
6
600
HV POLE 11. ELECTRICITY PILLARS TO HAVE 600mm EXCLUSION ZONE. NO
NON-ENERGEX ASSETS TO BE INSTALLED WITHIN THIS EXCLUSION
ZONE.
HV / LV POLE
HANSEN PLACE 12. ENERGEX REQUIRE 1.0m CLEARANCE BETWEEN SERVICE PILLARS AND
DRIVEWAYS. IF LESS THAN 1.0m SEPARATION THEN PROTECTIVE
BOLLARDS MUST BE INSTALLED.
LV POLE
CONSTRUCTION CONTRACTOR
1
HV UNDERGROUND 10 5 4 3 2 THE CONTRACTOR SHALL BE RATED BY ENERGEX FOR THE FOLLOWING
POLE TERMINATION PROCESS.
WCS 2 - UNDERGROUND CONSTRUCTION
WCS 31 - COMMISSIONING AND OPERATION OF THE NETWORK
LV UNDERGROUND
WCS 34 - EARTHING SYSTEMS
POLE TERMINATION WCS 61 - UNDERGROUND CIVIL CONSTRUCTION
SANDY STREET STANDARDS AND SPECIFICATIONS
AERIAL STAY
THIS WORKS PLAN IS TO BE READ IN CONJUNCTION AND COMPLY WITH THE
FOLLOWING ENERGEX MANUALS AND SPECIFICATIONS
GROUND STAY
· UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
· WCS 61.1 - UNDERGROUND TRENCHLESS TECHNOLOGY
· NETWORK LABELLING AND SIGNAGE MANUAL
EARTH
LOCALITY PLAN
NOT TO SCALE CONSUMER'S INSTALLATION SHALL COMPLY WITH AS/NZS 3000:2018 - SAA
WIRING RULES.
EXISTING PILLAR FOR DETAILS OF TRENCH CROSS-SECTIONS, REFER TO ENERGEX
UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL.
STREETLIGHTING CERTIFICATION CERTIFICATE OF COMPLIANCE
PROPOSED PILLAR
This lighting design is certified to comply generally with the nominated categories
ON SITE SERVICES CHECKS
DESIGN DOCUMENTATION IN ACCORDANCE WITH THE REQUIREMENTS OF:
of AS/NZS 1158.3.1:2020 (P Category) for luminaires supplied on the following UNDERGROUND SERVICES SHOWN ON THIS WORKS PLAN IN THE VICINITY
APPLICABLE STANDARD : AS/NZS 1158.3.1:2020 OF PROPOSED EXCAVATION WORKS HAVE BEEN TAKEN FROM ASSET
LINK PILLAR roads within this design : OWNER'S PAPER RECORDS AND ARE INDICATIVE ONLY.
CALCULATION SOFTWARE : PERFECT LITE v5.06
240LV
D
HANSEN PLACE PR6 Lighting Category THE CONTRACTOR IS RESPONSIBLE FOR THE REPAIR OF DAMAGE TO ANY
EXISTING UNDERGROUND ASSETS CAUSED BY HIS WORKS AND THE
CONDUIT / CABLE HANSEN PLACE
CROSS-SECTION Road Name(s) RE-ESTABLISHMENT OF ANY SURVEY MARKS DISLODGED.
X THE CONTRACTOR SHALL REQUEST ON-SITE IDENTIFICATION AND
Nominated Category PR6 LOCATION OF EXISTING BURIED SERVICES FROM THE QUEENSLAND DIAL
WATER METER With the following exceptions:
UWLR exceeds 1% for modular LEDs (2.8%)
Road Surface Reflection N/A PILLARS / PITS ON ZERO LOT BOUNDARIES BEFORE YOU DIG SERVICE - PHONE: 1100 WEB: www.1100.com.au (A MINIMUM
Road Reserve Width 15m OF TWO DAYS NOTICE IS REQUIRED)
PROPOSED 1.0m
DRIVEWAY ENTRY Mounting Height 5.1m SEWERAGE, STORMWATER, GAS AND WATER PLANS FOR THE SITE MAY BE
Maintenance Factor: Overhang/Offset Distance 3.90m OBTAINED ON REQUEST FROM THE PROJECT SERVICE SUPERVISOR.
PROPOSED ZERO This lighting design uses the following maintenance factor(s): Lighting Arrangement Single Sided
LOT IDENTIFIER
Maintenance Factor Calculated : 0.75 Pole Setback 0.7m NFK REINSTATEMENT NOTES
driveway
Back of K
erb
Future
Upcast Angle 0° 0.6m 1m Pillar 1.0m
LIGHTING These maintenance factor(s) are based on the following nominal maintenance clear of driveway · BACKFILL & REINSTATEMENT OF FOOTPATH AND ROADWAY TO COUNCIL
Luminaire Details
PIT-ID
LEGEND 5 REQUIREMENTS. REFER STANDARD DRAWINGS:
regime: Lamp Type / Wattage L17
Electricity
supply co
rridor ·· RS-065 - PATHWAYS CONCRETE PATHWAY CONSTRUCTION
NOTE: NOT ALL RP BOU
· Lamp replacement (for non-LED luminaires) at 36 month intervals. Exclusion NDARY DETAILS
DARY
SYMBOLS MAY BE Luminaire Identification Modular LED 15W 4K 170326PHM Zone
USED 0.75 / 0.9
0m ·· 8 - 00398 - PATHWAY DETAILS AND SECTIONS
· Cleaning, inspection and maintenance of all luminaires at 36 month intervals
T BOUN
Lamp Flux (lumens) 1899 lms Side of the ·· 8 - 00399 - CONCRETE FOOTPATH FULL WIDTH
pillar aligned
· Service availability maintained at not less than 95%. I-table Identifier 170326PHM.CIE
ZERO LO
with the
Lighting Tariff RATE 2 boundary
LED STREET · Vegetation kept clear of luminaires.
LIGHT
If the asset owner elects not to adopt this maintenance regime, they shall develop
Power Factor
Start/run Currents
HPF (≥ 0.9)
0.08 / 0.08A
House on the
boundary DEVELOPERS NOTES
1. DO NOT CONSTRUCT DRIVEWAYS /
S100 HPS STREET an inspection and maintenance regime such that the overall lighting installation Ip Rating IP66
CROSSOVERS UNTIL ELECTRICAL
LIGHT
operates in accordance with this design. Spacing Calculations WORKS HAVE BEEN COMPLETED.
Proposed House
Average Horizontal Illuminance (E h) ≥ 0.7 lx
S150 HPS STREET Min Point Horizontal Illuminance (E Ph ) ≥ 0.07 lx
LIGHT Illuminance Uniformity (U E2) ≤ 10 N.T.S
Upward Wasted Light Ratio (UWLR) % 2.8% REQUIREMENTS FOR ELECTRICAL, GAS &
S250 HPS STREET
Road Reserve Lighting Design Width (m) Maximum Spacing (m) COMMUNICATIONS COUNCIL REQUIRE 1.0m CLEARANCE BETWEEN
ELECTRICAL PILLARS AND WATER METERS. INSTALL
LIGHT 15 73.0
Fire Ant The proposed pillar shall be offset at the zero lot WATER METERS MINIMUM 1.5m FROM BOUNDARY PEG
Biosecurity
boundary with the side of the pillar being aligned
WHERE WATER METERS SHARE A COMMON BOUNDARY
Caution
EXISTING UNKNOWN with the lot boundary in order to provide a 1.0m
STREET LIGHT minimum clearance from the future driveway. WITH ELECTRICAL PILLARS.
A proposed streetlight shall be offset 1.0m from
FILE: P:\221308\01 WORKING\A221308A
the boundary peg to centre of pole.
Zone COMMUNICATIONS PITS GAS SERVICE TEE-OFFS
FOR APPROVALS
are to remain outside 600mm are to remain outside 600mm (NOT FOR CONSTRUCTION)
TO BE BUILT IN CONJUNCTION WITH For Info pillar exclusion zone
shall not clash with future
pillar exclusion zone where a
pillar is offset to align on one
TELECOMMUNICATIONS CABLE PROVISIONING Call 13 25 23 driveways side with the boundary peg 26/05/2022 1:50 PM
S2602185
This document is CLIENT SITE CONTACT DETAILS ALIGNMENTS PROJECT / CERTIFICATION: PROJECT
the property of NAME ENERGEX OH 3.0 RP SUB PROJECT NO. APPROVED: 10 LOT RESIDENTIAL SUBDIVISION
RPEQ No:
Ampflo Pty Ltd NOEL SHIPP ENERGEX UG 0-0.90 PARENT PROJECT NO. - DATE: 25 PAVILION STREET, POMONA
and may only be COMPANY TELSTRA 2.1-3.0 WORK REQUEST NO. - LOCALITY PLAN, NOTES, LEGEND &
PLOT: 26/05/2022 1:50:08 PM
used for the ABN 28 111 423 842
purpose for JNE DEVELOPMENTS JNE DEVELOPMENTS PTY. LTD. GAS N/A PLANNER & PHONE SUBDIVISIONS
Electrical and Telecommunications
STREETLIGHTING COMPLIANCE
which it was PHONE HP GAS N/A LOTS 1 - 10 + 600 Consultants CHECKED:
commissioned. MOBILE 0421572866 WATER 0.9-2.1 CANCELLING LOTS 21 ON SP316902 ISO 9 0 0 1
Phone : (07) 3372 9280 ISSUE
CERTIFIED DESIGNER: S.LYNSKEY DRAWING: 221308
A
Unauthorised A 10/05/2022 PRELIMINARY ISSUE SL EMAIL [email protected] STORMWATER N/A LOCAL AUTHORITY NOOSA SHIRE COUNCIL Email : [email protected]
Q U A L I T Y
use is prohibited. REV DATE DETAILS DRAWN CHECKED APPRVD SEWERAGE 0.9-2.1 PEGGED? ON REQUEST MANAGEMENT
Website : ampflo.com.au ISSUE DATE: 10/05/2022 PROJECT: A221308 SHEET 1 OF 3