70. Noise emission from mechanical equipment (air conditioners, refrigeration equipment or pool pumps etc)
shall comply with the following requirements:
The equipment shall be installed and located in a manner that prevents excessive noise in accordance
with Council’s Local Law No. 12 - Control of Nuisances. Infringement Notices (on-the-spot fines) may
apply for offences.
A person must not use equipment on any day if it makes or causes noise to be made –
From 10pm to 7am: More than the lower of either –
40 dB(A)
3 dB(A) above the background noise level
No audible noise for pool pumps apply during these hours.
From 7am to 7pm: More than the lower of either –
50 dB(A)
5 dB(A) above the background noise level
From 7pm to 10pm: More than 3 dB(A) above the background noise level.
71. Submission of written certification from a suitably qualified person confirming that the noise levels from all
mechanical equipment comply when measured at either the residential boundary or outside the most
exposed part of an affected building, whichever is the closest to the equipment.
The assessment and certification is required immediately after installation of the equipment and prior to
any occupation of the building, and in a format approved by Council. This assessment must take into
account noise from any other fixed equipment on the property e.g. swimming pool pump, heating/cooling
equipment, etc that may increase the overall noise level emitted.
Advice: It is highly recommended that the person you engage to certify the installation is involved at the
plan development stage so they can recommend where this equipment is best located. They can also
advise about noise enclosures and can make other suggestions to avoid noise problems. It is a lot more
costly to try and deal with noise problems after everything is built.
72. An acoustic report prepared by a registered professional Acoustic Consultant shall be submitted and
approved prior to the issue of a development approval for operational works. The acoustic report shall
assess all potential noise sources and demonstrate how the development will not cause –
72.1. Excessive noise under Council’s Local Law No. 12 – Control of Nuisances.
72.2. Unlawful environmental nuisance under the Environmental Protection Regulation 1998.
NB: In particular, the noise from the cars on the ramp entering and leaving the underneath parking.
AOP2 c:\docume~1\aop2\locals~1\temp\bcl technologies\easypdf 5\@bcl@40076eb3\@[email protected]
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
SUPERSEDED Decision Notice - 010.2006.00002689.001 [As Published]Related documentApplication case desk ↗
About this file
- File size
- 283 KB (small file)
- File type
No other editions are linked here.