CIVIL ENGINEERING PROJECT MANAGEMENT
SEDIMENT AND EROSION CONTROL
ENGINEERING REPORT
Material Change of Use – Industrial Warehouses
9 Bartlett Road, NOOSAVILLE
DATE: 06.12.21 REF: 124-003
ATT: Mr Michael Klobas EMAIL: [email protected]
REV: A
2261 david low way, peregian beach, qld 4573 acn: 626 671 092 [email protected]
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalVery large file: the download may take a few minutes. If you are on mobile data, it is best to wait until you are on Wi-Fi.
Searchable page text hides email addresses. Original files are unchanged and may show email addresses.
Full text of the other 37 pages
Page 2
CONTENTS PAGE
Flooding ....................................................................................................................... 9
Quantity ....................................................................................................................... 9
Quality ......................................................................................................................... 9
Electrical and Communications ................................................................................. 10
Gas ............................................................................................................................. 10
Page 2 of 12
2261 david low way, peregian beach, qld 4573 acn: 626 671 092 [email protected]
Page 3
LIST OF FIGURES
Figure 1 - Locality Plan ......................................................................................................................................... 5
Figure 2 – Stormwater Network and Contour Plan ............................................................................................. 6
LIST OF APPENDICES
Appendix A Building Plans
Prepared by Sprout Architects dated November 2021
Appendix B Flood Mapping
Noosa Council Flood mapping
Appendix C Water and Sewer Infrastructure
Unitywater Mapping
Appendix D DBYD Plans
NC, Telstra, NBN and Energex Asset Reports
Page 3 of 12
2261 david low way, peregian beach, qld 4573 acn: 626 671 092 [email protected]
Page 4
INTRODUCTION
Bax Engineering has been commissioned by Mr Michael Klobas of Juklo Pty Ltd to provide an engineering
assessment for the proposed development at 9 Bartlett Road, Noosaville.
The report is intended to support the development application seeking approval for a Material Change of Use.
The proposal covers a site area of 1,528m2 and is currently used as a storage business. It is proposed that the
development would consist of a single, two storey building with three separate industrial warehouse
tenancies.
Page 4 of 12
2261 david low way, peregian beach, qld 4573 acn: 626 671 092 [email protected]
Page 5
THE SITE AND ITS CONTEXT
LOCALITY
The site is described as lot 48 on RP173566 at 9 Bartlett Road in Noosaville, Queensland and is within the
Noosa Council local government boundary. The development is identified in Figure 1.
The property is bounded by Bartlett Street to the north, commercial lots in the west and east with residential
lots on Gumdale Court to the south.
Figure 1 - Locality Plan
Source: Queensland Globe
The site is currently being used for self-storage and is fully impervious with concrete hardstand and roof area
covering the entire property. There is an existing high point of approximately 19.0m AHD at the north-west
frontage in Bartlett Street with fall towards the southern rear boundary to an AHD of 18.0m. There is existing
Page 5 of 12
2261 david low way, peregian beach, qld 4573 acn: 626 671 092 [email protected]
Page 6
stormwater infrastructure in this location which will be utilised as a lawful point of discharge. This 225mm dia.
stormwater pipe collects runoff from the adjacent property to the east and enters the stormwater network in
Gumdale Court to the south. It is expected that the design of the building and surrounds will utilise the
stormwater system to collect minor storm events and roof water runoff while major events will be directed to
the Bartlett Road frontage. It is expected some earthworks will be needed to achieve these design levels and
for standard vehicle and pedestrian access to the proposed development.
Figure 2 – Stormwater Network and Contour Plan
Source: Noosa Council Mapping
Page 6 of 12
2261 david low way, peregian beach, qld 4573 acn: 626 671 092 [email protected]
Page 7
PROPOSED DEVELOPMENT
The proposed development will consist of a single two storey building that will consist of three separate
commercial tenancies. It is proposed that vehicle and pedestrian access will be from the Bartlett Road frontage
with carparking in the north of the property. Construction works will consist of bulk earthworks, carparking,
stormwater drainage and the installation of stormwater improvement devices. Internal water and sanitary
drainage for the building will also be provided under a separate plumbing approval as part of the building
development. These will be connected to the existing water and sewer main connections provided for the
property.
Where required, sediment and erosion control devices will also be installed during all stages of construction.
The proposed lot configuration and development are shown in Appendix A.
DRAINAGE AND EXISTING TOPOGRAPHY
In general, the site is elevated at around 19.0m AHD in Bartlett Street and grades at approximately 2% towards
an existing low point at around RL 18.0m AHD in the south-west corner. There is an existing drainage pit in this
location which will be utilised as a lawful point of discharge for roofwater and carpark drainage. Due to the
proposed design of the building, overland flows from major events will be diverted to the Bartlett Road
frontage in the north. This will ensure any pipe blockages will not create flooding to the tenancies.
Page 7 of 12
2261 david low way, peregian beach, qld 4573 acn: 626 671 092 [email protected]
Page 8
ENGINEERING
VEGETATION CLEARING AND MANAGEMENT
There are no established trees or existing vegetation on the site. However, the existing concrete hardstand
and buildings will all be demolished and removed as part of the new development.
EARTHWORKS
The existing site conditions has a maximum elevation of approximately 19.0m AHD with a site grading of
around 2% across the development to the south west.
It is expected that some filling of the property is required along with some minor retaining for stormwater
management and standard vehicle and pedestrian access to the proposed development.
These earthworks would be limited to the site bounds and to the volumes that would assist in allowing positive
fall to the street frontage and vehicle access.
Earthworks will be designed to reduce the amount of disturbance as much as possible while conforming with
accessibility, safety and ease of maintenance requirements. Any unsuitable spoil would be lawfully removed
and some minor volumes of fill imported to site.
All bulk earthworks within the development would be completed under Level 1 Geotechnical Supervision and
Australian Standard AS3798:2007 - Guidelines on earthworks for commercial and residential developments.
ROADWORKS/CARPARK CONSTRUCTION
The roadworks for the proposed development will consist of an entry and exit point from the existing Bartlett
Road frontage as well as the carpark within the property boundary. It is proposed that the access driveway
would be from the northern boundary and provide service to the carpark only. Vehicle crossovers would be
constructed in concrete to the Noosa Council standards, the proposed pavement of the internal carpark would
be concrete.
All pavements will be graded as such that runoff is directed to stormwater inlets and to the ultimate lawful
point of discharge.
The carpark and driveway would be such that it complies with the Noosa Council and Australian standards for
roadworks design, turning movements for Medium Rigid vehicles and off-street parking.
Page 8 of 12
2261 david low way, peregian beach, qld 4573 acn: 626 671 092 [email protected]
Page 9
STORMWATER DRAINAGE
It is expected that stormwater drainage management will be required as part of the development. This would
include quality control measures with treated stormwater runoff directed to the existing stormwater system
in the rear of the property and ultimately into the stormwater network in Gumdale Court to the south.
Flooding
Flood mapping courtesy of the Noosa Council and provided in Appendix B indicates the site is not subject to
flooding from any sources.
The mapping demonstrates all defined major and extreme flood extents are limited to the Lake Entrance
Boulevarde in the south.
Quantity
The objective of the stormwater management will be to limit the post-development, peak discharge to the
pre-development peaks in order to control flooding and erosion and to limit nuisance. It is expected that due
to the impervious site area being reduced from 100% to 85% and that major overland flows would be diverted
to the north, the post-developed conditions will be slightly lessened and detention will not be required. This
will be subject to a detailed analysis during the operational works design.
Quality
The stormwater quality treatment measures will be designed to mitigate stormwater pollutants in accordance
with WSUD load reduction targets in Council’s Planning Scheme Policy for Development Works.
The stormwater quality management objectives during the construction phase will be addressed in separate
Erosion and Sediment Control Plans (ESCP) prior to the commencement of works. The efficiency of the
Stormwater Quality Improvement Devices (SQIDs) will be modelled for efficiency and will consist of baskets
(SPEL Stormbaskets or similar) in the carpark gully inlets and bioretention systems in the landscaping design
SEWER RETICULATION
An existing sewer main is located along the northern boundary. A 150mm diameter (AC) pipe traverses the
property from the west to the east and flows towards the east. Being a proposed commercial development,
the sanitary drainage from the property will connect into a proposed manhole in the north east corner of the
site.
The existing sewer infrastructure is shown on the Assets map provided in Appendix C.
Page 9 of 12
2261 david low way, peregian beach, qld 4573 acn: 626 671 092 [email protected]
Page 10
WATER RETICULATION
An existing AC 150mm diameter main is located within the Bartlett Road frontage on the northern boundary.
The proposed connection will include a fire hydrant and water meter assembly in accordance with the relevant
plumbing code and hydraulic plans.
The existing water infrastructure is shown on the assets map provided in Appendix C.
OTHER SERVICES
Electrical and Communications
New electrical and communications would be provided for the proposed development. Investigations show
that a telecommunications service (Telstra) is located underground in the Bartlett Road road reserve. NBN is
also available in the same location.
An underground electrical service is also located in Bartlett Road in the north west corner of the site. Overhead
power is available from this location and runs along the frontage to the east. It is expected that the connection
locations and any additional infrastructure will be included as part of the detailed design by an appropriate
Electrical/Communications engineer.
All electrical and communication services would be provided in accordance with the relevant authority and
standards. The existing infrastructure is shown on the Telstra cable plan (Sequence Number: 205962432), the
NBN network plan and the Energex DBYD plan ((Sequence Number: 205962429) provided in Appendix D.
Gas
No gas mains were identified in the vicinity as part of the service investigation undertaken for the site.
Page 10 of 12
2261 david low way, peregian beach, qld 4573 acn: 626 671 092 [email protected]
Page 11
CONCLUSION
The report has reviewed the engineering constraints identified as part of the proposed development. It is
generally in accordance with the Noosa Planning Scheme and other relevant standards and codes.
It is anticipated the report, when reviewed in conjunction with the planning report and the development plans;
will assist in supporting the application seeking approval for a Material Change of Use.
Yours Faithfully,
GLENN AINSWORTH
MIEAust CPEng NER RPEQ CPESC
BAX ENGINEERING PTY. LTD.
Ph: 0407 021 300
Page 11 of 12
2261 david low way, peregian beach, qld 4573 acn: 626 671 092 [email protected]
Page 12
REFERENCES
Proposed Building Design
Prepared by Sprout Architects (Document No: 21010) dated 04.11.21
NC Council – Relevant Codes and Standards
Planning Scheme Codes
Planning Scheme Codes - Word Version – NoosaCouncil
DBYD – Service Locations
https://www.1100.com.au/
Queensland Globe – Site Mapping
https://qldglobe.information.qld.gov.au/
Page 12 of 12
2261 david low way, peregian beach, qld 4573 acn: 626 671 092 [email protected]
Page 13
APPENDIX A
Building Plans
Prepared by Sprout Architects dated November, 2021
[OCR of page images]
APPENDIX A
Building Plans
Prepared by Sprout Architects dated November, 2021
Page 14
&3
63
%$57/(7752$'
53
:DWHU0DLQOLQHSORWWHGIURPUHFR
7HOVWUD1%1OLQHSORWWHGIURPUHFR
6HZHUOLQHSORWWHGIURPUHFRUGV
&3
63
*5281'/(9(/
6FDOH
6FDOH
5(9 '(6&5,37,21 '5$:1 '$7(
SURMHFW GUDZLQJ
3 35(/,0,1$5<,668( 11
352326('1(:,1'8675,$/ *5281'/(9(/)/2253/$1
3 35(/,0,1$5<,668( 11
681&2$675(6257%86,1(66&(175( :$5(+286(6
68,7(&15*$5'$.67 685)5' &RS\ULJKWRIWKLVGRFXPHQWUHPDLQVWKHH[FOXVLYH
IRU SURSHUW\RI635287$5&+,7(&7637</7'
$/(;$1'5$+($'/$1' 4OG -8./237</7' $%1
32%2;0$522&+<'25(%& 4OG GDWH GUDZQ 11 VFDOH $66+2:1 &RQWUDFWRUVDUHWRYHULI\DOOGLPHQVLRQVDQGOHYHOVRQ
3+ )$; DW #$
1
VLWHSULRUWRFRPPHQFLQJ5HSRUWDOOGLVFUHSDQFLHVWR
$%1 %$57/(7752$' WKH$UFKLWHFW8VHILJXUHGGLPHQVLRQVLQSUHIHUHQFH
WRVFDOHG
(0$,/DGPLQ#VSURXWDUFKFRPDX 1226$9,//( GUDZLQJQR 6' UHYLVLRQ $
[OCR of page images]
|
l Existing building cp
| ‘SP105411
|
| Caretaker
e|
2 ~Linie of mezzanine Toor over”
Tenancy 1
re)
b5.|
Existing stormwater
Line of
4 mezzanine
ao floor over ~
4 S|
oJ Tenancy 2/
os, | RP173566
NBN
3 Tenancy 3 Line df mezzanine floor ove!
| a Entry
l
I
l
3
cP
SP226614
Existing building
GROUND LEVEL
‘Seale 1:200
REV DESCRIPTION DRAWN DATE
Pi PRELIMINARY ISSUE NN 729021
P2 PRELIMINARY ISSUE NN stot
SUNCOAST RESORT BUSINESS
SUITE 2 CNR GARDAK ST & SURF RD
ALEXANDRA HEADLAND
PO BOX 6232 MAROOCHYDORE BC
PH: 7 5443 5028 F
s
180°03'
-AX07 8479 2500
ABN 23.123 917 724
EMAIL: [email protected] au
‘sp10084 Woy
128 VCr
a7 |
[ |
/ |
/, Powdercoated
aluminium
‘over masonry wall
Temp bin /
collection,
4
Z
W
z
Signage and
letterboxes
S| (ee lie 7,
/
co
iS
Oo
Motorised
Powdercoated
aluminium,
sliding entry gate
oul) NEN/ENSIOL,
0081 Woy panoid eu UEW JEM,
pal WOH
Scale 1:200 a a
0 5 10 20
" project raning
PROPOSED NEW INDUSTRIAL
WAREHOUSES.
for
JUKLO PTY LTD
9 BARTLETT ROAD
| NOOSAVILLE
GROUND LEVEL FLOOR PLAN
date 4/14/2021 drawn NN scale As sHoWN Conraor art very al menos sn avel on
rauing no.21010 SDO1 revision A.
Page 15
&3
63
%$57/(7752$'
3
53
&3
63
0(==$1,1(/(9(/
6FDOH
6FDOH
5(9 '(6&5,37,21 '5$:1 '$7(
SURMHFW GUDZLQJ
3 35(/,0,1$5<,668( 11
352326('1(:,1'8675,$/ 0(==$1,1(/(9(/3/$1
3 35(/,0,1$5<,668( 11
681&2$675(6257%86,1(66&(175( :$5(+286(6
68,7(&15*$5'$.67 685)5' &RS\ULJKWRIWKLVGRFXPHQWUHPDLQVWKHH[FOXVLYH
IRU SURSHUW\RI635287$5&+,7(&7637</7'
$/(;$1'5$+($'/$1' 4OG -8./237</7' $%1
32%2;0$522&+<'25(%& 4OG GDWH GUDZQ 11 VFDOH $66+2:1 &RQWUDFWRUVDUHWRYHULI\DOOGLPHQVLRQVDQGOHYHOVRQ
3+ )$; DW #$
1
VLWHSULRUWRFRPPHQFLQJ5HSRUWDOOGLVFUHSDQFLHVWR
$%1 %$57/(7752$' WKH$UFKLWHFW8VHILJXUHGGLPHQVLRQVLQSUHIHUHQFH
WRVFDOHG
(0$,/DGPLQ#VSURXWDUFKFRPDX 1226$9,//( GUDZLQJQR 6' UHYLVLRQ $
[OCR of page images]
Existing building
Balcony
14.5 m®
Feature aluminium-
framed sun hoods
Existing building
MEZZANINE LEVEL
‘Scale 7-200
Caretaker
Bed
Tenancy 1
Void
Tenancy 2
Void
Tenancy 3
Void
REV DESCRIPTION DRAWN DATE
‘PRELIMINARY ISSUE NN 2021
P2 PRELIMINARY ISSUE NN stot
A
Tenancy 1
Mezzanine
30.5 m2
Signage above
roller door
Tenancy 3
Mezzanine
Balcony
13.0 me
48
|
— Line of roof over RP 473566
Tenancy 3
Mezzanine
180°03'
SUITE 2 CNR GARDAK ST & SURF RD
ADI
ALEXANDRA HEADLAND
PO BOX 6232 MAROOCHYDORE BC
PH: 7 5443 5028 F
s
SUNCOAST RESORT BUSINESS
c
RCHITECT
Driveway
below
Scale 1:200
Driveway
Crossover
20
ABN 23.123 917 724
EMAIL: [email protected] au
project
PROPOSED NEW INDUSTRIAL
WAREHOUSES.
for
JUKLO PTY LTD
9 BARTLETT ROAD
| NOOSAVILLE
‘raming
MEZZANINE LEVEL PLAN
date 4/11/2021 drawn NN scale As SHOWN
rauing no.21010 $DO2 revision A.
Copy fi acuant emai the xcve
eas ete erty a enon: reap
Page 16
&3
63
RYHUKDQJ
53
RYHUKDQJ
53
&3
63
522)
6FDOH
6FDOH
5(9 '(6&5,37,21 '5$:1 '$7(
SURMHFW GUDZLQJ
3 35(/,0,1$5<,668( 11
352326('1(:,1'8675,$/ 522)3/$1
3 35(/,0,1$5<,668( 11
681&2$675(6257%86,1(66&(175( :$5(+286(6
68,7(&15*$5'$.67 685)5' &RS\ULJKWRIWKLVGRFXPHQWUHPDLQVWKHH[FOXVLYH
IRU SURSHUW\RI635287$5&+,7(&7637</7'
$/(;$1'5$+($'/$1' 4OG -8./237</7' $%1
32%2;0$522&+<'25(%& 4OG GDWH GUDZQ 11 VFDOH $66+2:1 &RQWUDFWRUVDUHWRYHULI\DOOGLPHQVLRQVDQGOHYHOVRQ
3+ )$; DW #$
1
VLWHSULRUWRFRPPHQFLQJ5HSRUWDOOGLVFUHSDQFLHVWR
$%1 %$57/(7752$' WKH$UFKLWHFW8VHILJXUHGGLPHQVLRQVLQSUHIHUHQFH
WRVFDOHG
(0$,/DGPLQ#VSURXWDUFKFRPDX 1226$9,//( GUDZLQJQR 6' UHYLVLRQ $
[OCR of page images]
cP
‘SP105411
Existing building
4 0°03"
oe Oo pp
yg |
y I
+ |
|
|
|
el
3 |
o| nv
gle
os
|e
| s
g 2
a rT | Ee
“| &
33 e
RP228902 g |
aj
|
4 |
| 48
a | RP173566
|
oh |
|
2
3 |
4+ o4
8
cP
SP226614
Existing building
(ROOF
7 ‘Scale 1:200
Rev _DESCRIFTON DRAWN DATE
Pi PRELWMARY SUE mi er02t
Pe PRELIMINARY sSUE sw tetnot
SUNCOAST RESORT BUSINESS _ CENTRE
SUITE 2 CNR GARDAK ST & SURF RD
ALEXANDRA HEADLAND Qld 4572
@
R
ARCHITECTS ABN (23123 917 724
fhe sone
Scale 1:200
5 10 20
pie toning
PROPOSED NEW INDUSTRIAL ROOF PLAN
WAREHOUSES
to coe esermsentntss
JUKLO PTY LTD (ABN 23 123 917 724.
date 4/11/2021 crown NN sce svown cores sen on
9 BARTLETT ROAD
| NOOSAVILLE
rauing no.21010 $D03 revision A.
Page 17
6287+(/(9$7,21
6FDOH
([LVW72:
5/
:(67(/(9$7,21
6FDOH
6FDOH
5(9 '(6&5,37,21 '5$:1 '$7(
SURMHFW GUDZLQJ
3 35(/,0,1$5<,668( 11
352326('1(:,1'8675,$/ (/(9$7,216
3 35(/,0,1$5<,668( 11
681&2$675(6257%86,1(66&(175( :$5(+286(6
68,7(&15*$5'$.67 685)5' &RS\ULJKWRIWKLVGRFXPHQWUHPDLQVWKHH[FOXVLYH
IRU SURSHUW\RI635287$5&+,7(&7637</7'
$/(;$1'5$+($'/$1' 4OG -8./237</7' $%1
32%2;0$522&+<'25(%& 4OG GDWH GUDZQ 11 VFDOH $66+2:1 &RQWUDFWRUVDUHWRYHULI\DOOGLPHQVLRQVDQGOHYHOVRQ
3+ )$; DW #$
VLWHSULRUWRFRPPHQFLQJ5HSRUWDOOGLVFUHSDQFLHVWR
$%1 %$57/(7752$' WKH$UFKLWHFW8VHILJXUHGGLPHQVLRQVLQSUHIHUHQFH
WRVFDOHG
(0$,/DGPLQ#VSURXWDUFKFRPDX 1226$9,//( GUDZLQJQR 6' UHYLVLRQ $
[OCR of page images]
v
S
&
Ss
e
5
3
8.
©
ao
Site boundan
Tenancy 1 Tenancy 2 tenancy 3
9,500 9,900
Selected metal roof Powdercoated
Landecape Void. sheeting over steel rafters aluminium-louvre Select paint finish
glass windows tlt panels,
Top of Root
RL26.060
We rs
g Select feature metal
2 wall cladding Reinforced concrete tilt
See r panels 50mm off
Pea FC cladding [Eaumsy
WS SS = = tobalustrade < ee
3 Retain existing Retain existing
| — Ground Level boundary wall boundary wall
RL 18.500
jw ee
Powdercoated aluminium Powdercoated |
sliding doors aluminium-tramed
roller shutter door I
(_\ SOUTH ELEVATION
Mezzanine Level
RL 21.900
_/ ‘Scale 1200
2
§ I>
3 g
2 8
3 <
Sl 13
@ 8
al ig
|
| Selected metal roof |
Top of Root a BSmheightlimit = sheeting over steel rafters
azo EE HH Hf HR +-—-
4 Ww - - - - - ~ - - - - - - = - - _ - - - - - ~e - a
|
y
g \
4 Exist. TOW
RL22.147 |
y
Carpark
A A _| * |
3,015 5.400 6,600 5,400 L Reinforced concrete tilt- Retain existing boundary wall. J |
up panels to boundary
|
Bollard
Ground Level
RL 18.500
| 3.400 _|
(WEST ELEVATION
CI ‘Scale 7:200
Seale 1:250 | 1
0 10 20 30 50
REV DESCRIPTION DRAWN OATE '
Pi PRELIMINARY ISSUE NN 2x04 rodect crowing
be PREuninaRy ISSUE tN tenor PROPOSED NEW INDUSTRIAL ELEVATIONS
SUNCOAST RESORT BUSINESS CENTRE WAREHOUSES
SUITE 2 CNR GARDAK ST & SURF RD for
ALEXANDRA HEADLAND Q4572 SUKLO PTY LTD /
PH: 07 5443 5028 FAxo7 5479 2560 at we" |
ARCHITECTS 23123917724 9 BARTLETT ROAD \
ABN
EMAL admin@sprouiacheomauy | NOOSAVILLE rowing n0.21010 SDOS revision A
Page 18
APPENDIX B Flood Mapping Noosa Council Mapping [OCR of page images] APPENDIX B Flood Mapping Noosa Council Mapping
Page 19
Noosa Shire Council does not warrant the accuracy of information in this publication and 14/12/2021 any person using or relying upon such information does so on the basis that Noosa Shire Council shall bear no responsibility or liability whatsoever for any errors, faults, 1:4500 defects or omissions in the information.
Page 20
APPENDIX C
Water and Sewer Infrastructure
Unitywater Mapping
[OCR of page images]
APPENDIX C
Water and Sewer Infrastructure
Unitywater Mapping
Page 21
Unitywater Map
11 8
13 18
17 1/17
2/17
13 3/17
22
6
1/11
15 2/11
3/11 19
4/11
4A/11 24
5/11
5A/11
11
17
23
1/7
6/11
7/11
8/11 2/7
9/11 7 1/26
10/11 9 2/26 25
19 16/11 3/7
17/11 3/26
4/7 5
4/26
27
7/7 5/7
6/7 26
5/26
21
29
3 5 9 3/8
7
30
29A 4/8
11
5/8
1
32
31
1/8A
2/8A
34 33
12/14/2021, 8:23:34 PM 1:1,128
0 0.01 0.03 0.05 mi
Water System Valve Sewer Manhole Cadastre
Water Fitting Manhole Base 0 0.02 0.04 0.08 km
Tee Sewer Gravity Main Easement
NPSR, Esri, © OpenStreetMap contributors, HERE, Garmin, USGS
Water Hydrant Reticulation Main Unitywater Operational Area
Hydrant Approved Development Applications
Reticulation Main Unapproved Development Applications
Unitywater
NPSR, Esri, © OpenStreetMap contributors, HERE, Garmin, USGS | © State of Queensland (Department of Natural Resources and Mines), 2016 | Moreton Bay Regional Council 2015. For information and updates, planning scheme amendments or other planning related enquires contact MBRC Strategic Planning
Page 22
APPENDIX D
DBYD Plans
NC, Telstra, NBN and Energex Asset Reports
[OCR of page images]
APPENDIX D
DBYD Plans
NG Telstra, NBN and Energex Asset Reports
Page 23
Sequence No: 205962428
Job No: 31021634
Location: 9 Bartlett Road, Noosaville, QLD 4566
Legend
1
Scale: 1:2050
Expires: 31 Dec 2021
2 DISCLAIMER: While reasonable
measures have been taken to ensure the
accuracy of the information contained in
this plan response, neither Noosa
Council nor PelicanCorp shall have any
liability whatsoever in relation to any
loss, damage, cost or expense arising
from the use of this plan response or the
information contained in it or the
completeness or accuracy of such
information. Use of such information is
Overview subject to and constitutes acceptance of
these terms.
Plans generated 03 Dec 2021 by Pelicancorp TicketAccess Software | www.pelicancorp.com AU.Noosa C (QLD) - Response Plan.docx (16 Mar 2021)
Page 24
Sequence No: 205962428
Job No: 31021634
Location: 9 Bartlett Road, Noosaville, QLD 4566
Legend
Scale: 1:1000
Expires: 31 Dec 2021
DISCLAIMER: While reasonable
measures have been taken to ensure the
accuracy of the information contained in
this plan response, neither Noosa
Council nor PelicanCorp shall have any
liability whatsoever in relation to any
loss, damage, cost or expense arising
from the use of this plan response or the
information contained in it or the
completeness or accuracy of such
information. Use of such information is
Tile No: 1 subject to and constitutes acceptance of
these terms.
Plans generated 03 Dec 2021 by Pelicancorp TicketAccess Software | www.pelicancorp.com AU.Noosa C (QLD) - Response Plan.docx (16 Mar 2021)
Page 25
Sequence No: 205962428
Job No: 31021634
Location: 9 Bartlett Road, Noosaville, QLD 4566
Legend
Scale: 1:1000
Expires: 31 Dec 2021
DISCLAIMER: While reasonable
measures have been taken to ensure the
accuracy of the information contained in
this plan response, neither Noosa
Council nor PelicanCorp shall have any
liability whatsoever in relation to any
loss, damage, cost or expense arising
from the use of this plan response or the
information contained in it or the
completeness or accuracy of such
information. Use of such information is
Tile No: 2 subject to and constitutes acceptance of
these terms.
Plans generated 03 Dec 2021 by Pelicancorp TicketAccess Software | www.pelicancorp.com AU.Noosa C (QLD) - Response Plan.docx (16 Mar 2021)
Page 26
Paper size A3 Map has been designed to be reproduced in colour
All underground cables shall be treated as being energised. Where a cable is located that is For Emergency Situations
not represented on the ENERGEX DBYD map, then ENERGEX shall be contacted immediately. please call 13 19 62
DBYD
Sequence: 205962429
Date: 03/12/2021
Scale: 1:1538
1 2 OVERVIEW
For a full list of Map
Symbols, please
refer to the supplied
DBYD Symbology
Legend page
3 4
AS5488 Category “D” Plan
5 6
DISCLAIMER: While reasonable
measures have been taken to ensure the
accuracy of the information contained in
this plan response, neither Energex nor
PelicanCorp shall have any liability
whatsoever in relation to any loss,
damage, cost or expense arising from
the use of this plan response or the
information contained in it or the
completeness or accuracy of such
information. Use of such information is
This output provides details of the ENERGEX electrical network. As variations map exist no responsibility is incurred by ENERGEX for the subject to and constitutes acceptance of
accuracy or completeness of the information provided. Exact positions of cables and electrical connectivity should be confirmed on site. these terms.
Plans generated 03/12/2021 by Pelicancorp TicketAccess Software | www.pelicancorp.com AU.Energex (QLD) - Response Plan.docx (03 Sep 2021)
Page 27
Paper size A3 Map has been designed to be reproduced in colour
All underground cables shall be treated as being energised. Where a cable is located that is For Emergency Situations
not represented on the ENERGEX DBYD map, then ENERGEX shall be contacted immediately. please call 13 19 62
DBYD
Sequence: 205962429
Date: 03/12/2021
Scale: 1:500
Tile No: 1
For a full list of Map
Symbols, please
refer to the supplied
DBYD Symbology
Legend page
AS5488 Category “D” Plan
DISCLAIMER: While reasonable
measures have been taken to ensure the
accuracy of the information contained in
this plan response, neither Energex nor
PelicanCorp shall have any liability
whatsoever in relation to any loss,
damage, cost or expense arising from
the use of this plan response or the
information contained in it or the
completeness or accuracy of such
information. Use of such information is
This output provides details of the ENERGEX electrical network. As variations map exist no responsibility is incurred by ENERGEX for the subject to and constitutes acceptance of
accuracy or completeness of the information provided. Exact positions of cables and electrical connectivity should be confirmed on site. these terms.
Plans generated 03/12/2021 by Pelicancorp TicketAccess Software | www.pelicancorp.com AU.Energex (QLD) - Response Plan.docx (03 Sep 2021)
Page 28
Paper size A3 Map has been designed to be reproduced in colour
All underground cables shall be treated as being energised. Where a cable is located that is For Emergency Situations
not represented on the ENERGEX DBYD map, then ENERGEX shall be contacted immediately. please call 13 19 62
DBYD
Sequence: 205962429
Date: 03/12/2021
Scale: 1:500
Tile No: 2
For a full list of Map
Symbols, please
refer to the supplied
DBYD Symbology
Legend page
AS5488 Category “D” Plan
DISCLAIMER: While reasonable
measures have been taken to ensure the
accuracy of the information contained in
this plan response, neither Energex nor
PelicanCorp shall have any liability
whatsoever in relation to any loss,
damage, cost or expense arising from
the use of this plan response or the
information contained in it or the
completeness or accuracy of such
information. Use of such information is
This output provides details of the ENERGEX electrical network. As variations map exist no responsibility is incurred by ENERGEX for the subject to and constitutes acceptance of
accuracy or completeness of the information provided. Exact positions of cables and electrical connectivity should be confirmed on site. these terms.
Plans generated 03/12/2021 by Pelicancorp TicketAccess Software | www.pelicancorp.com AU.Energex (QLD) - Response Plan.docx (03 Sep 2021)
Page 29
Paper size A3 Map has been designed to be reproduced in colour
All underground cables shall be treated as being energised. Where a cable is located that is For Emergency Situations
not represented on the ENERGEX DBYD map, then ENERGEX shall be contacted immediately. please call 13 19 62
DBYD
Sequence: 205962429
Date: 03/12/2021
Scale: 1:500
Tile No: 3
For a full list of Map
Symbols, please
refer to the supplied
DBYD Symbology
Legend page
AS5488 Category “D” Plan
DISCLAIMER: While reasonable
measures have been taken to ensure the
accuracy of the information contained in
this plan response, neither Energex nor
PelicanCorp shall have any liability
whatsoever in relation to any loss,
damage, cost or expense arising from
the use of this plan response or the
information contained in it or the
completeness or accuracy of such
information. Use of such information is
This output provides details of the ENERGEX electrical network. As variations map exist no responsibility is incurred by ENERGEX for the subject to and constitutes acceptance of
accuracy or completeness of the information provided. Exact positions of cables and electrical connectivity should be confirmed on site. these terms.
Plans generated 03/12/2021 by Pelicancorp TicketAccess Software | www.pelicancorp.com AU.Energex (QLD) - Response Plan.docx (03 Sep 2021)
Page 30
Paper size A3 Map has been designed to be reproduced in colour
All underground cables shall be treated as being energised. Where a cable is located that is For Emergency Situations
not represented on the ENERGEX DBYD map, then ENERGEX shall be contacted immediately. please call 13 19 62
DBYD
Sequence: 205962429
Date: 03/12/2021
Scale: 1:500
Tile No: 4
For a full list of Map
Symbols, please
refer to the supplied
DBYD Symbology
Legend page
AS5488 Category “D” Plan
DISCLAIMER: While reasonable
measures have been taken to ensure the
accuracy of the information contained in
this plan response, neither Energex nor
PelicanCorp shall have any liability
whatsoever in relation to any loss,
damage, cost or expense arising from
the use of this plan response or the
information contained in it or the
completeness or accuracy of such
information. Use of such information is
This output provides details of the ENERGEX electrical network. As variations map exist no responsibility is incurred by ENERGEX for the subject to and constitutes acceptance of
accuracy or completeness of the information provided. Exact positions of cables and electrical connectivity should be confirmed on site. these terms.
Plans generated 03/12/2021 by Pelicancorp TicketAccess Software | www.pelicancorp.com AU.Energex (QLD) - Response Plan.docx (03 Sep 2021)
Page 31
Paper size A3 Map has been designed to be reproduced in colour
All underground cables shall be treated as being energised. Where a cable is located that is For Emergency Situations
not represented on the ENERGEX DBYD map, then ENERGEX shall be contacted immediately. please call 13 19 62
DBYD
Sequence: 205962429
Date: 03/12/2021
Scale: 1:500
Tile No: 5
For a full list of Map
Symbols, please
refer to the supplied
DBYD Symbology
Legend page
AS5488 Category “D” Plan
DISCLAIMER: While reasonable
measures have been taken to ensure the
accuracy of the information contained in
this plan response, neither Energex nor
PelicanCorp shall have any liability
whatsoever in relation to any loss,
damage, cost or expense arising from
the use of this plan response or the
information contained in it or the
completeness or accuracy of such
information. Use of such information is
This output provides details of the ENERGEX electrical network. As variations map exist no responsibility is incurred by ENERGEX for the subject to and constitutes acceptance of
accuracy or completeness of the information provided. Exact positions of cables and electrical connectivity should be confirmed on site. these terms.
Plans generated 03/12/2021 by Pelicancorp TicketAccess Software | www.pelicancorp.com AU.Energex (QLD) - Response Plan.docx (03 Sep 2021)
Page 32
Paper size A3 Map has been designed to be reproduced in colour
All underground cables shall be treated as being energised. Where a cable is located that is For Emergency Situations
not represented on the ENERGEX DBYD map, then ENERGEX shall be contacted immediately. please call 13 19 62
DBYD
Sequence: 205962429
Date: 03/12/2021
Scale: 1:500
Tile No: 6
For a full list of Map
Symbols, please
refer to the supplied
DBYD Symbology
Legend page
AS5488 Category “D” Plan
DISCLAIMER: While reasonable
measures have been taken to ensure the
accuracy of the information contained in
this plan response, neither Energex nor
PelicanCorp shall have any liability
whatsoever in relation to any loss,
damage, cost or expense arising from
the use of this plan response or the
information contained in it or the
completeness or accuracy of such
information. Use of such information is
This output provides details of the ENERGEX electrical network. As variations map exist no responsibility is incurred by ENERGEX for the subject to and constitutes acceptance of
accuracy or completeness of the information provided. Exact positions of cables and electrical connectivity should be confirmed on site. these terms.
Plans generated 03/12/2021 by Pelicancorp TicketAccess Software | www.pelicancorp.com AU.Energex (QLD) - Response Plan.docx (03 Sep 2021)
Page 33
To: Glenn Ainsworth Phone: Not Supplied Fax: Not Supplied Email: [email protected] Dial before you dig Job #: 31021634 Sequence # 205962430 Issue Date: 03/12/2021 Location: 9 Bartlett Road , Noosaville , QLD , 4566 Indicative Plans
Page 34
LEGEND Parcel and the location Pit with size “5” Power Pit with size “2E”. Valid PIT Size: e.g. 2E, SE, 6E, SE, 9E, E, null. Manhole Pillar Cable count of trench is 2. One “Other size” PVC conduit (PO) owned by Telstra (-T-), between pits of sizes, “S” and “S" are 25.0m apart. One 40mm PVC conduit (P40) owned by NBN, between pits of sizes, “5” and “9” are 20.0m apart. 2 Direct buried cables between pits of sizes ,"5" and "9" are 10,0m apart. Trench containing any INSERVICE/CONSTRUCTED (Copper/RF/Fibre) cables. Trench containing only DESIGNED/PLANNED (Copper/RF/Fibre/Power) cables. Trench containing any |NSERVICE/CONSTRUCTED (Power) cables. BROADWAY ST Road and the street name “Broadway ST” Scale 0 20 40 60 Meters 1:2000 lees
Page 35
Ls ene ST 1 PO Lou Soe, dot on
Page 36
Emergency Contacts You must immediately report any damage to the nbn™ network that you are/become aware of. Notification may be by telephone - 1800 626 329.
Page 37
Cable Plan
U1
N
U2
U3
U4
91.4
U5
U6
U7
U8
6-8
W E
P35 18.4
5
OC[13m
m ]
S
]
mm
m] [ 10 27.3
OC[ 4m OC5
P3
10
7
OC
[ 6m
m
]
P3 12
P35
2
P1
OP
OC
SHO
[10
SHO
SH
mm
]
9
14
P3OC[1
5
13
0m
m
32 ]
16
.0
11
18
2
U1 U
13
8
P3
5
U1
OC
20
U2
[12
U3
mm
11
MC
U4
35
]
U4A
.6
P35
U5
34.0
15
U5A OC[
13m
22
P35 10.0 m]
2
5
P3
OC[10mm] 1
5
30.3
6
OC
P35 24.2
OC[ mm]
m]
[10
OC[10mm]
OC
P3
10m
23
mm
24
5
[12
10
OC[
MC
OC[
]
mm
0
17
10m
27
.0
P35 m]
]
BAR
.2
52.0 2
TLE 28.0
5
TT
P50 m] OC[
OC[14m P35 17m
m]
U6 61.5 2
0
U7
45.
.6 2 RD
]
]
mm
U8
11 m
0m
U9
OC[10mm]
5
[23
3 [1
P3
U10
MC 10.1
C U1 P35 15.3 OC[
MC 16m
OC
U11
O m]
MC
5 U17 U2 OC[16mm]
U16 OC[10mm] 62.2
P5
13m m]
2xO 3mm]
U3 SHO
m]
m
U4
7
C[16
2
U4
OC[
5
OC[
9
9
26
U3
32.5
m]
U7 U6
16m
7
U5 P3
P35
5 P35
U2
OC[
OC
[13 3
5 mm 0.0
]
U1
5
]
30
L37
6mm
]
6mm
P50
33.7
2.0
]
6mm
OC[ P35
OC[
10m
OC[
m]1
60.0
5
OC[
E ST
P35 31.5
OC P3 OC
11
3 P3 5 [10
P3
P35
] 2 5 [10
2xOC[ 4mm]
4mm mm
5xOC[
REN
42.0
3xO
mm
OC[ mm]
5
U3
]
OC[ mm]
34 ]
m]
.6
P35
20.0
C[
32
13m
23
22
16
U2
5
P35 22
4m
OC[
.0
.0 35.0
CT OC[ 4 P35
m
3 mm] OC[13mm]
]
OC[ 6mm]
U1
m]
2
26.0
P50 19.3
13m
MC
OC[ 6mm]
OC[ 6mm]
OC[ 4mm]
OC[ 6mm]
30.0
OC[
OC[12mm] P35 m]
34
m
OC
L39
C [1 0
P35
O
3
OC[ mm]
[ 4m
OC
13m ]
U1
m
m]
0m
OC [220m
10m 30m 40m 2xO 50m 60m
16m
3m C[ 6
m]
23
OC [13m m]
8
24.0
mm
]
25.0
OC[
[10 m]
OC[
mm
]
For all Telstra DBYD plan enquiries - Sequence Number: 205962432
email - [email protected]
For urgent onsite contact only - ph 1800 653 935 (bus hrs) CAUTION: Fibre optic and/ or major network present
TELSTRA CORPORATION LIMITED A.C.N. 051 775 556
in plot area. Please read the Duty of Care and
contact Telstra Plan Services should you require
Generated On 03/12/2021 14:01:12 any assistance.
The above plan must be viewed in conjunction with the Mains Cable Plan on the following page
WARNING - Due to the nature of Telstra underground plant and the age of some cables and records, it is impossible to ascertain the precise location of all Telstra plant from Telstra's plans. The accuracy and/or
completeness of the information supplied can not be guaranteed as property boundaries, depths and other natural landscape features may change over time, and accordingly the plans are indicative only.
Telstra does not warrant or hold out that its plans are accurate and accepts no responsibility for any inaccuracy shown on the plans.
It is your responsibility to locate Telstra's underground plant by careful hand pot-holing prior to any excavation in the vicinity and to exercise due care during that excavation.
Please read and understand the information supplied in the duty of care statement attached with the Telstra plans. TELSTRA WILL SEEK COMPENSATION FOR LOSS CAUSED BY DAMAGE TO ITS PLANT.
Telstra plans and information supplied are valid for 60 days from the date of issue. If this timeframe has elapsed, please reapply for plans.
Page 1 of 2
Page 38
c2:M2301-2400 100 PIUT (AA)
5xOC (AA)
c6:M1201-1400 200/0.40 CPIUT (BA)
DIST (BA) Mains Cable Plan c2:M2301-2340 100 PIUT (AA)
.0
N
20
OC[23mm] (BA) c2:M2341-2400
c2:M1601-1800 200/0.40 PIUT (AA) W E
c10:M1201-1400 200/0.40 CPFUT (AA) AD
B19 c6:M1401-1600 200/0.40 PIUT (AA)
3004:AW-CP/1-36 36F/- SMOF FNPEHJ/STD (AB) AC
S
3002:AW-CP/1-12 12F/- SMOF FNPEHJC/STD (AB) AB
AA
3002:AW-B19/1-12 12F/- SMOF FNPEHJ/STD (AA)
AA
P35 OC[16mm] (AA) P100
c2:M2101-2150 50/0.40 CPFUT <- (AA) AA
3002:CP-B39/1-12 12F/- SMOF FNPEHJC/STD (AA)
P100
3004:CP-B58/1-12 12F/- SMOF SM@RTCORE (AA) AA
P100
3004:CP-CR/1-36 36F/- SMOF FNPEHJ/STD (AA) AA
2xOC (AA)
P100
3004:CP-B58/1-12 12F/- SMOF SM@RTCORE (AA) AA
2xOC (AA) P50
5
3004:CP-B58/1-12 12F/- SMOF SM@RTCORE (AA) AA
2xOC (AA) P35
30.3
BAR
TLE
TT
5
2 RD
3004:CP-B58/1-12 12F/- SMOF SM@RTCORE (AA) AA
45.0
OC[10mm] (AA) P35 62.2
10.1
25.0
85.0
5
3004:CP-B58/1-12 12F/- SMOF SM@RTCORE
3004:CP-B58/1-12 12F/- SMOF SM@RTCORE (AA) AA
OC[16mm] (AA) P35
5
E ST
REN
42.0
CT
3
0m 10m 20m 30m 40m 50m 60m
24.0
For all Telstra DBYD plan enquiries - Sequence Number: 205962432
email - [email protected]
For urgent onsite contact only - ph 1800 653 935 (bus hrs) CAUTION: Fibre optic and/ or major network present
TELSTRA CORPORATION LIMITED A.C.N. 051 775 556
in plot area. Please read the Duty of Care and
contact Telstra Plan Services should you require
Generated On 03/12/2021 14:01:14 any assistance.
WARNING - Due to the nature of Telstra underground plant and the age of some cables and records, it is impossible to ascertain the precise location of all Telstra plant from Telstra's plans. The accuracy and/or
completeness of the information supplied can not be guaranteed as property boundaries, depths and other natural landscape features may change over time, and accordingly the plans are indicative only.
Telstra does not warrant or hold out that its plans are accurate and accepts no responsibility for any inaccuracy shown on the plans.
It is your responsibility to locate Telstra's underground plant by careful hand pot-holing prior to any excavation in the vicinity and to exercise due care during that excavation.
Please read and understand the information supplied in the duty of care statement attached with the Telstra plans. TELSTRA WILL SEEK COMPENSATION FOR LOSS CAUSED BY DAMAGE TO ITS PLANT.
Telstra plans and information supplied are valid for 60 days from the date of issue. If this timeframe has elapsed, please reapply for plans.
Page 2 of 2