Page 1

  Report number - 9247D938-B19E-4B10-A329-476931F159EB-1636510345




         Dilapidation Inspection
         Report
         Inspection Date: 10 Nov 2021
         Property Address: 35 Wyuna Drive Noosaville 4566
Full text of the other 34 pages

Page 2

Page 2




         Contents

         Inspection Details                                                                                                      3

         General description of property                                                                                         4

         Accessibility                                                                                                           5

         Summary                                                                                                                 6

         Significant Items                                                                                                       7

         Additional comments                                                                                                     7

         Conclusion                                                                                                            33

         Terms on which this report was prepared                                                                               33

         If you have any queries with this report or require further information, please do not hesitate to contact the person who
         carried out the inspection.

Page 3

Page 3




         Inspection Details
         Property Address:                35 Wyuna Drive Noosaville 4566



         Date:                            10 Nov 2021



         Client

         Name:                            Mick Devlin ( Braeden Constructions)



         Email Address:                   [email protected]



         Phone Number:                    0418505117



         Consultant

         Name:                            Steve Wilson



         Email Address:                   [email protected]



         Licence / Registration Number:   QBCC 15011540



         Company Name:                    Pams Home Services Pty Ltd T/A Building Inspections Noosa



         Company Address:                 Noosa Heads QLD 4567



         Company Phone Number:            0499093959

Page 4

Page 4




         General description of property
         Building Type:                                    Detached house



         Storeys:                                          Two storey



         Siting of the building:                           Towards the middle of a large block



         Gradient:                                         The land is gently sloping



         Site drainage:                                    The site appears to be adequately drained



         Orientation of the property:                      Not relevant for this report.
                                                           Note. For the purpose of this report the façade of the building contains
                                                           the main entrance door.



         Weather conditions:                               Showers



         Primary method of construction

         Main building – floor construction:               Slab on ground, Part suspended timber framed and slab-on-ground



         Main building – wall construction:                Concrete block, Finished with render



         Main building – roof construction:                Concrete structure part metal roof



         Special conditions or instructions

         Special requirements, requests or instructions given by the client or the client's representative -

         There are no special conditions or instructions

Page 5

Page 5




         Accessibility
         Areas Inspected
         The inspection covered the Readily Accessible Areas of the property.

         - Building exterior
         - Building interior
         - The site
         - Part roof surface due to height above 3.6 metres




         Obstructions and Limitations
         The following obstructions may conceal defects:

         - Built-in cupboards
         - Curtains / blinds
         - Floor coverings
         - Furniture
         - Thick foliage
         - Vegetation
         - Painted surfaces can cover defects on surfaces inspected.

         Obstructions increase the risk of undetected defects, please see the overall risk rating for undetected defects.


         Inaccessible Areas
         The following areas were inaccessible:

         - Wall cavity.
         - External roof surface partial inspection via ladder up to 3.6metres around the perimeter of the house.

         Any areas which are inaccessible at the time of inspection present a high risk for undetected building defects. The
         client is strongly advised to make arrangements to access inaccessible areas urgently.

Page 6

Page 6




         Summary
         SUMMARY INFORMATION: The summary below is used to give a brief overview of observations made in each
         inspection area. The items listed in the summary are noted in detail under the applicable sub headings within the body
         of the report. The summary is NEVER to be relied upon as a comprehensive report and the client MUST read the entire
         report and not rely solely on this summary. If there is a discrepancy between the information provided in this summary
         and that contained within the body of the Report, the information in the body of the Report shall override this summary.
         (See definitions & information below the summary to help understand the report)


         Evidence of Safety Hazard                                                                                Not Found


         Evidence of Major Defect                                                                                 Not Found


         Evidence of Minor Defect                                                                                 Not Found




         Additional specialist inspections
         The following inspections / reports are recommended


         Not Applicable

Page 7

Page 7




         Significant Items

         Safety Hazard
         No evidence was found


         Major Defect
         No evidence was found


         Minor Defect
         No evidence was found




         Additional comments
         There are no additional comments


         For your information

         For your information 4.01

         Location:            All External Areas
         Finding:             Additional Photos
                              Defects found under a classification of minor or maintenance are identified for the purpose of a
                              Dilapidation report to identify defects prior to demolition of a neighbouring building.

                              Additional photos are provided for your general reference. Any comments on the photos are to
                              clarify the captured photo. No comment on the photo is because it will be an expansion/ follow
                              on from the previous one or there is no defect or concern as it currently stands.

Page 8

Page 8

Page 9

Page 9

Page 10

Page 10

Page 11

Page 11

Page 12

Page 12


          For your information 4.02

          Location:      All Internal Areas
          Finding:       Additional photos are provided for your general reference.
                         Any comments on the photos are to clarify the captured photo. No comment on the photo is
                         because it will be an expansion/ follow on from the previous one or there is no defect or
                         concern as it currently stands.
                         Defects found under a classification of minor or maintenance are identified for the purpose of a
                         Dilapidation report to identify defects prior to demolition of a neighbouring building.

Page 13

Page 13

Page 14

Page 14

Page 15

Page 15


[OCR of page images]
CL RY

 

Page 16

Page 16

Page 17

Page 17


[OCR of page images]
Page

 

Page 18

Page 18

Page 19

Page 19




          For your information 4.03

          Location:      The site
          Finding:       Additional Photos
                         Additional photos are provided for your general reference. Any comments on the photos are to
                         clarify the captured photo. No comment on the photo is because it will be an expansion/ follow
                         on from the previous one or there is no defect or concern as it currently stands.

                         Defects found under a classification of minor or maintenance are identified for the purpose of a
                         Dilapidation report to identify defects prior to demolition of a neighbouring building.

Page 20

Page 20

Page 21

Page 21

Page 22

Page 22




          For your information 4.04

          Location:      Boundary Fence
          Finding:       Additional Photos
                         Additional photos are provided for your general reference. Any comments on the photos are to
                         clarify the captured photo. No comment on the photo is because it will be an expansion/ follow
                         on from the previous one or there is no defect or concern as it currently stands. Defects found
                         under a classification of minor or maintenance are identified for the purpose of a Dilapidation
                         report to identify defects prior to demolition of a neighbouring building.

Page 23

Page 23




          For your information 4.05

          Location:      Identified Cracks, Separation Or Movement
          Finding:       Additional photos are provided for your general reference.
                         Additional photos are provided for your general reference. Any comments on the photos are to
                         clarify the captured photo. No comment on the photo is because it will be an expansion/ follow
                         on from the previous one or there is no defect or concern as it currently stands. Defects found
                         under a classification of minor or maintenance are identified for the purpose of a Dilapidation
                         report to identify defects prior to demolition of a neighbouring building.

Page 24

Page 24


          For your information 4.06

          Location:      Tiled Wet Areas
          Finding:       The additional photos are provide for your information to understand the property and condition.
                         Additional photos are provided for your general reference. Any comments on the photos are to
                         clarify the captured photo. No comment on the photo is because it will be an expansion/ follow
                         on from the previous one or there is no defect or concern as it currently stands. Defects noted
                         in the report where identified under a classification of Minor or maintenance are a reference for
                         comparison for the purpose of a Dilapidation report to identify defects prior to demolition of a
                         neighbouring building.

Page 25

Page 25


[OCR of page images]
Page 25

 

Page 26

Page 26




          For your information 4.07

          Location:      Retaining Wall/ Pool Walls
          Finding:       The additional photos are provide for your information to understand the property condition for
                         the Delapidation report.

                         Defects noted in the report where identified under a classification of Minor or maintenance are a
                         reference for comparison.
                         Any comments on the photos are to clarify the captured photo. No comment on the photo is
                         because it will be an expansion/ follow on from the previous one or there is no defect or
                         concern as it currently stands.
                         Defects found under a classification of minor or maintenance are identified for the purpose of a
                         Dilapidation report to identify defects prior to demolition of a neighbouring building.

Page 27

Page 27

Page 28

Page 28

Page 29

Page 29




          For your information 4.08

          Location:      Roof Ext & Tiled Balconies
          Finding:       Additional Photos
                         Additional photos are provided for your general reference. Any comments on the photos are to
                         clarify the captured photo. No comment on the photo is because it will be an expansion/ follow
                         on from the previous one or there is no defect or concern as it currently stands. Defects found
                         under a classification of minor or maintenance are identified for the purpose of a Dilapidation
                         report to identify defects prior to demolition of a neighbouring building.

Page 30

Page 30

Page 31

Page 31

Page 32

Page 32

Page 33

Page 33




          Conclusion

          Building consultant's summary
          Defects found under a classification of Minor or Major are identified for the purpose of a Dilapidation report to
          identify defects prior to demolition of a neighbouring building.


          Signature of consultant -




          Terms on which this report was prepared
          Service

          1. This agreement is between the building consultant (“Inspector”) and you (“Client”). You have requested the
          Inspector to carry out an inspection of your property for the purpose of preparing a Standard Property Report
          (“Report”) to you outlining their findings and recommendation from the inspection.

          2. The purpose of the inspection is to provide the Client with an overview of the Inspector’s findings at the time of the
          inspection and advice as to the nature and extent of their findings.

          3. This Report has been prepared at the direction of and exclusively for the Client. Details contained within this Report
          are tailored to the Pre-Inspection Agreement between the Inspector and the Client at the time of the Inspection and no
          other party can rely on the Report nor is the Report intended for any other party.

          Scope of the Report

          4. This Report is limited to the findings of the of the Inspector at the time of the inspection and any condition of the
          property which is not within the scope as set out herein or which occurs after the inspection is expressly excluded from
          this Report.

          5. This Report expressly addresses only the following discernible to the Inspector at the time of inspection:
          (a) Major Defects in the condition of Primary Elements including Structural Damage and Conditions Conducive to
          Structural Damage;
          (b) any Major Defect in the condition of Secondary Elements and Finishing Elements and collective (but not individual)
          Minor Defects; and
          (c) any Serious Safety Hazard.

          6. This Report is limited to the observations and conclusions of the Inspector that were readily observable at the
          building or site and given the state of property at the time of the Inspection.

          7. This Report does not include the inspection and assessment of items or matters that are beyond the Inspectors
          direct expertise.

          Inspection Limitations

          8. The Inspection is limited to Readily Accessible Areas of the Building & Site based on the Inspector’s visual

Page 34

Page 34


          examination of surface work (excluding furniture and stored items) and the carrying out of Tests.

          9. Where the Inspection is carried out on a strata or company title property, the Inspection is limited to the interior and
          the immediate exterior of the residence inspected. The Inspection does not extend to common property areas and the
          Inspector will not inspect common property areas.

          10. The Inspector’s findings do not extend to matters where the Inspector was restricted or prevented from assessing
          the building or site as a result of:
          (a) possible concealment of defects, including but not limited to, defects concealed by lack of accessibility, obstructions
          such as furniture, wall linings and floor coverings, or by applied finishes such as render and paint;
          (b) undetectable or latent defects, including but not limited to, defects that may not be apparent at the time of
          inspection due to seasonal changes, recent or prevailing weather conditions, and whether or not services have been
          used some time prior to the inspection being carried out; and
          (c) areas of the building or site that were obstructed at the time of the inspection or not Readily Accessible Areas of the
          Building Site. An obstruction may include a condition or physical limitation which inhibits or prevents inspection and
          may include – but are not limited to – roofing, fixed ceilings, wall linings, floor coverings, fixtures, fittings, furniture,
          clothes, stored articles/materials, thermal insulation, sarking, pipe/duct work, builder’s debris, vegetation, pavements or
          earth.

          Exclusions

          11. This Report does not consider or deal with the following:
          (a) any individual Minor Defect;
          (b) solving or providing costs for any rectification or repair work;
          (c) the structural design or adequacy of any element of construction;
          (d) detection of wood destroying insects such as termites and wood borers;
          (e) the operation of fireplaces and chimneys;
          (f) any services including building, engineering (electronic), fire and smoke detection or mechanical;
          (g) lighting or energy efficiency;
          (h) any swimming pools and associated pool equipment or spa baths and spa equipment or the like;
          (i) any appliances or white goods including dishwashers, refrigerators, ovens, stoves and ducted vacuum systems;
          (j) a review of occupational, health or safety issues such as asbestos content, the provision of safety glass or the use of
          lead based paints;
          (k) a review of environmental or health or biological risks such as toxic mould;
          (l) whether the building complies with the provisions of any building Act, code, regulation(s) or by-laws;
          (m) whether the ground on which the building rests has been filled, is liable to subside, swell or shrink, is subject to
          landslip or tidal inundation, or if it is flood prone; and
          (n) in the case of strata and company title properties, the inspection of common property areas or strata/company
          records.

          12. Should the Client seek information from the Inspector related to one of exclusions above, that information is to be
          provided by way of a Special-Purpose Inspection Report which is adequately specified and must be undertaken by an
          appropriately qualified inspector. Additional information requested by the Client is not included in this Report.

          Workplace Safety

          13. The Client warrants to the Inspector (including the Inspector’s, agents, employees and other personnel) that the
          Building Site is, to the Client’s reasonable knowledge, safe and free of hazardous materials and that no party of the
          Building site constitutes a dangerous environment or work place safety concern.

          Acceptance Criteria

          14. The Inspector may compare the building being inspected with a similar building, unless specified otherwise in the
          Special Conditions or Instructions. The similar building which the Inspector may compare the current building to was, to
          the best of the Inspector’s knowledge, constructed in accordance with ordinary building construction and maintenance
          practices at the time of construction and as such has not encountered significant loss or of strength or serviceability.

          15. The Inspector assumes in their Report that the existing use of the building or site will continue unless specified
          otherwise in the Special Conditions or Instructions.

          Acknowledgments

Page 35

Page 35


          Acknowledgments

          16. The Client Acknowledges that contents of the Report is subject to the Scope of the Report, Inspection Limitations,
          Exclusions and Acceptance Criteria. This Report does not include recommendations or advice about matters outside
          the scope of the requested inspection.

          17. Should the Client have any queries or concerns about the purposes, scope or acceptance criteria on which this
          Report was prepared, all enquiries or concerns are to be discussed with the Inspector within a reasonable time upon
          receipt of this report.

          18. The Client acknowledges that they will take all reasonable steps to implement any recommendation or advice
          provided by the Inspector in their Report as a matter of urgency specified otherwise.

          19. Any further discussions the Inspector following the production of this Report addressing concerns will not be
          reflected in this Report and as such the Report may not contain all advice or information related to the building or site
          provided by the Inspector.

          20. The Client acknowledges that a visual only inspection restricts the Inspectors capacity to inspect the building or site
          thoroughly and is not recommended by the Inspector unless an inspection of the Readily Accessible Areas and
          appropriate tests are also carried out.

          21. The Client Acknowledges that in accordance with the Australian Standard AS4349.0 2007 Inspection of Buildings,
          this Report does not warrant or give insurance that the building or site from developing issues following the date of
          inspection.

          22. The Client acknowledges that the Inspector is not affiliated with Hello Inspections Pty Ltd ACN 620 518 238 (“Hello
          Inspections”) nor is Hello Inspections liable for the content of the Report prepared by the Inspector or any other third
          party and the Client hereby indemnifies Hello Inspections from all claims, losses and damage arising, either directly or
          indirectly, from the Report and the Client accepts this document can be presented to a court as a complete bar to any
          proceedings by the client or its agents or related parties against Hello Inspections. The Client further acknowledges the
          Inspector is the agent for Hello Inspections solely for the purposes of this clause.

          23. The Client acknowledges that Hello Inspections may reproduce the content within this Report for any commercial
          purpose, including sale of the Report in whole or in part to third parties, provided personal details or information of the
          Client contained therein are excluded.

Used in these records

About this file

File size
9.1 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Delapidation 35 Wyuna Drive Noosaville 4566.pdf · 9.1 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.