29228 - CD Issue 1 · OPW20/0072
Attached to the e-mail Operational Works Application OPW20/0072 - New Driveway - 8 Lorikeet Dr Peregian Beach.
DRAWING SIZE — A2
HEIGHT DATUM
ALL STORMWATER
PIPES TO BE LAID AT
GALVANISED KERB ADAPTOR TO LOCAL
AUTHORITY STANDARDS AND IPWEA
INSTALL REECE 'RHS TO PVC
ADAPTOR’ (PROD. CODE 304284),
OR APPROVED EQUIVELANT AS PER
MANUFACTURERS SPECIFICATIONS.
STD. DRG SEQ—RS-081. CUT OUT
LAYBACK KERB AS NECESSARY TO
INSTALL GALVANISED KERB ADAPTOR
WITH NEAT, TIGHT FIT.
\
i
LOTS 718 ON P 93127 Level
Datum AHD
1:100
NOMINAL KERB, |
SETOUT LINE
|
40 110
R20 —
|
|/ 4 2
PAVEMENT LEVEL \f 4 2
‘ re
4 44 44 ae — Nn
“uf ‘ < r -
300/450 150
SECTION ~ TYPE M1 KERB & CHANNEL (RS-080)
REPLACE EXISTING DRAINAGE
FEATURE WITH GRATED
SURCHARGE PIT WITHIN KERB
FORMATION, HEAVY DUTY GALV.
GRATE TO COUNCIL STANDARDS.
NEW DRIVEWAY CROSSOVER
(125mm THK) IN ACCORDANCE
WITH IPWEA STD DRG R-0050
AND COUNCIL REQUIREMENTS.
TYPICAL.
DEMOLISH & REMOVED EXISTING
CROSSOVERS AND RE-CONSTRUCT
STAND-UP KERB TO LOCAL AUTHORITY
STANDARDS & DETAILS. MAINTAIN
POSITIVE FALLS ALONG NEW KERB & s
CHANNEL FOR STORMWATER FLOWS. oY
LEGEND —ypicaL ALL LocaTions.
_--7 INDICATES PROPOSED SURFACE
p07 CONTOURS AND LEVELS TO AHD.
__ 50h» INDICATES FINISHED SURFACE GRADE
CPI 450Sq STORMWATER SURCHARGE PIT,
PRE-CAST CONCRETE. AND HEAVY DUTY
TRAFFICABLE GRATED LID, PROVIDE
2/100 SLOW LEAK PIPES, REFER DETAIL
INDICATES EXISTING SEWER LINE
— Ww INDICATES WATER MAIN APPROX
ALIGNMENT, BUILDER TO CONFIRM EXACT
LOCATION PRIOR TO WORKS
ne INDICATES TELSTRA LINE APPROX
ALIGNMENT, BUILDER TO CONFIRM EXACT
LOCATION PRIOR TO WORKS
INDICATES STORMWATER DRAIN PROPOSED
sw
AS NOTED MIN 1 IN 100 FALL UNLESS
NOTED OTHERWISE
— sw/eEx INDICATES STORMWATER DRAIN EXISTING
AS NOTED
www.dialbeforeyoudig.com.au
DIAL1100
BEFORE YOU DIG
MIN. UNO.
Z yf oe
\\ YQ
2/125x75 x4.0 RHS
H.D. GALV. PIPES ACROSS
M. RCP
—— 97x sy,
EX. 300 DIAM.
12 s°533W.M
eee oO Ex.Water
FOOTPATH/VERGE.
SECTION DETAIL
KERB OUTLET (2) rP
F.H FIRE HYDRANT
TELSTRA PIT
KERB _EXISTING KERBING
STAND-UP KERB ADAPTOR 10
EXISTING KERB DETAIL (RHS).
i Screw
Se RL 14.63
™~ ~, — A vit
ve =a Po
rS eo «—|oo™m™m
= + op i - oe
=r : / “= a os, 4
5B 2 / ‘4 6 ™~— .. S =
i 0 \ “ ~
LS } / POOL. la NN mM
i = \ \ \ ve oN
Is . |
Wie Lot 718 — |
o-___- Pp fowl Y a2
= “ Postar YY JT
es RESIDENTIAL “ nA |
A: DWELLING =~ ~~~ nes
iY 2 NS ~ Pe
bE i OAL i A 4 - oe 38
wat ly | Z :
! mid - - — / x “ / : /
tiaesEX.SMH) 1 | - “fee
ood FEDS Be BO Re “Te 756 T3307 73, }
ee es : ame |
ze
RHS (GALV.) LAID AT 1 in
100 MIN. NUMBER & SIZE AS
| INDICATED. INSTALL TO NEW Lot /19
KERB ADAPTORS AND MAKE
P93127
- FOOTPATH GOOD. TYPICAL. Type BI K & C TO COUNCIL
| | STANDARDS AND IPWEA STD DRG |
RS-081. KERB TO CONTINUE BEHIND
SITE PLAN — STORMWATER MANAGEMENT PLAN NEW KERB SURCHARGE PIT YO Kae
Scale 1: 150 KERB BACK LL ee
ALL SERVICES SHOWN ON THIS PLAN INDICATIVE KERB _TOP eee STORNWATER >
ONLY CONTRACTOR TO LOCATE ALL SERVICES KERE WERT FLOW, 707 FW INFLOW
PRIOR TO COMMENCING WORKS ON SITE. ALL Se 1 be
SERVICES ARE TO BE PROTECTED IN A— 5 BX 3008 ROP ! —~
|
ACCORDANCE WITH THE AUTHORITY RESPONSIBLE
FOR THE SERVICE
ALL PIPES TO BE LAID AT 1 IN 100 MIN.
UNLESS NOTED
KERB EDGE
450 SQ KERB SURCHARGE
INLET. CLASS D WITH
HINGED GALV. GRATE.
REFER IPWEA STD Drg
DS-062.
PROVIDE 2/1006 CLASS 16 PVC
KEY
50 GAP.
Min. _ EX. SWPT EXISTING STORMWATER PIT
RC. HW. REINFORCED CONCRETE HEADWALL
EX. SMH EXISTING SEWER MANHOLE
l EX. SCP EXISTING SEWER CONNECTION POINT
rT + iN Nh + E.0B. EXISTING EDCE OF BITUMEN
| sot thse | K &C EXISTING KERB & CHANNEL
N.SL. NATURAL SURFACE LEVEL
ELECTRICAL POWER POLE
IL TO BE DETERMINED ON SITE.
CONSTRUCTION NOTES
GENERAL;
1. DO NOT SCALE FROM THIS DRAWING.
2. ALL DIMENSIONS IN MILLIMETRES
3. SETTING OUT DIMENSIONS ARE TO BE OBTAINED FROM THE
ARCHITECTURAL DRAWINGS.
4. ANY DISCREPANCIES BETWEEN THESE DRAWING AND THE
ARCHITECTURAL DRAWINGS ARE TO BE REFERRED TO THE ENGINEER
IMMEDIATELY.
5. THE BUILDER IS RESPONSIBLE FOR LOCATING ALL EXISTING SERVICES
WITHIN AND ADJACENT THE ALLOTMENT AND SHALL ENSURE THAT ALL
NEW WORKS ARE IN ACCORDANCE WITH THE ATTACHED CRITICAL DEPTH
LINE DIAGRAM.
HYDRAULICS
1. HYDRAULIC SERVICES SHOWN ARE DIAGRAMATIC ONLY. REFER TO
ARCHITECTURAL DRAWINGS FOR LOCATIONS OF FIXTURES.
2. ALL SANITARY HYDRAULICS AND WATER RETICULATION WITHIN THE
ALLOTMENT BOUNDARY TO BE IN ACCORDANCE WITH AS3500.
3. ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF AUTHORITIES
HAVING JURISDICTION, AFTER OBTAINING ALL NECESSARY PERMITS AND
APPROVALS.
4. THE CONTRACTOR IS TO CONFIRM THE POSITION OF ALL EXISTING
SERVICES AS INDICATED ON THESE AND ASSOCIATED PLANS DO NOT
CLASH WITH THE PROPOSED PIPE WORKS PRIOR TO THE COMMENCING
OF WORK.
5. ALL TRENCH EXCAVATIONS AND CONSTRUCTION TO BE IN ACCORD
WITH WORKPLACE HEALTH & SAFETY 1989 AND ANY AMENDMENTS AND
THE MINE REGULATION ACT.
6. STORMWATER DRAINAGE PIPES SHALL BE LAID AT A MINIMUM GRADE
OF 1 IN 100 U.N.O. JOINS ARE TO BE CONSTRUCTED IN ACCORDANCE
WITH THE MANUFACTURERS REQUIREMENTS. (REFER NOTE 10.)
7. ALL PRECAST CONCRETE PIPES AND TO MANUFACTURED IN ACCORD
WITH AS. 4058.
8. STORMWATER PIPES SHALL BE THE FOLLOWING CLASSES:
8.1. REINFORCED CONCRETE PIPES (RCP) = CLASS 2.
8.2. uPVC 100¢ OR GREATER = CLASS ’SN8’,
8.3. ’STORMPRO’ PIPES = CLASS 'SN8’.
9. ALL RCP PIPES TO HAVE THE FOLLOWING JOINTS U.N.O:
9.1. RCP 6006 OR LESS = RUBBER RING JOINT.
9.2. RCP 600¢ OR GREATER = FLUSH JOINT.
10. ROOF STORMWATER TO DESIGN BY HYDRAULIC CONSULTANTS TO
CLASS SH’ U.N.O.
11. INSTALL SW MANHOLE AND FILED GULLY/INLETS IN ACCORDANCE
WITH AS1657 AND AS DESCRIBED BELOW:
11.1. MANHOLE/FIELD INLETS >1.35m DEEP = STEP IRONS.
11.2. MANHOLES 0.85m—3.0m DEEP = STEP IRONS.
11,3. MANHOLES >3.0m DEEP = FIXED ACCESS LADDER.
12. SEWERS 100mm DIAM. UPVC U.N.O. AND LAID AT A MINIMUM GRADE
OF 1 IN 60.
13. WATER SUPPLY PIPEWORK BELOW GROUND IS TO BE:
13.1. 63mm DIAM. OR LESS — HIGH DENSITY TYPE 50
CLASS 12 POLYETHYLENE
14. ALL ABOVE GROUND AND INTERNAL WATER SUPPLY PIPEWORK TO
BE TYPE B COPPER.
15. WATER SERVICES ARE NOT PERMITTED IN GROUND SLABS AND ALL
JOINS AND CONNECTIONS SHALL BE MADE ABOVE THE SLAB.
16. FIRE HYDRANTS ARE TO BE INSTALLED IN ACCORDANCE WITH
AS2419.1. HOSE REELS ARE TO BE INSTALLED IN ACCORDANCE WITH
AS2441. CLEAN—OUTS, INSPECTION OPENINGS AND CLOSING CAPS
SITUATED IN VEHICULAR OR PEDESTRIAN PAVEMENTS ARE TO BE FITTED
WITH EITHER BRASS OR CAST-IRON COVERS.
17. ALL IN-GROUND VALVES SHALL BE IN ACCORDANCE IN APPROVED
CONCRETE PATH BOXES.
18. ALL WASTE PIPES AND WATER SERVICES PENETRATING SLABS TO BE
WRAPPED IN AN APPROVED FLEXIBLE JOINT JOINT WRAPPING.
19. THE TERM ’SERVICE’ REFERS TO THE MINIMUM INTERNAL PIPE
DIAMETER UNLESS NOTED OTHERWISE.
Date
Revision | Description
issue: FOR APPROVAL
C) Ste
DEBUILD T/A
ABN 40 098 481 299,
Unit 1/11 Project Ave,
Noosa Heads
Ph (07) 5455 5604
email:[email protected]
web:www.scg-engiteers.com
Title) OPERATIONAL WORKS:
baa 4 DOUBLE STACKED SLOW LEAK PIPES #00 SO PRECAST STORMWATER MANAGEMENT PLAN
FOR DRAINAGE AFTER RAIN EVENT SECTION AA CONCRETE, JUNCTION BOX
PLAN VIEW CONNECT TO K & C DOWNSLOPE TO WITH GALVANISED GRATE. Project 8 Lorikeet Dr
APPROVED KERB ADAPTORS, Peregian Beach
Date: Mar 2020 Drawn: TH Desig1: TH
GP1_& KERBING TYPICAL DETAILS Dot sks Vchocea: Brg No. =
rua F$—7____ym1:100 © A2-— 4 REQ 5835 -
| Sion 29228 -SW1.1| .
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
29228 - CD Issue 1.pdfRelated documentApplication case desk ↗
About this file
- File size
- 2.3 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.