RFI - Attachment F - Revised Architectural Plans · MCU25/0053

of 16

Check the original when the exact wording matters.

Plans and drawings: the text below has words only, no drawings.

Log in to see the plans as drawn

Original PDF page 9, section 1. The text section number identifies this passage in the reader.

                                                                                                                                                                                                                                                                   GENERAL NOTES
                                                                                                                                                                                                                                                                   VERIFY ALL DIMENSIONS AND LEVELS BEFORE COMMENCING WORK. DO NOT SCALE FROM DRAWING.

                                                                                                                                                                                                                                                                   COPYRIGHT
                                                                                                                                                                                                                                                                   THE COPYRIGHT OF THESE DOCUMENTS AND ALL WORKS EXECUTED FROM THESE DOCUMENTS
                                                                                                                                                                                                                                                                   SHALL REMAIN THE PROPERTY OF THE ARCHITECT OR ON CREATION VEST IN THE ARCHITECT.
                                                                                                                                                                                                                                                                   THESE DOCUMENTS MAY ONLY BE USED TO PRODUCE THE PROJECT FOR THE CLIENT AND IN THE
                                                                                                                                                                                                                                                                   LOCATION DESCRIBE HEREON

                                                                                                                                                                                                                                                                    7               MCU RFI RESPONSE                                                    22.09.25
                                                                                                                                                                                                                                                                    6               CONSULTANT ISSUE                                                    02.05.25
                                                                                                                                                                                                                                                                    5               CONSULTANT ISSUE                                                    30.04.25
                                                                                                                                                                                                                                                                    4               UPDATED BASEMENT, STRUCTURE                                         11.03.25
                                                                                                                                                                                                                                                                    3               GENERAL UPDATES                                                     30.01.25
                                                                                                                                                                                                                                                                    2               CONSULTANT COORDINATION                                             16.01.25
                                                                                                                                                                                                                                                                    1               STRUCTURAL ENG INFORMATION                                          08.01.25
                                    A                                                                                B                   C                                        A                                                              B         C
                                                                                                                                                                                                                                                                    REV DESCRIPTION                                                                     DATE
                                                                                                                                                                                                                                                                    REVISION SCHEDULE

                                                                                                                                                                                                                                                                    LEGEND
                                                                                                                                                                                                                                                                    CODE                        DESCRIPTION

                                                                                                                                                                                                                                                                    AFG-01                      ALUMINIUM FRAMED GLAZING - TYPE 1
                                                                                                                                                                                                                                                                    AFG-SD1                     ALUMINIUM FRAMED GLAZED SLIDING DOOR - 4-PANEL XXXO
                                                                                                                                                                                                                                                                    AFG-SD2                     ALUMINIUM FRAMED GLAZED SLIDING DOOR - 3-PANEL XXO
                           2005                                            11210                                                  4400             2500
                                                                                                                                                                                                                                                                    AFG-SD3                     ALUMINIUM FRAMED GLAZED SLIDING DOOR - 2-PANEL XO
                         SETBACK                                                                                                                 SETBACK
                                                                                                                                                                                                                                                                    BAL-01                      BALUSTRADE TYPE 1
                                                                                                                                                                                                                                                                    BAL-02                      BALUSTRADE TYPE 2
                                                                                   8M HEIGHT                                                                                                                                                                        BAL-03                      BALUSTRADE TYPE 3
                                                                                                                                                                                                                                                                    CNC-PF                      CONCRETE - PAINT FINISH
                                                                                                                                                                                                                                                                    COL-A                       CONCRE COLUMN - PAINT FINISH
ROOF                                                                                                                                                                                                                                                                RND                         RENDER - PAINT FINISH
RL 9.800
                                                                                                                                                                                                                                                                    SCN-01                      SCREEN - TYPE 1
                                                                                                                                                                                                                                                                    SGG                         SLIDING GLASS GATE
                                                                                                                                                                                                                                                                    SMG                         SLIDING METAL GATE
                                                                                                                                                  SCN-01                                                                                                            SST                         STACKED STONE VENEER
                  3450




01_FIRST FLOOR
RL 6.350
                                                                       AFG-01
                                                                                                                                                      1500
                                                                                                                                                    SETBACK
                                                                                                                                                                                                                           1800 FRONT BOUNDARY
                  3650




                                                                                                                                                                                                                           FENCE AND GATE
                                                                                                                         RND


                                                                                                                                                                                           SGG                 SST                                   SMG
00_GROUND FLOOR
RL 2.700                                                                                                                                                          DFL
                                                                                                                                                              RL 2.400

                                                                                   NATURAL GROUND LINE




                                                                NORTH ELEVATION                                                                                                                      FRONT BOUNDARY ELEVATION
                                                        1       1 : 100
                                                                                                                                                                                                 3   1 : 100




                                                                                                                                                                                                                                                                   GENERAL NOTES:
                                                                                                                                                                                                                                                                   1.         REFER TO ARCHITECTURAL & INTERIOR FINISHES SCHEDULES FOR
                                                                                                                                                                                                                                                                              SYSTEMS, LININGS & FINISHES.
                                                                                                                                                                                                                                                                   2.         ALL WET AREAS TO HAVE WET AREA PLASTERBOARD OR EQUAL.
                                                                                                                                                                                                                                                                   3.         FALLS TO SCREED TO BE PROVIDED TO WET AREAS TO COMPLY WITH
                                                                                                                                                                                                                                                                              AS1428.1 GRADES FOR BATHROOM AND SHOWER FLOORS.
                                                                                                                                                                                                                                                                              UPPERMOST FFL NOTED ONLY.
                                                                                                                                                                                                                                                                   4.         ALL WALLS AND PARTITIONS TO ALLOW FOR STRUCTURAL
                                                                                                                                                                                                                                                                              DEFLECTION AND STRUCTURAL MOVEMENT.
                                        C                              B                                                                     A                                        C                    B                                                   A   5.         REFER TO NCC REPORT & ACOUSTIC REPORT FOR ACOUSTIC
                                                                                                                                                                                                                                                                              REQUIREMENTS. ACOUSTIC LINING TO ALL TIMBER FLOORS.
                                                                                                                                                                                                                                                                   6.         REFER TO NCC REPORT & ESD REPORT FOR THERMAL
                                                                                                                                                                                                                                                                              REQUIREMENTS.
                                                                                                                                                                                                                                                                   7.         FIRE HYDRANT AND FIRE HOSE REEL INSTALLATIONS TO COMPLY
                                                                                                                                                                                                                                                                              WITH AS2419 AND AS2441.
                                                                                                                                                                                                                                                                   8.         VERIFY ALL DIMENSIONS/SETOUTS ON SITE PRIOR TO
                                                                                                                                                                                                                                                                              CONSTRUCTION.
                                                                                                                                                                                                                                                                   9.         REFER TO CONSULTANT DRAWINGS FOR SERVICES LOCATIONS AND
                                                                                                                                                                                                                                                                              SIZES. CONTRACTOR TO VERIFY PRIOR TO CONSTRUCTION.
                                                                                                                                                                                                                                                                   10.        REFER TO ELEVATIONS FOR FURTHER FINISHES AND PANEL SETOUT
                                                                                                                                                                                                                                                                              INFORMATION.
                                                                                                                                                                                                                                                                   11.        ALL STRUCTURAL STEEL TO BE HOT DIPPED GALVANISED, REFER
                            2500                      4400                                                   11210                                  2005                                                                                                                      STRUCTURAL ENGINEERS DETAILS
                          SETBACK                                                                                                                 SETBACK
                                                                                                                                                                                                                                                                   12.        OVERFLOW LOCATIONS TO BE COORDINATED WITH HYDRAULIC
                                                                                                                                                                                                                                                                              ENGINEER, OVERFLOW REQUIRED BY THE HYDRAULIC ENGINEER TO
                                                                                                                                                                                                                                                                              BE COORDINATED WITH THE ARCHITECT.
                                                                                     8M HEIGHT                                                                                                                                                                     13.        REFER TO ELEVATIONS FOR FACADE SCREEN SET-OUT.
                          CNC-PF                                                                                                                                                                                                                                   14.        ALL EXPOSED CONCRETE WALLS/COLUMNS TO BE CLASS 2 FINISH.
                                                                                                                                                                                                                                                                              ANY BACK OF HOUSE CONCRETE WALLS/COLUMNS TO BE CLASS 3
ROOF
                                                                                                                                                                                                                                                                              FINISH.
RL 9.800
                                                                                                                                                                                                                                                                   15.        DISCONTINUOUS CONSTRUCTION AS REQUIRED TO COMPLY WITH NCC
                                            AFG-SD3           AFG-01                           AFG-SD1                                                                                                                                                                        REQUIREMENTS.
                                                                                                                                                                                                                                                                   16.        ROOF VENTILATION REQUIRMENTS BY OTHERS. CONTRACTOR TO
                                                                                                                                                                                                                                                                              VERIFY PRIOR TO CONSTRUCTION.
                                                                                                                                                    SCN-01
                  3450




                                                                                      BAL-01
                          CNC-PF
01_FIRST FLOOR                                                                                   SST
RL 6.350

                                    AFG-SD1                                                        AFG-SD2

                                                      COL-A                                                                    COL-A
                  3650




                                                                                                                                                                                                                                                                   bureau^proberts PTY LTD
                                                                                                                                                                                                                                                                   ABN 53 073 087 993 ACN 073 087 993
                                                                                                                                                                                                                                                                   LEVEL 14, 100 CREEK STREET, BRISBANE QLD 4000, GPO Box 3204 QLD 4001
                                                                                                                                                                                                                                                                   P: 07 3221 0672 F: 07 3221 0683 EMAIL : [email protected] www.bureauproberts.com.au

                                                                                                                                                                                                                 BAL-03                                            CLIENT:
00_GROUND FLOOR
RL 2.700                                                                                                                                                          DFL DFL                                            SST                                           SEYMOUR GROUP
                                                                                                                                                              RL 2.400 RL 2.400                                                                                    PROJECT:

                                                                                                                                                                                                                                                                   NOOSA RESIDENCE
                                                                                                                                                                                  BAL-02

                                                                                     NATURAL GROUND LINE                                                                                                                                                           ADDRESS:

                                                                                                                                                                                                                                                                   7 NOOSA PARADE

                                                                                                                                                                                                                                                                   DRAWN BY:                                                                                  NORTH:
                                                                                                                                                                                                                                                                                                            TH
                                                                                                                                                                                                                                                                   CHECK BY:
                                                                                                                                                                                                                                                                                                            JC
                                                                                                                                                                                                                                                                   PROJECT

                                                                SOUTH ELEVATION                                                                                                                      REAR BOUNDARY ELEVATION                                       ARCHITECT                                JC

                                                        2       1 : 100
                                                                                                                                                                                                 4   1 : 100
                                                                                                                                                                                                                                                                   DESIGN
                                                                                                                                                                                                                                                                   ARCHITECT                                AB
                                                                                                                                                                                                                                                                                                                                                                  SCALE:
                                                                                                                                                                                                                                                                                                                                     5             1 : 100 [A1]
                                                                                                                                                                                                                                                                   DRAWING TITLE:

                                                                                                                                                                                                                                                                   NORTH & SOUTH ELEVATIONS

                                                                                                                                                                                                                                                                   CAD FILE REF:                                                                                   DATE:
                                                                                                                                                                                                                                                                   C:\_Revit Local\24048_7 Noosa Parade_B.A_larissaf4R2ZR.rvt
                                                                                                                                                                                                                                                                                                                                                          22.09.25
                                                                                                                                                                                                                                                                   PROJECT NO:                             PHASE:               DRAWING NUMBER:             REVISION:


                                                                                                                                                                                                                                                                   24048                                        B.A.            AR 30.01                             7
                                                                                                                                                                                                                                                                                                                                                       22/09/2025 3:37:11 PM

Used in these records

About this file

File size
7.4 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

RFI - Attachment F - Revised Architectural Plans.pdf · 7.4 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.