2022-02-14 General Committee Meeting Minutes

of 26

Page text shows just the words. Original shows the document exactly as it was published.

Text sections have not been matched to the original PDF pages. Use the original document to check page numbers.

                       MINUTES


         General Committee
              Meeting


             Monday, 14 February 2022

                                10am
         Council Chambers, 9 Pelican Street, Tewantin



Committee:   Crs Frank Wilkie (Chair), Karen Finzel, Joe Jurisevic, Amelia
             Lorentson, Clare Stewart, Brian Stockwell, Tom Wegener



                    “Noosa Shire – different by nature”
Log in to download the original file

2022-02-14 General Committee Meeting Minutes(PDF, 373KB).pdf · 382 KB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

Full text of the other 25 sections

Section 2

GENERAL COMMITTEE MEETING MINUTES                                      14 FEBRUARY 2022



1.   ATTENDANCE & APOLOGIES


     COUNCILLORS
     Cr Frank Wilkie
     Cr Karen Finzel (via Microsoft Teams)
     Cr Joe Jurisevic (via Microsoft Teams)
     Cr Amelia Lorentson
     Cr Clare Stewart (via Microsoft Teams)
     Cr Brian Stockwell (via Microsoft Teams)
     Cr Tom Wegener

     EXECUTIVE
     L Sengstock, Acting Chief Executive Officer & Director Infrastructure Services
     L Jensen, Acting Director Environment & Sustainable Development (via Microsoft Teams)
     T Grauf, Acting Director Corporate Services (via Microsoft Teams)
     D Iezzi, Director Executive Services (via Microsoft Teams)
     K Contini, Director Community Services (via Microsoft Teams)
     APOLOGIES
     Nil


     The meeting commenced at 10.01am.



2.   CONFIRMATION OF MINUTES

     Committee Resolution
     Moved:           Cr Finzel
     Seconded:        Cr Lorentson
     The Minutes of the General Committee Meeting held on 17 January 2022 be received and
     confirmed.
                                                                    Carried unanimously.



3.   PRESENTATIONS

     Nil.


4.   DEPUTATIONS


     1.     DAVID MCCREADY, GOETZ VON SCHWEINFURTH & JAN DAVEY
            (via Microsoft Teams)
            Topic:   30 Toulambi Street Zoning to Environmental Management & Conservation
                     Zone



                                                                               Page 2 of 26

Section 3

GENERAL COMMITTEE MEETING MINUTES                                                       14 FEBRUARY 2022


5.   ITEMS REFERRED FROM COMMITTEES


PLANNING & ENVIRONMENT COMMITTEE


1    PLANNING APPLICATIONS DECIDED BY DELEGATED AUTHORITY FOR NOVEMBER
     & DECEMBER 2021
     In accordance with Chapter 5B of the Local Government Act 2009, Cr Stewart provided the
     following declaration to the meeting of a declarable conflict of interest in this matter:
     I, Cr Stewart, inform the meeting that I have a declarable conflict of interest in this matter in relation to
     the application by Altum Constructions in Item 31 – MCU20/0150.1. I have a close personal friendship
     with Leigh and Rob McCready, who are associated with the applicant. As a result of my conflict of
     interest I will now leave the meeting room while the matter is considered and voted on.
     Cr Stewart left the meeting.
     In accordance with Chapter 5B of the Local Government Act 2009, Cr Finzel provided the following
     declaration to the meeting of a declarable conflict of interest in this matter:
     I, Cr Finzel, inform the meeting that I have a declarable conflict of interest in this matter in relation to
     the application by Altum Constructions in Item 31 – MCU20/0150.1. Leigh McCready who is
     associated with the applicant was involved in a volunteer capacity with my 2020 election campaign
     where I was one of three candidates that ran as a group known as 'Future Noosa' (which is no longer
     an entity). As a result of my conflict of interest I will now leave the meeting room while the matter is
     considered and voted on.
     Cr Finzel left the meeting.
     In accordance with Chapter 5B of the Local Government Act 2009, Cr Stockwell provided the following
     declaration to the meeting of a prescribed conflict of interest in this matter:
     I, Cr Stockwell declare I have a prescribed conflict of interest in this matter as follows: Suncoast
     Building Approvals are identified as the applicant in number 26 for Development Application
     EXE21/0035. I contracted Suncoast Building Approvals to undertake Building Certification for my
     proposed residence in Boreen Point on the 29 November 2021. This process is currently underway.
     The total fees associated with the completion of the certification and inspection regime is $5,904 which
     includes Noosa Council Plumbing and Drainage fees. As a result of my conflict of interest I will now
     leave the meeting room while the matter is considered and voted on.
     Cr Stockwell left the meeting.
     Committee Recommendation
     Moved:             Cr Wegener
     Seconded:          Cr Lorentson
     That Council note the report by the Development Assessment Manger to the Planning &
     Environment Committee Meeting dated 8 February 2022 regarding planning applications that
     have been decided by delegated authority.
                                                                                      Carried unanimously.
     Cr Stockwell, Cr Stewart and Cr Finzel returned to the meeting


2    REFER TO CLOSED SESSION AT ITEM 7 – (REPORT 10)




                                                                                                  Page 3 of 26

Section 4

GENERAL COMMITTEE MEETING MINUTES                                            14 FEBRUARY 2022


SERVICES & ORGANISATION COMMITTEE


3    2021 DELEGATIONS OF AUTHORITY ANNUAL REVIEW
     Committee Recommendation
     Moved:          Cr Lorentson
     Seconded:       Cr Stockwell
     That Council note the report by the Governance Officer to the Services & Organisation
     Committee Meeting dated 08 February 2022 and adopt:
     A.   New Delegations - Pursuant to section 257 of the Local Government Act 2009, to
          delegate the powers of the Local Government outlined in the Delegations of Authority
          provided at Attachment 1, to the Chief Executive Officer of Council;
     B.   Updated Delegations - Pursuant to section 257 of the Local Government Act 2009, to
          delegate the powers of the Local Government outlined in the Delegations of Authority
          provided at Attachment 2, to the Chief Executive Officer of Council; and
     C.   Unchanged Delegations - Pursuant to section 257 of the Local Government Act 2009,
          to delegate the powers of the Local Government outlined in the Delegations of Authority
          provided at Attachment 3, to the Chief Executive Officer of Council.
                                                                          Carried unanimously.



6.   REPORTS DIRECT TO GENERAL COMMITTEE



4    30 TOULAMBI STREET, NOOSA HEADS DESCRIBED AS LOT 15 RP129286 - SITE
     INVESTIGATION FOR SOCIAL HOUSING AND MEMORANDUM OF UNDERSTANDING
     WITH COMMUNITY HOUSING PROVIDER
     Motion
     Moved:           Cr Wilkie
     Seconded:        Cr Stockwell

     That Council note the report by the Senior Strategic Planner to the General Committee
     Meeting dated 14 February 2022 and agree to:

     A.   Not proceed with any further investigation at 30 Toulambi Street for social or affordable
          housing;
     B.   Resolve to amend the Noosa Plan 2020 by having 30 Toulambi Street included in the
          Environmental Management and Conservation Zone;
     C.   Delegate to the Chief Executive Officer to finalise the details of a Memorandum of
          Understanding with Coast2Bay Housing Group to allow collaboration and
          investigations for social housing/affordable housing outcomes on Council owned land
          and other land or opportunities across the Shire.
     D.   Invite the Federal Member for Wide Bay to a roundtable meeting to discuss the
          implications of the phase-out of the National Rental Assistance scheme.




                                                                                     Page 4 of 26

Section 5

GENERAL COMMITTEE MEETING MINUTES                                           14 FEBRUARY 2022


    Amendment No.1
    Moved:           Cr Jurisevic
    Seconded:        Cr Wegener
    That the item E be added to read:
    E.    Prepare an updated Management Plan for Pinnaroo Park in accordance with the Noosa
          Bushland Reserve Strategic Management Plan and refer the consideration of this to
          the 2022/2023 budget process.
                                                                     Carried unanimously.


    Amendment No.2
    Moved:          Cr Lorentson
    Seconded:       Cr Finzel
    That item F be added to read:
    F.   Acknowledge the commitment, dedication, local knowledge and years of volunteering
         work from the former Pinnaroo Park Community Bushland Care Group and adjacent
         residents who have assisted with management activities within the Reserve, including
         assisting with the control of environmentally damaging weed species, assisting with
         revegetation of denuded areas by planting local native species and for providing
         opportunities for community members to connect and become involved in the
         management of bushland values of the area.
                                                                      Carried unanimously.

    Committee Recommendation
    Moved:          Cr Wilkie
    Seconded:       Cr Stockwell
    That Council note the report by the Senior Strategic Planner to the General Committee
    Meeting dated 14 February 2022 and agree to:
    A.   Not proceed with any further investigation at 30 Toulambi Street for social or affordable
         housing;
    B.   Resolve to amend the Noosa Plan 2020 by having 30 Toulambi Street included in the
         Environmental Management and Conservation Zone;
    C.   Delegate to the Chief Executive Officer to finalise the details of a Memorandum of
         Understanding with Coast2Bay Housing Group to allow collaboration and
         investigations for social housing/affordable housing outcomes on Council owned land
         and other land or opportunities across the Shire.
    D.   Invite the Federal Member for Wide Bay to a roundtable meeting to discuss the
         implications of the phase-out of the National Rental Assistance scheme.
    E.   Prepare an updated Management Plan for Pinnaroo Park in accordance with the Noosa
         Bushland Reserve Strategic Management Plan and refer the consideration of this to
         the 2022/2023 budget process.
    F.   Acknowledge the commitment, dedication, local knowledge and years of volunteering
         work from the former Pinnaroo Park Community Bushland Care Group and adjacent
         residents who have assisted with management activities within the Reserve, including
         assisting with the control of environmentally damaging weed species, assisting with
         revegetation of denuded areas by planting local native species and for providing
         opportunities for community members to connect and become involved in the
         management of bushland values of the area.
                                                                      Carried unanimously.

                                                                                    Page 5 of 26

Section 6

GENERAL COMMITTEE MEETING MINUTES                                             14 FEBRUARY 2022


5   MCU21/0162 - APPLICATION FOR A MATERIAL CHANGE OF USE – COMMUNITY USE
    (SURF MUSEUM), FOOD AND DRINK OUTLET, INDOOR SPORT AND RECREATION
    AND OFFICES AT 3 HILTON TERRACE, TEWANTIN
    Committee Recommendation
    Moved:           Cr Stewart
    Seconded:        Cr Stockwell
    That Council note the report by the Development Planner to the General Committee Meeting
    dated 14 February 2022 regarding Application No. MCU21/0162 for a Development Permit
    for Material Change of Use - Community Use (Surf Museum), Food and Drink Outlet
    (Restaurant), Indoor Sport and Recreation (Gym) & Offices situated at Noosa Lakes Resort
    3 & 95/3 Hilton Tce Tewantin:

    A.   Approve the application in accordance with the following conditions:

         PLANNING
         When Conditions must be Complied With
    1.   Unless otherwise stated, all conditions of this Decision Notice must be complied with
         prior to the use commencing, and then compliance maintained at all times while the
         use continues.
         Approved Plans
    2.   Development undertaken in accordance with this approval must generally comply with
         the approved plans of development. The approved plans are listed in the following table
         unless otherwise amended by these conditions.
          Plan No.               Rev.   Plan/Document Name                                 Date
          TP101                  A      Site Plan, Skeco Building Design                   13/08/21
          TP202                  A      Existing First Floor Plan, Skeco Building Design   13/08/21
                                        (annotated)
          TP203                  A      New Ground Layout Plan, Skeco Building             13/08/21
                                        Design (annotated)
          TP204                  A      Café Bar Restaurant, Skeco Building Design         13/08/21
          TP205                  A      Gymnasium, Skeco Building Design                   13/08/21
         Nature and Extent of Approved Use
    3.   Service vehicle movements associated with the approved use (including loading and
         unloading) must not occur outside the hours of 7am to 6pm Monday to Saturday and
         not at all on Sundays or public holidays.
    4.   The outdoor dining area associated with the Food and Drink establishment must not
         exceed 39m2.
    5.   Classes in the gymnasium are limited to a maximum of 10 people at any given time
         (excluding staff).
    6.   The offices must be in accordance with the approved first floor plan, and include a
         minimum of 16 small office tenancies, with rooms 17 and 18 comprising a shared multi-
         purpose room and boardroom.
         Currency Period
    7.   This development approval lapses if the use has not happened by 17 February 2028,
         unless an application to extend the currency period is approved by Council.
         Street Identification
    8.   The street address of the development must be clearly visible and discernible from the
         primary frontage of the site by the provision of a street number and, where appropriate,
         the building name.

                                                                                       Page 6 of 26

Section 7

GENERAL COMMITTEE MEETING MINUTES                                            14 FEBRUARY 2022


          Damage to infrastructure
    9.    Any damage to footpaths, street plantings, natural vegetation/trees kerb and channel,
          bridges or roadways must be repaired or reinstated to at least pre-existing conditions.
          Building Appearance
    10.   All mechanical equipment and other service infrastructure located on the site must be:
          a.    located not less than 2 metres from a property boundary
          b.    fully enclosed or screened such that they are not visible from the street frontages
                nor adjoining properties. Where screened by landscaping, landscaping beds
                must be at least 1.5 metres wide.
          No part of the site may be used for outdoor storage of materials unless specified on
          the Approved Plans or the conditions of this Decision Notice. Materials stored outside
          of the building must not exceed 4 metres in height or half the height of the building,
          whichever is the greater.
          Car Parking
    11.   A minimum of 31 car parking spaces must be provided and marked on the site and
          made available and accessible at all times while the uses are open for business. All
          car parking areas and access driveways must be maintained exclusively for vehicle
          parking and manoeuvring and kept in a tidy and safe condition at all times.
    12.   Directional signage must be provided to direct visitors and customers to the car parking
          spaces provided on site.
          Landscaping Works
    13.   The development site must be landscaped. The works must be undertaken in
          accordance with an Operational Works approval and the Noosa Plan for that specific
          area and must include in particular:
           a.    the works shown on the Approved Plans
          b.    revitalisation of the existing landscape beds and landscape setbacks along the
                Hilton Terrace Road frontage of the subject site (where the conference building
                is located), exclusive of the access driveway, generally uncompromised by
                infrastructure items.
    14.   All landscape works must be established and maintained in accordance with the
          approved design for the life of the development, and in a manner that ensures healthy,
          sustained and vigorous plant growth. All plant material must be allowed to grow to full
          form and be refurbished when its life expectancy is reached.
    15.   All landscape works must be maintained generally in accordance with the approved
          design for the life of the development.
    B.    Refuse the proposed Offices for the following reasons:
          1.    The proposed Offices are not consistent with the purpose of the Tourist
                Accommodation Zone as the use does not support short-term accommodation
                and tourist attractions.
          2.    The proposed Offices are not consistent with Overall Outcomes (2)(a), (2)(b) and
                (2)(y) and Performance Outcomes PO1, PO2, PO3 and Acceptable Outcome 3.2
                of the Tourist Accommodation Zone Code because:
                a.    The offices will not complement and enhance the function and
                      attractiveness of the areas a visitor destination as the offices do not cater
                      to the needs of visitors or residents enjoying the area.



                                                                                     Page 7 of 26

Section 8

GENERAL COMMITTEE MEETING MINUTES                                          14 FEBRUARY 2022


                b.   The offices will not serve visitors and preserve the role of the area as
                     tourism focus area.
                c.   Offices are not intended to establish in the Tourist Accommodation zone
                     unless they support the area’s accommodation facilities and tourism and
                     recreation activities.
         3.     The proposed offices are contrary to the Strategic Intent and Outcomes for the
                Shire as commercial offices are intended to be located in the defined centres and
                key visitor areas intended for tourism activities.
         4.     There is no need for additional land or floor space outside the designated
                business centres for offices.
    B.   Find the following matters relevant to the assessment and sufficient reason to approve
         the application:
         1.     The proposal is consistent with the Tourist accommodation zone overall outcome
                2(b) which envisages that visitor accommodation in the urban areas is supported
                by a mix of business activities which create a vibrant atmosphere and
                complement and enhance the function and attractiveness of the area as a visitor
                destination
         2.     The office space will encourage business tourism and act as an incubator for
                start-up businesses and is of a scale that is ancillary to the visitor
                accommodation.
         3.     The office space is of a nature and scale that is compatible with the mixed-use
                character and coastal amenity of the area.
         4.     The proposed office space will not compromise the viability of the Noosa Shire
                centres hierarchy considering the specific nature of office space and it small
                gross floor area.
    C.     Note the report is provided in accordance with Section 63(5) of the Planning Act 2016.
                                                                         Carried unanimously.


6   ORGANISATIONAL STRUCTURE

    Committee Recommendation
    Moved:           Cr Finzel
    Seconded:        Cr Wegener

    That Council note the report by the Director Executive Services Department to the General
    Committee Meeting dated 14 February 2022 and adopt the Noosa Council Organisational
    Structure as set out in Attachment 1 to the report.
                                                                       Carried unanimously.




                                                                                   Page 8 of 26

Section 9

GENERAL COMMITTEE MEETING MINUTES                                            14 FEBRUARY 2022




7     COUNCILLOR REPRESENTATION ON COUNCIL OF MAYORS WORKING GROUPS

      Committee Recommendation
      Moved:              Cr Stewart
      Seconded:           Cr Lorentson
      That Council note the report by the Acting Chief Executive Officer to the General
      Committee Meeting dated 14 February 2021 and
      1.     Appoint Cr Stewart as Council’s representative on the SEQ 2032 Legacy Working
             Group;
      2.     Appoint Cr Joe Jurisevic as Council’s representative and Cr Tom Wegener as the proxy
             for the SEQ Waste Working Group;
      3.     Appoint Cr Amelia Lorentson as Council’s representative and Cr Karen Finzel as the
             proxy for the SEQ Economic Development Working Group.
                                                                         Carried unanimously.




8     FINANCIAL PERFORMANCE REPORT – JANUARY 2022
      Committee Recommendation
      Moved:             Cr Jurisevic
      Seconded:          Cr Stewart
      That Council note the report by the Financial Services Manager (Acting) to the General
      Committee Meeting dated 14 February 2022 outlining January 2022 year to date financial
      performance against budget, including changes to the financial performance report with the
      inclusion of key financial sustainability indicators.
                                                                          Carried unanimously.




9     OPERATIONAL PLAN PROGRESS REPORT – SECOND QUARTER 2021-22
      Committee Recommendation
      Moved:              Cr Wegener
      Seconded:           Cr Stockwell
      That Council note the report by the Chief Executive Officer to the Services and Organisation
      Committee Meeting dated 14 February 2022 regarding the 2021-22 Operational Plan and:
      A.     Note the progress report for the 2021-22 Operational Plan to 31 December 2021
             provided as Attachment 1; and
      B.     Note the status of Council’s Key Performance Indicators provided as Attachment 2.


Cr Finzel left the meeting (offline due to power outage)
                                                                          Carried unanimously.
Cr Finzel returned to the meeting.




                                                                                    Page 9 of 26

Section 10

GENERAL COMMITTEE MEETING MINUTES                                                      14 FEBRUARY 2022


7.   CLOSED SESSION


10   MCU21/0013 & OPW21/0031 – PLANNING & ENVIRONMENT COURT
     APPEAL NO. BD2677 OF 2021 – REFUSAL OF AN APPLICATION FOR MULTIPLE
     DWELLING UNITS (19 UNITS), FOOD & DRINK OUTLET, INDOOR SPORT &
     RECREATION, HEALTH CARE SERVICE, OFFICE & OPERATIONAL WORKS AT 30-32
     DOONELLA ST, TEWANTIN
     In accordance with Chapter 5B of the Local Government Act 2009, Cr Jurisevic provided the following
     declaration to the meeting of a declarable conflict of interest in this matter:
     I, Cr Jurisevic declare I have a declarable conflict of interest in this matter as the matter is a planning
     application for a Doonella St property that is at least in part owned by Chris Wright, as I understand it.
     My family and I have had a close relationship with Chris Wright and his family over the years that we
     have lived in Tewantin. The nature of the relationship stems from my wife having worked for Chris’
     wife, Kelly and in the same office where Chris’ business is located. Kelly was also the Treasurer of the
     Sunshine Beach State High School P&C during my term as P&C President. My wife and I attended
     Chris and Kelly’s wedding as well as several social gatherings at each other’s houses over the years
     as our children were close friends and attended the same playgroup and schools growing up. As a
     result of my conflict I will leave the meeting room while the matter is considered and voted on.

     Cr Jurisevic left the meeting.

     CLOSURE OF THE MEETING TO THE PUBLIC

     Committee Resolution
     Moved:            Cr Stockwell
     Seconded:         Cr Lorentson
     That the meeting be closed to the public pursuant to section 254J(3) of the Local Government
     Regulation 2012 for the purpose of discussing Legal advice obtained by the local government
     or legal proceedings involving the local government including, for example, legal proceedings
     that may be taken by or against the local government.
                                                                           Carried unanimously.

     RE-OPENING OF THE MEETING TO THE PUBLIC

     Committee Resolution
     Moved:           Cr Lorentson
     Seconded:        Cr Finzel
     That the meeting be re-opened to the public.
                                                                                    Carried unanimously.

     Committee Recommendation
     Moved:              Cr Lorentson
     Seconded:           Cr Stewart
     That Council note the report by the Manager Development Assessment to the General
     Committee Meeting dated 8 February 2022 regarding Planning & Environment Court Appeal
     No. BD267 of 2021 and agree to settle the appeal generally in accordance with the following
     conditions:
                               MATERIAL CHANGE OF USE - MCU21/0013
     PLANNING

     When Conditions must be Complied With

                                                                                               Page 10 of 26

Section 11

GENERAL COMMITTEE MEETING MINUTES                                          14 FEBRUARY 2022


    1.    Unless otherwise stated, all conditions of this Decision Notice must be complied with
          prior to the use commencing, and then compliance maintained at all times while the
          use continues.
          Approved Plans
    2.    Development undertaken in accordance with this approval must generally comply with
          the approved plans of development. The approved plans are listed in the following table
          unless otherwise amended by these conditions.
          Plan No.   Rev.   Plan/Document Name                                        Date
          SD01       13     Site Plan, prepared by Archicology P/L                    08/07/21
          SD02       12     Ground / Carpark Plan, prepared by Archicology P/L        08/07/21
          SD03       10     Level 1 Plan, prepared by Archicology P/L                 31/05/21
          SD3A       2      LHA-SDA Compliance Plan, prepared by Archicology P/L      14/05/21
          SD04       6      Level 2 Plan, prepared by Archicology P/L                 23/04/21
          SD06       6      Roof Plan, prepared by Archicology P/L                    31/05/21
          SD10       10     Elevations, prepared by Archicology P/L                   08/07/21
          SD11       10     Elevations, prepared by Archicology P/L                   08/07/21
          SD12       7      Sections A, B, prepared by Archicology P/L                23/04/21
          SD13       7      Sections C, D, prepared by Archicology P/L                14/05/21
          SD14       10     3D Impression 01, 02, prepared by Archicology P/L         08/07/21
          SD15       9      3D Impression 03, 04, prepared by Archicology P/L         08/07/21
          SD16       6      3D Impression 05, 06, prepared by Archicology P/L         23/04/21
          SD17       6      3D Impression 07, prepared by Archicology P/L             23/04/21
    Nature and Extent of Approved Use
    3.    No more than one Food and drink outlet is approved to operate at any one time and
          must be located in one tenancy only as identified on the approved plans of
          development. The Food and drink outlet must only operate between the hours of 7am
          and 9pm, 7 days per week.
    4.    Class sizes for the Indoor Recreation use are not to exceed 5 persons at any one time
          between the hours of 9am and 5pm.
    5.    All dwelling units must have a gross floor area of no more than 100m 2 pursuant to the
          definition of a ‘small dwelling’ under the Noosa Plan 2020.
    6.    Service vehicle movements associated with non-residential uses on the premises
          (including loading and unloading) must not occur outside the hours of 7am to 6pm
          Monday to Saturday and not at all on Sundays or public holidays. The requirements of
          this condition must be included in the Community Management Statement for any body
          corporate for the subject site.
    Currency Period
    7.    This development approval lapses if the use has not happened by 17 February 2028,
          unless an application to extend the currency period is approved by Council.
    Building Height
    8.    The maximum height of the development must not exceed the building height and
          storeys shown on the approved plans.
    9.    Certification must be submitted to Council from a Licensed Surveyor which certifies
          that the buildings do not exceed the maximum height requirement of this Decision
          Notice.
    Performance Bond
    10.   Security in the form of a cash bond or trading bank guarantee to the sum of $30,000
          must be submitted to Council, to secure performance of all conditions of this approval,
          prior to pre-start meeting. The cash bond or trading bank guarantee will be returned on

                                                                                   Page 11 of 26

Section 12

GENERAL COMMITTEE MEETING MINUTES                                            14 FEBRUARY 2022


          performance of the conditions of approval less any costs incurred by Council in respect
          of enforcing performance of this permit. Council reserves the right to call upon the bond
          or guaranteed sum to effect compliance with conditions.
    Built form
    11.   All air conditioning units or other mechanical equipment must be fully enclosed or
          screened such that they are not visible from the street frontages nor adjoining
          properties.
    12.   All deck and balcony areas above ground floor must not be enclosed by permanent
          fixtures such as shutters, louvres, glass panelling or the like, except where required to
          satisfy any privacy condition of this Decision Notice.
    13.   External finishes must be as per the approved plans of development.
    14.   External colours must be muted environmental tones that blend with the natural
          environment.
    15.   The Energex PMT and the Fire hydrant booster must be finished in a colour that blends
          with the natural environment and the development.
    Communal Recreation Areas
    16.   Communal recreation area/s must be provided as shown on the approved plans of
          development.
    Street Identification
    17.   The street address of the development must be clearly visible and discernible from the
          primary frontage of the site by the provision of a street number and, where appropriate,
          the building name.
    Water & Sewer Connections
    18.   An underground connection to reticulated water and sewerage must be provided to the
          development site in accordance with the standards and requirements of Northern SEQ
          Distributor–Retailer Authority (Unitywater).
    19.   A Certificate of Completion from the Northern SEQ Distributor–Retailer Authority
          (Unitywater) must be submitted to Council that certifies an underground connection to
          reticulated water and sewerage has been provided to the development site.
    ENGINEERING
    Site Access and Driveways
    20.   Sealed access driveways must be provided from Doonella Street to all parking and
          manoeuvring areas of the development. The works must be undertaken in accordance
          with the conditions of this Decision Notice and must include in particular:
          a.     driveway crossovers generally in accordance with Council’s standard drawing
                 RS-051;
          b.     suitable safety measures, including warning signage, to improve driver
                 awareness of pedestrians and enhance pedestrian safety. Warning signage must
                 be provided near the exit ramp from the parking area to warn motorists of
                 pedestrian movement along the frontage street.
    Car Parking
    21.   Thirty three (33) car parking spaces must be provided and marked on the site and
          made available and accessible at all times. The works must be undertaken in
          accordance with the conditions of this Decision Notice and must include in particular:
          a.     for the residential development, a maximum of 20 parking spaces within the total,
                 which are clearly marked for that purpose and accessible at all times; and

                                                                                   Page 12 of 26

Section 13

GENERAL COMMITTEE MEETING MINUTES                                            14 FEBRUARY 2022


          b.    the balance of carparking for the commercial uses; and
          c.    12 motorcycle spaces; and
          d.    disabled parking spaces as shown on the approved plans; and
          e.    dimensions, crossfalls and gradients in accordance with Australian Standard
                AS2890: Parking Facilities.
    22.   All car parking areas and access driveways must be maintained exclusively for vehicle
          parking and manoeuvring and kept in a tidy and safe condition at all times.
    23.   Directional signage must be provided to direct visitors and customers to the car parking
          spaces provided on site.
    Pedestrian and Bicycle Facilities
    24.   Pedestrian and bicycle facilities must be provided for the development. The works must
          be undertaken in accordance with the conditions of this Decision Notice and must
          include in particular:
          a.    a 2 metre wide concrete footpath within the road verge, the same colour as the
                existing (dark), for the entire length of the site’s frontage to Doonella Street;
          b.    a 2m wide concrete pathway for the full length of the ‘public thoroughfare’
                easement, along the full length of the easement located along the northern
                boundary
          c.    pedestrian pathways between the proposed car parking area and the building/s;
          d.    adequate separation of all specific pedestrian routes from vehicle access and
                manoeuvring areas, and clear demarcation by pavement marking, signposts or
                changes in surface materials or levels;
          e.    signage and lighting at strategic locations to direct people to building entries and
                public toilet facilities;
          f.    bicycle parking spaces and lockers as shown on the approved Ground / Carpark
                Plan (Plan SD02, Iss.12).
    Stormwater Drainage
    25.   The site must be provided with a stormwater drainage system connecting to a lawful
          point of discharge. The works must be undertaken in accordance with the conditions
          of this Decision Notice.
    Services
    26.   Unless otherwise stipulated by telecommunications legislation at the time of
          construction, the development must be provided with all necessary conduits, pits and
          pipes to accommodate the future connection of optic fibre technology
          telecommunications.
    27.   27.Certification must be submitted to Council from all relevant service providers
          (Energex, NBN and Unitywater) which certifies that the development has met the
          requirements of this Decision Notice and all applicable legislation at the time of
          construction.
    Easements
    28.   A 3 metre wide easement for “Public Thoroughfare” must be registered against the title
          of the property in favour of Council. The easement must be located as shown, in red,
          on Drawing No. SD03, titled “Level 1 Plan”, Issue 10, dated 31/05/2021 and prepared
          by Archicology P/L.
    29.   Unless otherwise agreed in writing by the relevant service provider, any public or third
          party infrastructure located on the subject site must be placed within an easement

                                                                                    Page 13 of 26

Section 14

GENERAL COMMITTEE MEETING MINUTES                                           14 FEBRUARY 2022


          registered against the title of the property.
    30.   All easements must be designed in accordance with the planning scheme and granted
          at no cost to the Grantee. Where the Grantee is Council or a service authority, the
          easement documentation must be in accordance with the Grantee’s standard
          easement terms. Draft easement documentation must be submitted to Council for
          endorsement.
    31.   All works must be kept clear of any existing or proposed easements on the subject
          land, unless agreed otherwise in writing by the Grantee.
    Geotechnical Stability
    32.   All works must be carried out generally in accordance with geotechnical investigation
          report 18151-001-Rev0, titled: “Proposed Commercial & Residential Development 30-
          32 Doonella St Tewantin”, dated 22 June 2018 and prepared by Tectonic Geotechnical
          and Environmental Engineers.
    33.   Certification must be submitted to Council from a qualified person* which certifies that
          the development has been constructed in accordance with the recommendations
          contained in geotechnical investigation report 18151-001-Rev0, titled: “Proposed
          Commercial & Residential Development 30-32 Doonella St Tewantin”, dated 22 June
          2018 and prepared by Tectonic Geotechnical and Environmental Engineers, and that
          the development has a minimum factor of safety against landslip of 1.5 in the long term.
          *(Refer to advisory Note)
    Earthworks and Retaining Walls
    34.   All fill and associated batters must be undertaken in accordance with the conditions of
          this Decision notice, and must be contained entirely within the subject site unless
          written permission from the respective landowner(s) is provided to Council. All
          earthworks must be undertaken in accordance with the provisions of Australian
          Standard AS3798: Guidelines on Earthworks for Commercial and Residential
          Developments.
    35.   Where the development involves excavation or filling over, or adjacent to, drainage,
          water supply or sewerage infrastructure, all access chamber surface levels must be
          adjusted to provide a freeboard of 100mm above the finished ground surface level.
    36.   All retaining walls must be designed and constructed in accordance with the planning
          scheme and must be certified by an RPEQ where exceeding 1.0m in height. All
          retaining walls that are publicly accessible and exceed 1.0m in height must be fitted
          with a commercial grade safety fence.
    37.   The retaining wall located to the north of the bio basin (shown on section D of
          A6035/21/D1, E with a TOW of RL8.4) must be amended to not exceed 0.8m above
          the NGL. The area between this retaining wall and the footpath further north can either
          be tiered (retaining walls no greater than 0.8m above NGL) or battered (1:4) to the
          footpath to the north.
    Damage to Services and Assets
    38.   Any damage caused to existing services and assets as a result of the development
          works must be repaired at no cost to the asset owner at the following times:
          a.    where the damage would cause a hazard to pedestrian or vehicle safety,
                immediately; or
          b.    where otherwise, upon completion of the works associated with the development.
    Any repair work which proposes to alter the alignment or level of existing services and assets
    must first be referred to the relevant service authority for approval.


                                                                                   Page 14 of 26

Section 15

GENERAL COMMITTEE MEETING MINUTES                                            14 FEBRUARY 2022


    Water quality
    39.   The site must be provided with a stormwater drainage system connecting to a lawful
          point of discharge. The works must include in particular:
          a.    Water quality treatment features that achieve the following pollutant reduction
                targets as measured by a MUSIC model developed in accordance with the Water
                by Design MUSIC modelling guidelines;
          b.    the use of gravity stormwater drainage and not surcharge pits;
          c.    A stormwater quality treatment system must be provided for the development
                that achieved 80% reduction in Total Suspended Solids, 60% reduction in Total
                Phosphorous, 45% reduction in Total Nitrogen compared to an unmitigated
                scenario. The works must be undertaken in accordance with an Operational
                Works approval and the Water by Design Guidelines.
    40.   All stormwater quality treatment devices must be maintained in accordance with the
          Water by Design (2009) - Maintaining Vegetated Stormwater Assets (Version 1). A
          copy of this document must be retained on the site together with the approved
          Operational Works drawings for the stormwater quality treatment system and a detailed
          life cycle costing of the system attached as an addendum. Records of all maintenance
          activities undertaken must be kept and made available to Council upon request.
    41.   Any proposed Community Management Statement required for the development must
          include the Water by Design (2009) – Maintaining Vegetated Stormwater Assets
          (Version 1) document and must include the full cost of maintaining the system in
          accordance with that document.
    42.   Operating rainwater collection and stormwater harvesting tanks must be provided as
          shown identified in section 6.2 of the Engineering Report & Stormwater Management
          Plan report For Proposed Residential and Commercial Tenancies at 30-32 Doonella St
          (A6035/21/ENG/RevB). The tanks must be provided in accordance with an Operational
          Works approval.
    43.   Certification must be submitted to Council from a qualified person* which certifies that
          the rainwater collection tank/s and associated reticulation has/have been installed in
          accordance with the requirements of this Decision Notice.
          *(Refer to Advisory Note)
    Acid Sulfate Soils
    44.   All waters, including stormwater runoff, groundwater seepage and leachate must
          achieve the following quality prior to release from the site at all times:
          a.    a pH range of 6.5-8.5 pH units;
          b.    50mg/L maximum total suspended solids concentration;
          c.    0.3mg/L maximum total iron concentration;
          d.    0.2mg/L maximum total aluminium concentration; and
          e.    no visible plume at either the point of release from the site or within a waterway.
    ENVIRONMENTAL HEALTH
    Waste Storage
    45.   The developer must provide waste storage and disposal facilities in accordance with
          Planning Scheme Policy 9, Waste Management, including an external imperviously
          paved area correctly sized for all refuse and recycling containers and suitably screened
          from public places and neighbouring properties.



                                                                                    Page 15 of 26

Section 16

GENERAL COMMITTEE MEETING MINUTES                                            14 FEBRUARY 2022


    46.   A bin wash area is required with a cold-water tap, hose and drain outlet connected to
          sewer, via a bucket trap. The drain outlet is to be designed to prevent storm water entry
          to the sewerage system which can be achieved by a bunded area, with a nib wall height
          of 100mm maximum, enclosing a wash area of 700mm x 700mm minimum (max
          0.7m²). Alternatively, the waste area can be roofed, or any other appropriate design
          approved by Council.
          Noise
    47.   Written certification is required from a suitably qualified person confirming that sound
          pressure levels from all mechanical plant and equipment comply with the following:
          a.    Air-conditioning and Refrigeration
                •       7am to 10pm: Maximum level allowable = background + 5dB(A)
                •       10pm to 7am: Maximum level allowable = background + 3dB(A)
          b.      Pumps
                •       7am to 7pm: Maximum level allowable = background + 5dB(A)
                •       7pm to 10pm: Maximum level allowable = background + 3dB(A)
                •       10pm to 7am: No audible noise.
    48.   The certification must be submitted to Council, which certifies that operational noise
          from any fixed plant and equipment complies with the requirements of this Decision
          Notice.
    Kitchen Exhaust (Food and drink outlet)
    49.   Kitchen exhaust points for the Food and drink outlet must be located and operated in
          accordance with Australian Standard AS1668.2-2002 “The use of ventilation and air-
          conditioning in buildings” (specifically Section 5.10 – Air Discharges).
    50.   The development must be constructed with reticulated ducting inside the building to
          transfer kitchen exhaust fumes to a discharge point on the roof.
    51.   Submission of written certification must be provided from a suitably qualified person
          confirming that the kitchen exhaust is constructed, installed and is operating in
          accordance with Australian Standard AS1668.2-2002.
    52.   The assessment and certification is required immediately after installation of the
          equipment and prior to any occupation of the building, and in a format approved by
          Council.
    Outdoor Lighting Devices
    53.   Lighting associated with the use must be designed, sited, installed and tested to comply
          with Table 2.1 & 2.2 of Australian Standard AS4282-1997 “Control of the obtrusive
          effects of outdoor lighting” using a control level of 1.
    54.   Certification must be submitted to Council from a qualified person which certifies that
          all outdoor lighting devices comply with the requirements of this Decision Notice at the
          time of commissioning.
          For the purpose of certifying outdoor lighting devices for the development, a qualified
          person is:
           a.       a Registered Professional Engineer of Queensland;
           b.       an environmental or electrical design consultant with a minimum of 3 years
                    current experience in the field of outdoor lighting.
    LANDSCAPING
    55.   The development site must be landscaped. The works must be undertaken in

                                                                                   Page 16 of 26

Section 17

GENERAL COMMITTEE MEETING MINUTES                                          14 FEBRUARY 2022


          accordance Noosa Plan PSP 2 – Landscaping and generally in accordance with the
          approved Landscaping Plans and in particular:
          a.    A 1m wide garden along the south side of the ‘public thoroughfare’ easement
                must be provided which includes native species that effectively screen the
                development and grow to a minimum mature height of 4m.
          b.    Plantings along the eastern side of the bio basin must grow to a minimum height
                of 3-4m and provide screening to the car parking area.
          c.    Landscaping works to provide a suitable visual screening buffer between the
                building and the easement with a minimum garden bed width of 800mm.
          d.    The proposed 25 litre pot size feature trees within the front setback (facing
                Doonella Street) must be replaced with 45 litre pot size plants (the SYZ hem,
                CUP ana, ELA ret, ACR imp species)
          e.    The existing street trees in the road reserve may be removed. If removed they
                must be replaced with 4 x ex-ground Delonix regia (poinciana’s) as shown on
                the approved operational works landscape plans.
    56.   All landscape works must be established and maintained in accordance with the
          approved design for the life of the development, and in a manner that ensures healthy,
          sustained and vigorous plant growth. All plant material must be allowed to grow to full
          form and be refurbished when its life expectancy is reached.
    Signage
    57.   Advertising devices must comply with Council’s signage policy.
                           OPERATIONAL WORKS - OPW21/0031
    Approved Plans
    58.   Development undertaken in accordance with this approval must generally comply with
          the approved plans of development. The approved plans are listed in the following table
          unless otherwise amended by these conditions.
           Plan No.         Rev.   Plan/Document Name                          Date
           SD02             12     Ground / Carpark Plan, prepared by          08/07/2021
                                   Archicology P/L
           A6035/21/EW01    F      Earthworks Layout Plan, prepared by Alta    25/05/2021
                                   Engineering
           A6035/21/R01     F      Roadworks Layout Plan, prepared by Alta     25/05/2021
                                   Engineering
           A6035/21/R03     E      Roadworks Doonella Street – Cross           25/05/2021
                                   Sections, prepared by Alta Engineering
           A6035/21/R04     B      Roadworks Setout Plan, prepared by Alta     25/05/2021
                                   Engineering
           A6035/21/R08     A      Roadworks Boundary Cross Sections,          25/05/2021
                                   prepared by Alta Engineering
           A6035/21/D01     E      Stormwater Layout Plan, prepared by Alta    25/05/2021
                                   Engineering
           A6035/21/D02     E      Stormwater Drainage Details, prepared by    25/05/2021
                                   Alta Engineering
           A6035/21/D03     B      Stormwater Drainage Setout Plan, prepared   25/05/2021
                                   by Alta Engineering
           A6035/21/WQ01    E      Stormwater Treatment Catchment Plan,        25/05/2021
                                   prepared by Alta Engineering
           A6035/21/WQ02    E      Stormwater Quality Layout Plan and Notes,   25/05/2021
                                   prepared by Alta Engineering
           A6035/21/WQ03    E      Stormwater Quality Bio Basin Calculations   25/05/2021
                                   and Details, prepared by Alta Engineering


                                                                                  Page 17 of 26

Section 18

GENERAL COMMITTEE MEETING MINUTES                                           14 FEBRUARY 2022


                  CD-001     J      Vegetation Management Plan, prepared by     2021.05.28
                                    Project Urban
                  CD-002     L      Landscape Plan – In Ground, prepared by     2021.05.28
                                    Project Urban
                  CD-003     K      Landscape Plan – In Ground, prepared by     2021.01.25
                                    Project Urban
                  CD-004     I      Landscape Plan – On Podium, prepared by     2021.01.25
                                    Project Urban
                  CD-005     I      Landscape Plan – Boundary Fences,           2021.01.25
                                    prepared by Project Urban
                  CD-200     L      Construction Details, prepared by Project   2021.01.25
                                    Urban
                  CD-201     C      Planting Schedule, prepared by Project      2021.01.28
                                    Urban
                  CD-202     B      Planting Schedule, prepared by Project      2021.07.07
                                    Urban
    CURRENCY PERIOD
    59.   The Currency Period for this development approval lapses if the development has not
          substantially started by 17 February 2024, unless an application to extend the currency
          period is approved by Council.
    PRIOR TO COMMENCEMENT OF WORKS
    Engineering
    60.   All necessary approvals from external service providers (e.g. Unitywater) and external
          parties on which the development works are proposed have been obtained and a copy
          supplied to Council.
    61.   A condition report of the drainage system must be completed for agreement prior to
          the prestart meeting. The condition report is to include a CCTV inspection of the
          existing pipe and must include at least 50m upstream and downstream of all works.
    62.   A condition report including photographs of the frontage of the site must be completed
          and submitted to council prior to the prestart meeting.
    63.   Certificates demonstrating currency of public liability insurance and works insurance
          covering the works must be submitted to Council prior to the prestart meeting.
    64.   Council must be contacted at least 5 working days prior to any works commencing to
          organise a prestart. The contact number to arrange a pre-start meeting is 5329 6500.
          The pre-start meeting must include the relevant parties for the following aspects of the
          works:
          a.    Civil engineering works;
          b.    Landscape works;
          c.    Erosion and sediment control works;
          d.    Other relevant parties.
    65.   A Construction Management Plan must be submitted to Council prior to the pre-start
          meeting and must specifically address the following:
          a.    Traffic Management during all aspects of the construct phase including:
                i.    A Traffic Management Control Plan in accordance with Manual of Uniform
                      Traffic Control Devices (MUTCD) detailing all temporary signage and traffic
                      control measures prior to construction;
                ii.   Maintenance of safe pedestrian access across the frontage of the site both
                      during daily construction and after daily construction has ceased;


                                                                                   Page 18 of 26

Section 19

GENERAL COMMITTEE MEETING MINUTES                                              14 FEBRUARY 2022


                iii.   Proposed fencing to the site during the construction phase of the
                       development;
                iv.    Adequate parking arrangements for construction workers;
                v.     No queuing of trucks is permitted on residential streets, especially prior to
                       7.00am. Further parked trucks must have engines turned off.
          b.    Maintenance and protection of water quality and existing drainage lines through
                the construction site through the implementation of appropriate erosion and
                sediment control measures;
          c.    Provision for safe pedestrian access across the frontage of the site both during
                daily construction and after daily construction has ceased;
          d.    Works programme identifying key components of the works and their respective
                durations;
          e.    Establishment of a communication protocol with the general public, adjoining
                owners, emergency services and local businesses to advise of agreed
                construction times, impacts on traffic and services and other relevant issues;
          f.    Include a post out to the local residents and businesses advising of the proposed
                development, the expected time frames and the site contact details.
          g.    Include signage in prominent locations on the boundaries of the site advising of
                the proposed development, the expected time frames and the site contact details;
          h.    identification of complaint management procedures including:
                i.     contact details for the on-site manager;
                ii.    dispute resolution procedures;
          i.    For haulage operations involving significant volumes of excavated material being
                transported off the site: details on the location of external site, the haulage route,
                type of vehicle to be utilised during excavation operations and frequency of
                usage. NB any damage to the existing road system as a result of haulage
                operations must be fully repaired at the applicant’s expense.
    66.   Any changes to the details associated with the supervising RPEQ or Principal
          Contractor during construction, must be notified to council in writing within five business
          days of the change occurring.
    67.   Any conflict between the development and an existing or proposed service must be
          referred to the relevant service authority for determination prior to commencement of
          works.
    DURING CONSTRUCTION
    Engineering
    68.   All works must be supervised by a Registered Professional Engineer of Queensland
          (RPEQ) who is independent of the Developer and Principal Contractor, and they must
          certify that all works conform to the Operational Works permit. Where municipal works
          are involved, such confirmation must be submitted for the respective hold points prior
          to any site inspection by Council Officers.
    69.   All works must be constructed and work procedure undertaken in accordance with:
          a.    The approved plans/documents and conditions detailed in this Decision Notice;
          b.    All relevant Noosa Council Planning Scheme Policies, standard drawings,
                standard specifications and guidelines;
          c.    The latest version of the Healthy Waterways document “Water Sensitive Urban
                Design Technical Design Guidelines for South East Queensland” for all water

                                                                                      Page 19 of 26

Section 20

GENERAL COMMITTEE MEETING MINUTES                                             14 FEBRUARY 2022


                quality devices to be constructed on site.
    Roadworks
    70.   The installation and/or modification of any traffic signs, street signs, line marking and
          Raised Reflective Pavement Markings (RRPMs) must be in accordance with the
          Manual of Uniform Traffic Control Devices (MUTCD). New or relocated signage must
          be installed using the VLok installation system. All new signage must be Class 1
          retroreflective material in accordance with AS 1906.1, Retroreflective materials and
          devices for road traffic control purposes – Part 1: Retroreflective sheeting.
    71.   The developer must notify Council’s Traffic Engineer for any works involving the
          removal or modification of existing council traffic signs and/or parking bays prior to such
          works commencing.
    Pavement Design and Construction
    72.   Pavement design for privately owned works must be undertaken in accordance with
          the relevant standards. Structural integrity of the driveway and car park areas will
          remain the responsibility of the property owner/developer and must be certified by an
          RPEQ.
    Works within Road Reserve/Reinstatement
    73.   Safe pedestrian access on all streets in the vicinity of the development must be
          maintained at all times. Should footpath/road closures be necessary to carry out
          construction works, Council’s Engineering Officer must be notified prior to the proposed
          closure and all requirements complied with.
    74.   All frontage works must match neatly with existing road and verge/footpath features.
          Additional works beyond the frontage may be required to provide an acceptable
          transition to existing road and verge/footpath profiles.
    75.   Electrical conduits or other services proposed to be installed within existing and
          proposed road reserves under existing sealed carriageways, concrete pathways,
          concrete/sealed driveways or significant vegetation must be installed by boring.
          Trenching is not permitted, unless specifically approved by Council.
    Pathways
    76.   All pathways must be constructed in accordance with the following requirements:
          a.    All footpath/cycleway must comply with Council’s Standard Drawing SEQ R-065;
          b.    Provision must be made for disabled access at all kerb crossings associated with
                pathways, in accordance with Council's current standards;
          c.    All paths must have a slip resistant surface, with a colour to match the existing
                (dark);
          d.    Expansion and contraction joints must provide a flush finish. Installation of joints
                by saw cutting is preferred to ensure a smooth ride for cyclists;
          e.    Pram ramps where required.
          f.    The required work includes any modifications to ensure the footpath finishes
                flush with all existing service covers and the like, or alternatively these services
                are raised or altered, so as not to create a pedestrian safety hazard.
    77.   Pathways must:
          a.    terminate in a manner that ensures smooth transition to existing surfaces for
                public safety;
          b.    be designed and constructed to comply with the Disability Discrimination Act
                (DDA), Access to Premises Standard, Austroads and relevant sections of

                                                                                     Page 20 of 26

Section 21

GENERAL COMMITTEE MEETING MINUTES                                           14 FEBRUARY 2022


               AS1428 Design for access and mobility.
    Site Access and Driveways
    78.   Driveway crossovers must be constructed generally in accordance with Council’s
          Standard Drawing RS-051.
    79.   Any existing unnecessary or redundant property accesses must be removed, and the
          kerb, footpath and verge area reinstated to match the existing footpath and/or verge
          treatments. Grassed verge areas to be reinstated must be provided with 100 mm
          topsoil and grass seed or turf, and must be maintained by the developer until
          established.
    80.   The following must be complied with during the construction of the required
          crossover/driveway:
          a.   The driveway surfacing must consist of either an approved hot mixed asphaltic
               concrete or patterned/plain concrete;
          b.   The driveway must be constructed so as not to concentrate stormwater runoff
               onto neighbouring properties;
          c.   Where there is an existing pedestrian path, a matching crossfall must be provided
               for the driveway on the alignment of the path, for the full width of the path;
          d.   The property accesses must be located a minimum of 1m clear of existing power
               poles, streetlights or other signage. The developer is responsible for any
               necessary relocation of existing services to provide this clearance and must
               contact the relevant service authorities and comply with their requirements in
               relation to these works.
    Earthworks and Retaining Walls
    81.   All earthworks must be undertaken in accordance with the provisions of AS 3798
          Guidelines on Earthworks for Commercial and Residential Development, with
          geotechnical testing undertaken in accordance with Section 8 of the Standard, and to
          a minimum of ‘Level 2’ as defined in Appendix B. Test results as required by AS 3798,
          and a certificate of quality and uniformity of fill must be provided by a RPEQ and
          submitted to Council prior to Council undertaking the On-Maintenance inspection.
    82.   Fall protection must be provided to retaining walls that are over 1m high.
    83.   Slope and batters are a maximum grade of:
          a.   1 in 6 where in proximity to waterbodies;
          b.   1 in 4 for grassed areas;
          c.   1 in 3 for planted areas;
          d.   1 in 2 for combined structural engineering and planting solutions.
    Stormwater Drainage
    84.   Appropriate scour protection must be provided at the outlet of all stormwater pipes
          including temporary outlets.
    85.   Works associated with this permit must not adversely impact on the existing drainage
          conditions on other properties (e.g. by blocking or interfering with natural overland
          flows).
    86.   Construction of all internal stormwater drainage works must comply with the relevant
          section/s of Australian Standard AS/NZS 3500.3.




                                                                                    Page 21 of 26

Section 22

GENERAL COMMITTEE MEETING MINUTES                                           14 FEBRUARY 2022


    Landscaping
    87.   The development site must be landscaped. The works must be undertaken in
          accordance Noosa Plan PSP 2 – Landscaping and generally in accordance with the
          approved Landscaping Plans and in particular:
          a.   The along the south side of the easement must include native species that
               effectively screen the development and grow to a minimum mature height of 8m.
          b.   Plantings along the eastern side of the bio basin must grow to a minimum height
               of 4m and provide screening to the car parking area.
          c.   The proposed 25 litre pot size feature trees within the front setback (facing
               Doonella Street) must be replaced with 45 litre pot size plants
          d.   The existing street trees in the road reserve may be removed. If removed they
               must be replaced with 4 x ex-ground Delonix regia (Poinciana’s) 400L trees as
               shown on the approved landscape plans.
    88.   The finished level of all mulch in garden beds and landscaped medians is to be a
          minimum of 50mm below the level of the adjacent top of kerb. All landscaping is to be
          constructed in accordance with Council’s Planning Scheme Policy PSP2 Landscaping.
    89.   Suitable root barriers must be installed where proposed trees are adjacent to paths,
          pavement etc in accordance with Council’s Planning Scheme Policy PSP2
          Landscaping.
    Damage to Services and Assets
    90.   Any damage caused to existing services and assets as a result of the development
          works must be repaired at no cost to the asset owner at the following times:
          a.   where the damage would cause a hazard to pedestrian or vehicle safety,
               immediately; or
          a.   where otherwise, upon completion of the works associated with the development.
    Any repair work which proposes to alter the alignment or level of existing services and assets
    must first be referred to the relevant service authority for approval.
    Erosion & Sediment Control - Works adjacent to High Ecological Significance Water
    91.   Prior to the requesting the pre-start meeting the applicant must engage a Certified
          Professional and Erosion Control to prepare and provide to Council scheduling plans
          for the development which demonstrate that construction can be undertaken in a
          manner consistent with Accepted best practice standards and all relevant conditions of
          this approval. * (Refer to Advisory Note).
    92.   The applicant must engage a CPESC, or other suitably trained professional, (i.e. who
          has completed the CPESC training, and has a minimum of 5 years site experience
          supervising Erosion and Sediment Control management) to undertake weekly site
          visits to inspect and certify whether or not required Erosion and Sediment controls are
          properly installed and maintained to achieve the requirements on this approval.
    93.   Construction must be managed such that less than 2,500m2 of soil is exposed at any
          time.
    94.   Exposed soil is only permitted between the months of May to October, and all
          catchments with these soils must drain to sediment treatment features to achieve
          50mg/L TSS prior to release of waters from the site. Outside these months the site
          must achieve a C factor of 0.05 at all times.
    95.   A construction hold point with a council delegate and supervising RPEQ must be
          established prior to commencement of cut to fill earthworks for each stage of the
          development. The hold point must be held as soon as reasonably practical and prior to

                                                                                   Page 22 of 26

Section 23

GENERAL COMMITTEE MEETING MINUTES                                              14 FEBRUARY 2022


          the first rain event forecast following initial tree clearing or removal of soil stabilising
          material for each stage. At the hold point inspection, all required sediment basins,
          drains and bunds to divert waters away from disturbed soil or soils about to become
          exposed through cut to fill activities must be installed. All areas that will not require
          earthworks in the imminent cut to fill operation must be stabilised to prevent
          entrainment of sediments into receiving waters.
    96.   Cut to fill earthworks must not commence until after the Supervising CPESC has
          certified that all installed erosion and sediment controls required by this approval are
          sized in accordance with conditions of the approval and the written acceptance of the
          certification is provided to the supervising RPEQ by Council officers.
    97.   Prescribed Water Contaminants (as defined in Schedule 10 of Environmental
          Protection Regulation 2019) must not be released from the site or to waters within the
          site, or be likely to be released should rainfall occur, unless all reasonable and
          practicable measures are taken to prevent or minimise the release and concentration
          of contamination.
    98.   Sediment and erosion control measures must be in place prior to works commencing.
          If such measures are not in place or are not satisfactory, “on the spot” fines may be
          issued. Such fines can be issued if sediments from the site are found to enter or have
          the potential to enter Council’s stormwater system, natural waterways, any
          downstream stormwater filtration system or adversely impacting on other properties.
          The sediment and erosion control design and measures have NOT been approved, it
          is the site's Supervising Engineer who is responsible for ensuring that the sediment
          and erosion control measures have:
          a.    Been duly designed by an RPEQ or CPESC and constructed in accordance with
                "best practise" methods;
          b.    Been revised by an RPEQ or CPESC to address the issues raised by changes
                in the projected construction schedule and/or methods;
          c.    Been revised to address predicted rainfall events, and
          d.    Achieve the desired environmental outcomes.
    99.   Council may request further controls to be installed should the implemented measures
          be found inefficient.
    100. The erosion and sediment control measures must be designed, installed and
         maintained in accordance with the supervising engineer instructions and the current
         best practice standards * (Refer to Advisory Note).
    101. The developer must ensure non-essential exposure of soil is prevented by restricting
         the extent of disturbance and minimising the duration of soil exposure to adverse
         weather conditions and effectively turf, cover or stabilise any disturbed area without
         delay and prior to rainfall occurring.
    102. The developer in conjunction with the engaged CPESC must ensure measures
         installed to divert the upstream water are designed and certified by the supervising
         RPEQ and installed prior to commencement of bulk earthworks.
    103. The developer must ensure sediment does not leave the site or enter onto adjoining
         properties or Council’s drainage system due to surface runoff or on tyres of vehicles
         and/or machinery. It is essential to implement appropriate approved erosion and
         sediment control measures throughout the site during all phases of construction
         including vehicle shakedown pad/grid (or similar) at the access to the construction site.
         Where sediments or other contaminants are deposited on a road, they must be
         removed so as not to enter Council’s drainage system or waterways.



                                                                                      Page 23 of 26

Section 24

GENERAL COMMITTEE MEETING MINUTES                                            14 FEBRUARY 2022


    104. Prior to the completion of the development, all site surfaces must be effectively
         stabilised. For the purpose of this condition, an effectively stabilised surface is defined
         as one that does not, or is not likely to result in visible evidence of soil loss caused by
         sheet, rill or gully erosion or lead to sedimentation, or lead to water contamination.
    Water Sensitive Design
    105. The active filter media of the bioretention device must be 27m². Active filter media area
         is the area of the bioretention basin surface that is not covered by any impermeable
         structure such as a sediment forebay, riser, etc.
    106. During construction and establishment of the bioretention devices, the supervising
         RPEQ must certify forms contained in section 3.15 of the Construction and
         Establishment Guidelines: Swales, Bioretention Systems and Wetlands (Water by
         Design, 2009). These forms and certification must be submitted to council prior to the
         sealing of the survey plan.
    107. A construction hold point with a council delegate must be established once the
         bioretention device underdrainage pipe work is installed. At the time of inspection, a
         sample of the drainage layer, transition layer, and filtration media materials must be
         stockpiled onsite accompanied by laboratory results that demonstrate that the media
         complies with the specifications contained in the latest version of the Guidelines for
         Soil Filter Media in Bioretention Systems (Facility for Advancing Water Biofiltration) and
         that the minimum hydraulic conductivity of 180mm/hr or as specified on the approved
         engineering plans will be achieved. The drainage layer, transition layer, and filtration
         media materials shall not be installed until the catchment draining to the bioretention
         device has 80% groundcover as determined by council’s delegate.
    108. Eighty percent (80%) of the catchment flowing to the bioretention basin must be
         effectively stabilised prior to the construction holdpoint for the Bioretention device.
    109. Prior to the release of the plan of survey, the supervising RPEQ must certify must certify
         that all hardstand areas of the development drain to a bioretention device designed
         and constructed in accordance with all relevant conditions of this approval, the Water
         by Design Bioretention Technical Design Guidelines, relevant aspects of the IPWEAQ
         Standard Drawing WSUD-drawing series and Construction and Establishment
         Guidelines: Swales, Bioretention Systems and Wetlands (Water by Design, 2009).
    Bioretention Devices - Landscaping
    110. Landscape plans must include a mixture of at least five of the following species for
         planting in the bioretention basin extended detention surface at a minimum density of
         8 plants/m2:
          a.    Carex appressa
          b.    Carex fascicularis
          c.    Ficinia nodosa
          d.    Juncus usitatis
          e.    Lomandra longifolia
          f.    Ghania sieberiana
    111. Landscape plans for the areas surrounding the bioretention basin filter media footprint
         must be arranged to minimise shading to the filter media footprint are. Suitable plants
         include the following:
          a.    Cared appressa
          b.    Carex fascicularis
          c.    Ficinia nodosa

                                                                                    Page 24 of 26

Section 25

GENERAL COMMITTEE MEETING MINUTES                                           14 FEBRUARY 2022


         d.    Juncus usitatis
         e.    Lomandra longifolia
         f.    Ghania sieberiana
         g.    Banksia robur
         h.    Dianella brevipendunculata
         i.    Themada triandra
         j.    Cymbopogan refractus
         k.    Melaleuca thymifolia
    112. Where landscaping/garden beds are proposed adjacent to the bioretention basin, or
         where the basin is located adjacent to naturally forested areas, a 900mm deep root
         barrier must be installed to the interface between the landscape/garden/forest area and
         the bioretention basin to prevent root intrusion to the biobasin infrastructure.
    113. Landscaping to the surface of the bioretention basin filter media area must not
         commence until 80% of building work within each contributing catchment is complete
         or after 3 years, whichever occurs first. An uncompleted works bond of 150% of the
         value of the planting to the surface of the bioretention basin filter media area must be
         provided to Council prior to the release of the Plan of Survey.
    114. Where required, mulch within the batters of bioretention basins must be installed in a
         manner that it will not escape into receiving stormwater drainage infrastructure or water
         courses.
    Bioretention Devices - Education
    115. The development shall be provided with approved permanent signage that is deigned
         in accordance with Noosa’s Look and Feel document to educate the public on the
         function of the bioretention basin. The wording for the signage for each bioretention
         basin is to include: “BIORETENTION BASIN - This bioretention basin reduces the
         pollution of our waterways by reducing the amount of heavy metals, litter, suspended
         solids, and nutrients discharged to Lake Doonella”.
    FOLLOWING CONSTRUCTION / PRIOR TO THE ON-MAINTENANCE INSPECTION
    Certification
    116. Upon completion of the work a certificate must be issued by an RPEQ certifying that
         the works have been constructed in accordance with the Operational Works permit.
    117. A condition report of the drainage system must be completed for agreement prior to
         requesting the works to be accepted On-Maintenance. The condition report is to
         include a CCTV inspection of the existing pipe and must include at least 50m upstream
         and downstream of all works.
    As Constructed Plans and ADAC XML Files (Council)
    118. Prior to acceptance of civil works to become Council assets “On Maintenance”,
         satisfactory “As-Constructed” records must be submitted to Council. The bundle of “As
         Constructed” information must include:
         a.    As-Constructed Engineering Drawings. Data is to be submitted in an electronic
               drawing file format (.dwg), with all plans clearly endorsed “As-Constructed”, along
               with the accompanying hardcopies (PDFs of the As-Constructed .dwg drawing
               files), and;
         b.    ADAC XML Digital File. ADAC File format (ADAC - Asset Design As Constructed)
               prepared in accordance with industry standards and recorded in “MGA - UTM56
               / GDA94” projection.

                                                                                   Page 25 of 26

Section 26

GENERAL COMMITTEE MEETING MINUTES                                           14 FEBRUARY 2022


          c.    Please Note: Further information and advice relating to the as-constructed
                drawing presentation, as-constructed survey capture and associated guidelines
                for preparation of a compliant ADAC XML digital file are available on the webpage
                titled “As-Constructed Guidelines” and accessible at the Noosa Council Website:
                Planning & Development / Development Tools & Guidelines / As-Constructed
                Guidelines.
          d.    The “As-Constructed” drawings will require certification by a:
                i.    Qualified experienced Civil Engineer (RPEQ) confirming design intent and
                      conformance with applicable standards and specifications, along with the
                      relevant descriptions of assets, services and structures and;
                ii.   Licensed Surveyor in regard to the cadastral and locational information,
                      levels and applicable survey datum.
          e.    The data must be in accordance with Council’s “Planning Scheme Policy 6 –
                Engineering Design Standards”, and fully detail the levels for all engineering
                works including but not limited to the drainage network and structures, finished
                ground and pavement surface levels.
     On Maintenance
     119. All municipal works must be accepted ‘On Maintenance’ by Council in accordance with
          Council’s relevant Planning Scheme Policy prior to the On-Maintenance inspection. To
          achieve ‘On Maintenance’, the supervising RPEQ must submit to Council:
          a.    certification that all works have been undertaken and completed in accordance
                with the requirements of this Permit;
          b.    as Constructed details in accordance with Council’s Planning Scheme Policy;
          c.    maintenance and operational manuals for all proprietary or site specific devices.
     Off Maintenance
     120. Prior to requesting an Off Maintenance inspection the developer must provide a written
          request for the Off Maintenance inspection.
     121. A re-inspection fee in accordance with Council’s Fees and Charge Register will be
          charged where:
          a.    a Council inspection reveals works do not comply with approval requirements;
          b.    submitted certification falsely states works comply with approval requirements.
                                                                          Carried unanimously.



The meeting closed at 2.16pm.