App 5 - Wastewater Design
3.3 Soil Classification
Soil Classification - Adopted
Borehole Nos 1&2
Soil Category Adopted 5
Indicative Drainage Poorly Drained
Structure Strongly
Texture Sandy Clay
Indicative Permeability P (m/d) as Ksat* 0.12 - 0.5
Recommended DLR(AS/NZS 1547 / 2000) 10
4.0 Recommendations:
4.1 Treatment Facility:
The on-site treatment facility to service the new detached dwelling is to be an Advanced Enviro-Septic System (AES).
This system has a Chief Executive Approval # 14/2014 for Advanced Secondary Effluent. The Equivalent Person
(EP) for this system is to be no less than 2.
A new min 3000lt septic tank is to be installed to service the amenities in the shed/workshop and stables. This tank
must comply with AS/NZS:1546. All wastewater from these amenities is to be directed to the septic tank then to the
AES bed.
The Land Application Area is to be an Advanced Enviro-Septic Infiltration Bed of 24m2.
5.0 Design Calculation
The serviceable life of the Land Application Area will be compromised if the design flow is exceeded. Any
proposed changes to the position of the Land Application Area, System Type or House Design will require a
reassessment of this site. For our calculations we have assessed the design flow as follows:
Design Calculation
DLR (mm/d) (secondary quality effluent) 10
Hydraulic load (lt/day/person) Tank Water / 1 bedroom equivalent 120
Design Flow Q (lt/day) EP: 2 240
Design sizing calculation L = Q /(DLRxW)
= (240 / 10)
Disposal area A+B (square metres) AS/NZS1547:2000 24m2
Nominated Configuration (metres) AES System Design Calculations = 6.6 x 3.64m (L xW) 24m2
A new 3000L Septic Tank is required. AES System EP 2
C Copyright Lance Picton 2019 design & content. 3/10