Noosa Civic Expansion
Bushfire Assessment Report
> the High Potential Bushfire Intensity Class assigned to Covenant J using the new SPP methodology is also
conservative and there are reasonable grounds for classifying this area to a Low Potential Bushfire Intensity
Class under post-development conditions due to the limited extent, narrow width and isolation of this patch
of vegetation from larger areas of hazardous vegetation in the locality; and
> in the event of a bushfire occurring within Covenant J access for fire suppression purposes would be
available from the eastern, southern, western and northern perimeters of Covenant J.
It is also relevant to note all buildings constructed adjacent to Covenant J will need to be designed and
constructed in a manner that is appropriate to their level of exposure to flame, radiant heat and ember attack
as determined in accordance with Australian Standard AS3959-2009 Construction of buildings in bushfire
prone areas.
4.2 Water Supplies
The SPP 1/03 Guideline states that, for all development involving new or existing buildings with a gross floor
area greater than 50m2, each lot has:
a) a reliable reticulated water supply that has sufficient flow and pressure characteristics for fire
fighting purposes at all times (minimum pressure and flow is 10 litres a second at 200 kPa); or
b) an on-site water storage of not less than 5,000 litres (e.g. accessible dam or tank with fire
brigade tank fittings, swimming pool).
The proposed development would be serviced by a reticulated water supply that would be available for fire
fighting/suppression purposes. To ensure that access to this reticulated water supply is readily available and
adequate for fire suppression and property protection purposes in the event of a bushfire:
> a series of hydrants will be established around the perimeter of the Noosa Civic expansion, including the
western perimeter adjoining Covenant J; and
> a minimum water pressure and flow of 10 litres a second at 200kPa will be available at all times.
4.3 Lot Layout and Siting
The SPP 1/03 Guideline recommends that lots be designed so that their size and shape allow for the following.
1. Efficient emergency access to buildings for fire-fighting appliances (e.g. by avoiding long narrow lots
with long access drives to buildings).
2. Setbacks and building siting such that buildings can be situated in locations of lowest hazard within the
lot and appropriate setbacks from hazardous areas can be established and maintained.
With respect to the above, the proposed Noosa Civic expansion:
> does not involve the creation of any new lots;
> involves extensions to Hofmann Drive and the internal ring-road that will surround the existing Noosa Civic
development and proposed development with multiple access points to Walter Hay Drive; and
> provides building setbacks as discussed in Section 4.1 herein.
4.4 Firebreaks and Maintenance Trails
The SPP 1/03 Guideline recommends that for development that will result in multiple buildings or lots,
firebreaks are provided by:
a) a perimeter road that separates lots from areas of bushfire hazard and that road has:
- a minimum cleared width of 20 metres; and
- a constructed road width and weather standard complying with local government
standards.
OR
QIC Noosa Civic Pty Ltd Version 2 23 April 2015
J13041_Bushfire Assessment V2.docx Commercial in Confidence Page 18
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalLog in to download the original file
Very large file: the download may take a few minutes. If you are on mobile data, it is best to wait until you are on Wi-Fi.
Searchable page text hides email addresses. Original files are unchanged and may show email addresses.