Approved Plan OPW22-0273 · OPW22/0273
Plans and drawings: the text below has words only, no drawings.
LEGEND NOOSA COUNCIL
Flow Direction
32 APPROVED PLAN
Catchment Zone SP188268 OPW22/0273 13 MAR 2023
Subject to Conditions
The Rational Method (CTM1) - Minor Storm.
Q = (C . I . A)/360
Minor Storm for CMT 2 (10%)
Q = Peak Flow Rate (m3/s)
Intensity (5 min) = 226mm/hr
C = Coefficient of Discharge (QUDM Section 4.5 (c10))
From Table 4.5.1 Fi = 0.9
Iy = Rainfall Intensity (mm/hr)
From Table 4.5.2 Fy = 1.0 (Minor Storm 10% AEP)
A = Area in Hectares (Ha) 1
GARAGE Minor Storm for CMT1 (10%)
From Table 4.5.3 C10 = 0.88 (10
a 1 in 10 year ARI (74mm/hr))
= one hour rainfall intensity for
Intensity (5 min) = 226mm/hr
Therefore;
From Table 4.5.1 Fi = 0.9
Q = (0.88x226x0.0081)/360 = 0.00447 m3/s or 4.47 L/s
From Table 4.5.2 Fy = 1.0 (Minor Storm 10% AEP)
EXISTING 1
From Table 4.5.3 C10 = 0.88 (10 = one hour rainfall intensity for
Resultant Depth in Kerb at A-A = 20mm.
a 1 in 10 year ARI (74mm/hr))
HOUSE Therefore;
Major Storm for CMT2 (1%)
Intensity (5 min) = 332mm/hr
Q = (0.88x226x0.017)/360 = 0.0094 m3/s or 9.4 L/s From Table 4.5.1 Fi = 0.9
19 Major Storm for CMT1 (1%)
From Table 4.5.2 Fy = 1.2 (Major Storm 1% AEP)
1
From Table 4.5.3 C10 = 0.88 (10 = one hour rainfall intensity for
SP188268 Intensity (5 min) = 332mm/hr
From Table 4.5.1 Fi = 0.9
a 1 in 10 year ARI (74mm/hr))
Therefore;
Reshape Existing From Table 4.5.2 Fy = 1.2 (Major Storm 1% AEP)
1
Q = (1.05x332x0.0081)/360 = 0.0078 m3/s or 7.85L/s
Landscape to Ensure From Table 4.5.3 C10 = 0.88 (10 = one hour rainfall intensity for Resultant Depth in Kerb at A-A = 25mm.
a 1 in 10 year ARI (74mm/hr))
Overland Flow.
Therefore;
CTM1 Q = (1.05x332x0.017)/360 = 0.0165 m3/s or 16.5 L/s Using Mannings Equation for Kerb Depth A-A.
For Minor Flow (10% Storm);
Area, A(m²) = 0.009
Wetted Perimeter P (m) = 0.9
Kerb Grade, S(m/m) = 0.024
Mannings Value 'n' = 0.014
CTM2 31 Resultant;
ALIGNMENT OF LOW Velocity, V(m/s) = 0.51
A POINT IN DRIVEWAY ON
SP188268 Discharge, Q (m³/s) = 0.004
Resultant Depth at Invert is 20mm.
CONTINUATION OF
A
LOWPOINT IN DRIVEWAY For Major Flow (1% Storm);
OF No 14 Area, A(m²) = 0.014
Wetted Perimeter P (m) = 1.126
Kerb Grade, S(m/m) = 0.024
Flow Path Mannings Value 'n' = 0.014
Resultant;
Velocity, V(m/s) = 0.59
Reshape Landscape Discharge, Q (m³/s) = 0.008
For Drainage over Resultant Depth at Invert is 25mm.
Driveway
Neighbouring
Existing
A Driveway Invert.
Existing Driveway Match to Existing
40mm Invert
Boundary
A
Property
5.7% Driveway
Existing
Proposed Driveway
380
Kerb
12% Proposed Driveway
3.0% Road 3%
3600 1754 1246
SECTION A-A
No. Description Date JA Young APPROVED
AAA Design & Development Pty Ltd Jose David Lesmes Tirado STORMWATER CALCULATIONS
34/13 Norval Court, MAROOCHYDORE, QLD 4558 12 Grosvenor Tce,
Project number Y010-01
Tel/Fax: (07) 5479 6747
NOOSA HEADS QLD 4567
Mob: 0422 039 247 Date 03/02/2023 3847 - 01A
design & K.A.J
BEng, MIEAust, RPEQ 7198 Drawn by
email: [email protected] For & on behalf of AAA
A Driveway Amend 24/01/2023 DRIVEWAY PROPOSAL Design & Development Consulting Checked by D.L.T. Scale @ A3 1:100
Document Set ID: 22334920
Version: 1, Version Date: 08/03/2023