25-0424 Structural Issue A(1)(1)

of 6

Page text shows just the words. Original shows the document exactly as it was published.

                                             PROPOSED NEW JETTY
                                 at LOT 444 (#18) THE PENINSULA, NOOSAVILLE
                                          BUILDER: PONTOON WORKS
                                               Job No.: 25-0424
                                                                                                        DRAWING REGISTER
                                                                     Sheet No.          TITLE                                  REVISION   Date of Issue
                                                                       S01              GENERAL NOTES                      A              05/09/2025
                                                                       S02              JETTY LOCALITY PLAN                A              05/09/2025
                                                                       S03              JETTY PILE LAYOUT & DETAILS        A              05/09/2025
                                                                       S04              JETTY FRAMING LAYOUT & DETAILS     A              05/09/2025
                                                                       S05              CONNECTION DETAILS                 A              05/09/2025




                                                  Office:   Suite 35/13 Norval Court, Maroochydore
                                                  Ph:       (07) 5444 5578
                                                  Web:      hrdesigngroup.com.au
                                                  Email:    [email protected]
Cromar Winning Consulting Engineers Pty Ltd T/A
ABN 30 169 626 957
Log in to download the original file

25-0424 Structural Issue A(1)(1).pdf · 268 KB (small file)

Full text of the other 5 pages

Page 2

                   1 - GENERAL NOTES:                                                                                           5 - REINFORCED CONCRETE:                                                                                            6 - STRUCTURAL STEEL:                                                                                               7 - MASONRY BLOCKWORK & BRICKWORK (CONT.):
                   1.0   These drawings shall be read in conjunction with HR Design Group specification and                     5.0    All work shall be in accordance with all current Australian Standards as a MINIMUM                           6.0     All steelwork shall be constructed in accordance with code of practice AS4100 Steel Structures              7.15   All wall intersections shall be of bonded construction or tied with medium duty ties at
                         certification, all architectural and other consultants drawings and specifications.                           work standard.                                                                                                       Code, AS1554, AS1163, AS3679, AS4600 and all other codes of practice referred to therein.                          400mm max. crs.
                         Any discrepancies shall be referred to the architect or project manager for a
                         decision before proceeding with the work.                                                              5.1    Concrete shall have a characteristic compressive strength after 28 days of not less                          6.1     Steel quality shall conform with the following Australian Standards UNO:                                    7.16   Maximum height of core-filling :-
                                                                                                                                       than that listed below for the various concrete elements UNO.:                                                       - Steel Plates & Sections AS3679 Grade 300                                                                         140mm wide blockwork - 1.8m max
                   1.1   Dimensions SHALL NOT be obtained by scaling off the drawings.                                                       i)      FOOTINGS                            - 25 MPa                                                           - Rectangular Hollow Sections AS1163 Grade C350 LO                                                                 190mm wide blockwork - 3.4m max
                                                                                                                                             ii) INTERIOR GROUND SLABS                   - 25 MPa                                                           - Circular Hollow Sections AS1163 Grade C350
                   1.2   All dimensions shall be checked by Builder prior to commencement of works.
                                                                                                                                             iii) EXTERIOR GROUND SLABS                  - 32 MPa                                                           - Square Hollow Sections AS1163 Grade C350
                   1.3   Prior to the commencement of construction the Builder shall check and                                                                                                                                                              - Purlins/Girts AS1397 Grade G450 Z350                                                                      8 - TIMBER FRAMING:
                                                                                                                                             iv) BLOCKWORK CORE FILL                     - 20 MPa
                         co-ordinate with the Architect and other consultants all steps, falls, rebates,                                     v) SUSPENDED SLABS                          - 40 MPa                                                   6.2     Unless noted otherwise all welds shall be 6mm continuous fillet E41XX electrode,                            8.0    The timber roof and floor framing layouts shown on these engineering drawings form
                         setdowns, chases and penetrations. Any discrepancies with our drawings shall
                                                                                                                                                                                                                                                            all bolts M16 4.6/S, all plates 10mm thick.                                                                        the basis for the design of the structural support elements and the footings.
                         be referred to us for clarification and/or revision. Under no circumstances                            5.2    Minimum clear cover to reinforcing bar shall be in accordance with the following table. However
                                                                                                                                       cover to reinforcing noted on the plans shall take precedence over those stated in the table.                                                                                                                                           Alternative roof and floor framing layouts will only be permitted with the written
                         shall the Builder proceed with the works until all discrepancies have been                                                                                                                                                 6.3     Unless noted otherwise, bolt holes shall be 2mm greater than specified bolt size.
                                                                                                                                             i)     FOOTINGS                            - 50mm TO ALL SIDES                                                                                                                                                                    approval of the structural Engineer.
                         satisfactorily resolved.
                                                                                                                                             ii) INTERIOR GROUND SLABS                  - 30mm TOP & BOTTOM                                         6.4     The steelwork sub-contractor's shop drawings shall be submitted to the Engineer for
                                                                                                                                                                                                                                                                                                                                                                        8.1    All timber roof, wall and floor structural members that are designed by the
                   1.4   All workmanship and materials shall be in accordance with the relevant Australian                                   iii) EXTERIOR GROUND SLABS                 - 45mm TOP & BOTTOM                                                 review before fabrication commences.
                                                                                                                                                                                                                                                                                                                                                                               Contractor shall be designed in accordance with Engineering principles, AS1684 and
                         Standards, the BCA and local council regulations.
                                                                                                                                5.3    All concrete shall be mechanically vibrated. Vibrator shall not be used to spread                            6.5     Fabricator to check all dimensions on site with contractor.                                                        AS 1720.1 and shall be handled, erected, installed and braced in accordance with
                   1.5   The contractor shall be responsible for the maintaining the structure and adjacent                            concrete.                                                                                                                                                                                                                               AS 1860 and AS 4440.
                         structures in a stable condition, ensuring no part is overstressed during the works.                                                                                                                                       6.6     Internal steelwork shall be blast cleaned to class 1 and coated with minimum 100µm high
                                                                                                                                5.4    All concrete surfaces shall be cured using an approved method for seven (7) days                                     build Alkyd primer before erection. External steelwork shall be blast cleaned to class 2.5                  8.2    At the time of the frame inspection, the Contractor shall provide all engineering
                                                                                                                                       immediately after concrete is hard. Confirm method of curing with Engineer prior to                                  and hot dipped galvanised to AS4680 with a coating mass of 600g/m2 (average).                                      design, checking and inspection certification required by the statutory authority, duly
                                                                                                                                       use. Following concrete placement and as required during the finishing process,                                                                                                                                                         signed by a Registered Professional Engineer of Queensland (RPEQ), for all of the timber
                   2 - SAFETY RISK & HAZARDS                                                                                                                                                                                                        6.7     The structural steel framework and bracing members shown on the plans are those                                    roof, wall and floor structural members that have been designed by the Contractor.
                                                                                                                                       aliphatic alcohol or approved curing compound shall be applied to exposed surfaces
                   2.0   It is essential that an adequate safety plan is prepared by the contractor for the                                                                                                                                                 required in the design for the completed structure only and the contractor shall be
                                                                                                                                       to limit moisture loss from the fresh concrete.                                                                                                                                                                                  8.3    In addition, the Contractor shall inspect and certify that the roof wall and floor
                         works. HR Design Group may not be aware of all safety risks and hazards involved                                                                                                                                                   responsible for providing any necessary temporary connections, supports and bracing
                                                                                                                                5.5    Sizes of concrete elements do not include thickness of applied finishes.                                             during the erection process to maintain the stability and safety of the steelwork                                  framing that are designed by the Contractor, have been constructed in accordance
                         in this project and the absence of comment does not imply that there are no
                                                                                                                                                                                                                                                            throughout construction.                                                                                           with their design.
                         risks or hazards.
                                                                                                                                5.6    Construction joints where not shown shall be located to the Engineer's approval.
                                                                                                                                                                                                                                                    6.8     Encased steelwork shall not be painted and shall be wrapped with F41 fabric, 50 cover.                      8.4    Except where otherwise shown on these Engineering drawings, all timber connection,
                                                                                                                                5.7    No holes, chases, blockouts, ducts or embedment of pipes other than those shown                                                                                                                                                         tiedown and bracing details shall comply with AS 1684 and AS 1720.1.
                   3 - LOADINGS:                                                                                                       on the structural drawings shall be made in concrete members without prior approval                          6.9     The steel fabricator shall provide all bolts necessary for the erection of the steelwork
                                                                                                                                                                                                                                                                                                                                                                        8.5    All timber members used in the construction shall have a minimum level of preservative
                                                                                                                                       of the Engineer.                                                                                                     and bolt holes and cleats necessary for the erection of timber works as shown, noted
                   3.0   The structural work as shown on these drawings has been designed for the following                                                                                                                                                 or implied on these drawings or architects drawings and specification.                                             treatment to meet the appropriate hazard class as specified in AS 1604.1 Appendix F.
                         cases :                                                                                                5.8    No additives shall be added or applied to the concrete mix without the approval of
                                                                                                                                       the Engineer.                                                                                                6.10    The roof structure has been designed for normal roof loads only and does not allow                          8.6    The Contractor shall provide protection of the construction against termite attack in
                               i)    General floor live load of 1.5 kPa uniform distributed load
                                                                                                                                                                                                                                                            for any extraneous loads such as hoists, monorails etc ... except where shown on                                   accordance with NCC and AS 3660.1 and QMBA technical circular T -01-02/2001.
                               ii) General floor live load of 1.8 kN point load
                                                                                                                                5.9    All steel reinforcement in concrete elements shall be inspected by the Engineer and                                  drawings.                                                                                                          The Contractor shall provide certification of treatment.
                               iii) Balcony and stair floor live load of 2.0 kPa uniform distributed load                              passed prior to pouring of any concrete.
                                                                                                                                                                                                                                                    6.11    When shop splices are necessary in beams, the position of the splice shall be
                   3.1   Load combinations have been calculated in accordance with AS1170.1 requirements.                       5.10   All reinforcement shall be supported on plastic chairs, generally at not greater than                                approved by the Engineer.                                                                                   9 - COMPACTION OF FILL:
                                                                                                                                       800mm centres in both directions. Bars shall be tied at alternate intersections.
                                                                                                                                       Conduits, pipes etc ... shall not be placed in the cover of the concrete.                                    6.12    Provide protective coating on all steelwork partially embedded in concrete UNO. The                         9.0    Crawler plant track rolling is usually inadequate for compacting fill to approved
                   4 - FOUNDATIONS:                                                                                                                                                                                                                         coating should be non-conductive and extend a minimum of 200mm into the concrete                                   standards and if fill compaction is not of a suitable standard, then footings and the
                                                                                                                                5.11   All reinforcement shall comply with the requirements of the relevant Australian                                      in accordance with AS2312-2002 and a minimum of 100mm above the concrete.                                          slab are to be supported on bored piers.
                   4.0   Refer to the attached soil report for reference to the required founding material                             Standards.
                         for the footings and soil profile for the site.                                                                                                                                                                                                                                                                                                9.1    After the site has been stripped of all topsoil, organic material and debris, proof
                                                                                                                                5.12   Concrete to have a maximum aggregate size of 20mm with 80mm maximum slump                                                                                                                                                               rolling with a vibrating roller of 5 to 10 tonne capacity shall be carried out. If
                   4.1   The founding material and steel reinforcement to the footings and slab shall be
                                                                                                                                       and a water/cement ratio of not greater than 0.65.                                                           7 - MASONRY BLOCKWORK & BRICKWORK:
                         inspected by the Engineer prior to the pouring of concrete. 24 hours notice is                                                                                                                                                                                                                                                                        neighbouring structures are likely to be affected by vibration of the roller, a static
                         required for inspection.                                                                                                                                                                                                   7.0     Materials and workmanship shall comply with the requirements of AS3700 and AS2733                                  sheepsfoot roller may be used in clay soils by reducing the depth of fill layers to
                                                                                                                                5.13   The maximum permissible transport time for concrete between batching and placement
                                                                                                                                                                                                                                                            as a minimum standard.                                                                                             150mm.
                                                                                                                                       on site shall be in accordance with the following table.
                   4.2   The Engineer shall be notified immediately should foundation material differ from
                         that stated in the soils report.                                                                                                                                                                                           7.1     All masonry blocks shall have a min unconfined compressive strength of 15 Mpa. All                          9.2    Soft spots under rolling should be excavated and filled, then re-rolled.
                                                                                                                                                    AMBIENT AIR                                MAX. BATCHING TO
                                                                                                                                                                                                                                                            loadbearing bricks shall have a min unconfined compressive strength of 10 Mpa.
                                                                                                                                                   TEMPERATURE                                  PLACEMENT TIME                                                                                                                                                          9.3    Controlled fill is material that has been satisfactorily compacted to provide adequate
                   4.3   Topsoil containing plant roots and any organic material shall be removed from the
                                                                                                                                                     10° - 24°C                                    120 minutes                                      7.2     Mortar shall have the following mix proportions, 1 part cement : 0.5 part lime : 4.5 parts                         strength without excessive settlement.
                         area prior to filling and compaction.
                                                                                                                                                     25° - 27°C                                     90 minutes                                              clean sand. Sand shall be clean, well graded and free of silt and clay.
                   4.4   For sites where cut and fill is required, the fill shall continue past the edge of the                                      28° - 30°C                                     60 minutes                                                                                                                                                          9.4    Compaction requirements for fill material is as follows :-
                         building at least 1 metre and shall be retained or battered beyond this point by a                                          31° - 33°C                                     45 minutes                                      7.3     Provide medium duty galvanised wall ties at 600mm crs. vertically & horizontally.                                  i)  Sand fill up to 800mm deep is to be compacted in 200mm layers by a
                         slope not steeper than 2 horizontal to one vertical. The interior of the slab shall be                                      34° - 36°C                                     30 minutes                                              Embedment of ties in the mortar joint shall be a minimum of 50mm into each leaf.                                       vibrating plate or vibrating roller. The fill is to have an n value of 7 using a
                         founded on compacted material and the edge beams shall be founded on natural soil                                            37°C+                                 No placement of concrete                                        Stainless steel ties shall be used in locations < 1 km from the coast.                                                 standard penetrometer test. Density index is to be not less than 75% in
                         or controlled fill (refer soil report).                                                                                                                         unless chilled water or ice in mix                                                                                                                                                        accordance with AS 1289.
                                                                                                                                                                                                                                                    7.4     Hollow blocks to be filled with concrete shall have cleanout blocks laid at the base
                                                                                                                                                                                                                                                            course.                                                                                                            ii) Non-sand fill up to 450mm deep shall be compacted in not more than 150mm
                   4.5   The ground around the slab is to be well drained at all times by placing a gravel                      5.14   A leveling sand layer (50mm minimum in thickness) shall be placed under slab on                                                                                                                                                             layers by a mechanical roller, cloy fill shall be moist during compaction.
                         drain around the perimeter or by sloping the soil (1:10 maximum) away from the                                ground. The sand shall be salt free and compacted to 65% Density Index.                                      7.5     Additives shall not be added to the grout or mortar without the specific permission of                                 Standard compaction index is not to be less than 95% in accordance with
                         slab area. Ponding of water around the slab area is to be prevented during and after                                                                                                                                               the Engineer.                                                                                                          AS 1289.
                         construction of the slab. All water is to be drained to either the street frontage or                  5.15   A vapour barrier (200µm thick polythene sheet) shall be placed beneath the slab on
                         to existing or new field drainage pits connected to a stormwater line. Spoon drains                           ground so that the ground surface under the slab and thickenings is entirely covered in                      7.6     All mortar dags and protrusions into the block or brick cores shall be removed prior                        9.5    Testing of density index shall be done in accordance with Australian standard AS 1288.
                         are to be located at top and bottom of all batters.                                                           accordance with AS3610 and AS2870.                                                                                   to the placement of any concrete into the cavities. Loose material and debris shall be
                                                                                                                                                                                                                                                            also removed from the base of the masonry cores.                                                            9.6    Reactive clay should be avoided as fill but if used should be placed at a moisture
                   4.6   Edge footings shall be founded on material with an allowable bearing pressure not                      5.16   Slab fabric shall be lapped one full panel of fabric plus 25mm so that the two                                                                                                                                                          content which approximates the fixed equilibrium moisture content.
                         less than 100 kPa. The slab shall be founded in material with an allowable bearing                            outermost transverse wires of one sheet overlap the two outermost transverse wires of                        7.7     Fully bed solid units, face bed hollow units and fully fill vertical joints. No raking of
                         pressure not less than 50 kPa.                                                                                the sheet being lapped by 25mm.                                                                                      mortar joints is permitted.
                                                                                                                                5.17   Where brittle floor coverings such as ceramic tile shall be used, an additional layer of                     7.8     Grouting shall not commence until the mortar joints have gained sufficient strength to
                                                                                                                                                                                                                                                                                                                                                                        10 - UNCONTROLLED SHRINKAGE CRACKING:
                   4.7   Excavation adjacent to existing footings shall not extend below the underside of
                         existing footings unless instruction is obtained from the engineer.                                           SL62 Mesh shall be added to the existing slab reinforcement. If no extra reinforcement                               resist blowout and grout spaces have been cleaned out. Compaction of concrete shall                                To minimise uncontrolled shrinkage cracking the following procedures should be strictly
                                                                                                                                       is added covering should be delayed until 90 days after the slab has been placed.                                    be by vibrator or by rodding with a rod not less than 24mm diameter. Maximum                                       adhered to;
                   4.8   Notwithstanding that existing services may or may not be shown on these drawings,                                                                                                                                                  6 course height to be filled and compacted in one pass.
                         no responsibility is taken by the engineer for this information which has been                         5.18   Where service pipes penetrate the floor and or walls provision should be made for                                                                                                                                                10.0   Under no circumstances shall any water be added to the concrete truck after it leaves
                         supplied by others. The contractor shall asertain the position of all underground                             movement of the floor/walls.                                                                                 7.9    The concrete used to fill the masonry cores shall have a compressive strength of not                                the batching plant.
                         services prior to excavation.                                                                                                                                                                                                     less than 20 MPa after 28 days. The concrete shall have a maximum aggregate size of
                                                                                                                                5.19   All concrete shall be sampled and tested in accordance with AS 3600 adopting project                                10mm and a maximum slump of 230±30mm and a minimum cement content of 300kg/m3                                10.1   Slabs on ground shall be poured over a vapour barrier or compacted road base gravel
                                                                                                                                       assessment method for compressive strength and slump compliance. The results of all                                                                                                                                                     as detailed on the drawings.
                                                                                                                                       tests shall be promptly submitted to the Engineer for review.                                                7.10    All cores with reinforcement bars shall be filled with concrete, unless noted otherwise.
                                                                                                                                                                                                                                                            Where masonry blockwork is acting as a retaining structure then all cores shall be                          10.2   The concrete shall be vibrated during placement.
                                                   LAP SCHEDULE:                                                                5.20   Diagonal reinforcement shall be placed at all re-entrant corners. 2/N12 or 3-L11TM                                   filled with concrete.
                                                   MINIMUM REINFORCEMENT LAP FOR SLAB                                                                                                                                                                                                                                                                                   10.3   Aliphatic alcohol or approved curing compound shall be applied to the surface of the
                                                                                                                                       1500mm Min. long. Typical.
                                                                                                                                                                                                                                                    7.11    Reinforcement shall be placed accurately and tied securely before placement of concrete.                           concrete immediately after the initial screed and again immediately after the bull floating.
                                                   SIZE                LENGTH                                                   5.21   The edge rebate shall be flashed and drained by weep holes at not more than 1m
                                                                                                                                                                                                                                                    7.12   Unless noted otherwise vertical control joints shall be provided in blockwork at 12m crs.                    10.4   The surface of the newly placed concrete shall be protected from excessive wind by
                                                                                                                                       spacing. Weep holes shall be located above the finished ground level any
                                                   FABRIC ...............................225mm                                                                                                                                                                                                                                                                                 erecting a wind barrier such as hessian fencing when required.
                                                                                                                                       portion of a deepened rebate that cannot be drained shall be mortar filled.                                         and at 6m from corners. Vertical articulation joints shall be provided in unreinforced masonry
                                                   N12 ....................................500mm
                                                                                                                                                                                                                                                           walls in accordance with AS4773.1-2010 Section 13.3 and NCC Vol. 2 Part 3.3.                                 10.5   Once the slab is finished it shall be continuously cured for 7 days by either keeping
                                                   N16 ....................................700mm                                5.22   Approved steel reinforcement systems may be used in lieu of that stated on our plans
                                                   N20 ....................................1000mm                                                                                                                                                   7.13   No holes or chases shall be cut into blockwork/brickwork without prior approval of                                  continuously wet or covering with weighted down plastic or approved equivalent method
                                                                                                                                       (eg. Aquila steel "L" cage, Neumans F652 fabric etc ... ), provided the overall size of
                                                                                                                                                                                                                                                           the Engineer.                                                                                                       such as application of a curing compound.
                                                                                                                                       the footings and ground slab as detailed by us remains the same.
                                                                                                                                                                                                                                                    7.14   Bricks shall exhibit a max. 5 year expansion of 1.0mm/m or less, and the brick                               10.6   When early signs of plastic settlement cracks are visible, re-compact or re-trowel
                                                                                                                                5.23   All props and formwork under suspended concrete shall be removed before construction
                                                                                                                                                                                                                                                           supplier shall provide a recent test certificate confirming the above.                                              the concrete surface.
                                                                                                                                       of brickwork or blockwork above UNO.
                                                                                                                                                                                                                                                                                                                                                                        10.7   Where polished concrete finishes are specified, concrete to be 40MPa minimum with
                                                                                                                                                                                                                                                                                                                                                                               SL81 mesh UNO.




           Issue   Made By      Date              Description                                                     PROPOSED NEW JETTY                                                                                                                                                                                                                         Scale : N.T.S.                                                                           NOTES:
           A       WPH          05/09/25          Issue for construction
                                                                                                                  at LOT 444 (#18) THE PENINSULA, NOOSAVILLE
REVISION




                                                                                                                                                                                                                                                                                                                                                             Job No.: 25-0424                                                                         1. Do not scale drawings.
                                                                                                                                                                                                                                                                                                                                                                                                                                                      2. Scale is correct at A3.
                                                                                                                  BUILDER: PONTOON WORKS
                                                                                                                                                                                                                                                                                                                                                             Dwg No.: S01                                                                             3. Check and verify all dimensions
                                                                                                                  Designed By : J. SAYERS BEng (Civil) Hons                                                       Drawn By : WPH Date : 05/09/25                                                                                                                                                                                                        prior to commencement of work.
                                                                                                                  Certified By : B.R. CROMAR BEng (Civil) MIEAust CPEng RPEQ NER                                                 Date : 05/09/25   Ph: (07) 5444 5578      Email: [email protected]                                             GENERAL NOTES

Page 3

                                                                                                                                                                                                                                              Property Boundary                                                                          Projected Boundary
                                                        Property Boundary




                                                                                                                                                                                                                                                                                    Water Allocation Boundary




                                                                                                                                                                                                                                                                                                                                                                     Water Allocation Boundary
                                                                                                                                                                                                                                                                                                                        Existing Jetty
                                                                                                                                                                                                                                                                                                                        to be removed
                                            The Peninsula




                                                                                                                                          EXISTING RESIDENCE




                                                                                                                                                                                                                                                                                                       Proposed Jetty




                                                                                                                                                                                                                                                                                Property Boundary
                                                                                                                                                                                                                                                               Revetment Wall
                                                                                                                                                                                                                                                                                                                                         Water Allocation Boundary


                                                                            Property Boundary                                                                                                                                                                                                                                            Projected Boundary




           Issue   Made By   Date       Description                                             PROPOSED NEW JETTY                                                                                                                                                                                               Scale : 1:200                                                                   NOTES:
           A       WPH       05/09/25   Issue for construction
                                                                                                at LOT 444 (#18) THE PENINSULA, NOOSAVILLE
REVISION




                                                                                                                                                                                                                                                                                                                 Job No.: 25-0424                                                                1. Do not scale drawings.
                                                                                                                                                                                                                                                                                                                                                                                                 2. Scale is correct at A3.
                                                                                                BUILDER: PONTOON WORKS
                                                                                                                                                                                                                                                                                                                 Dwg No.: S02                                                                    3. Check and verify all dimensions
                                                                                                Designed By : J. SAYERS BEng (Civil) Hons                        Drawn By : WPH Date : 05/09/25                                                                                                                                                                                                    prior to commencement of work.
                                                                                                Certified By : B.R. CROMAR BEng (Civil) MIEAust CPEng RPEQ NER                  Date : 05/09/25   Ph: (07) 5444 5578   Email: [email protected]                                                     JETTY LOCALITY PLAN

Page 4

     SITE CLASSIFICATION:
    The site classification for this block, based on the attached soil          All footings to be founded on STIFF CLAYS or DENSE SANDS
    report, is Class 'N/A' as per AS2870. 'Residential Slabs and Footings'.     with an allowable bearing capacity of 100kPa. Engineer to be
                                                                                on site during excavation to confirm founding material and
                                                                                bearing capacity.
     EARTHWORKS:                                                                                                                                                                                                                                                                                                                                       65mm
                                                                                                                                                                                                                                                              315 outer diameter tube.
     1. Prepare the existing foundation below by removal of any top-soil                                                                                                                                                                                                                                                                               cover
                                                                                                                                                                                                                                                              Filled with concrete, N50/20.
         containing organic matter which could inhibit compaction                                                                                                                                                                                             Provide 6/N12 bars
     2. Proof roll the foundation and remove and reconstruct areas that
                                                                                                                                                                                                                                                              and R10 helix with 150mm pitch.
         break up or show evidence of movement under proof loading.
     3. Sand filling under slabs or footings shall be placed in 200mm
         max layers, (Uncompacted), Compacted in accordance with AS1289
                                                                                                                                                                                                                                                                                                                             315mm Ø
         E5.1 (Density to be greater than 65% in accordance with AS1289 E6.1)
     4. Fill material other than sand (ie gravel, decomposed rock or
         broken rock, free from organic material and lumps of clay) under
         slabs or footings to be compacted to achieve an density ratio                                                                                                                                                                                                 Projected Boundary
         (calculated by AS1289 E4.1) of not less that 95% at maximum
         dry density as determined by AS 1289 E1.1
         Alternatively fill is to be placed an machine track rolled and piers
         drilled/installed as per the layout plan. Compaction testing is then
         not required due to the presence of supporting piers.                                                                                                                                                                                                       Water Allocation Boundary
     5. All Earthworks to be carried out in accordance with AS 3798

     FOOTINGS:
     1. All footings are to be deepened through any soft spots and bear
         a minimum of 300mm into Recommended Founding Material with
         a minimum bearing capacity of 100kPa
     2. Construct footings under all load bearing walls

     SLAB:(UNO)
     1. To be a minimum of 100mm thick.                                                                                                                                                        Existing Jetty
     2. Reinforcement to be a minimum of SL82 Mesh with 30mm cover.                                                                                                                            to be removed
                                                                                                                                                                                                                                                                                                                               315 outer diameter tube.
         50mm compacted sand bed with 0.2mm Visqueen Moisture barrier                                                                                                                                                                                                                                                          Filled with concrete, N50/20.
         to AS 3360.1 required under slab.                                                                                                                                                                                                                                                                                     Provide 6/N12 bars
     3. Deepen slab to 150mm thick under all bracing walls or position                                                                                                                                                                                                                                                         and R10 helix with 150mm pitch.
         where Chemical or Mechanical anchor bolts are to be used.

     SITE MAINTENANCE:
     1. Finished ground surface must be shaped to direct water away
        from building area in accordance with the BCA requirements.
        Refer to attached CSIRO BTF18: Foundation Maintenance and
        Footing Performance and Homeowners Guide for further Guidance
        on site Maintenance                                                                                                                                                                                                                                                                                                                                                                     Approx Broadwater Bottom

     GENERAL:
     1. These drawings are to be read in conjunction with HR Design Group
         Specification FS.01.




                                                                                                                                                                                                                                                                                                 Water Allocation Boundary
                                                                                                                                                  C1                  C1                       C1                      C1




                                                                                                                                                                                                                                                                                                                                                        TBC by specilist contractor
                                                                                                                                                       Denotes 315Ø jetted concrete piles
                                                                                                                                                       to achieve minimum working loads:
                                                                                                                                                       Vertical load capacity - 21kN
                                                                                                                                                       Horizontal load capacity - 4kN
                                                                                                                                                                                                                       C1
                                                                                                                                                                                                                                         Outline of proposed jetty
                                                                                                                              Property Boundary
                                                                                                             Revetment Wall




                                                                                                                                                                                                                       C1



                                                                                                                                                                                                                                    steps by others                                                                                                                                               Pile depth to be confirmed with
                                                                                                                                                                                                                                                                                                                                                                                                  specilist contractor and install piles
                                                                                                                                                                                                                                                                     Water Allocation Boundary                                                                                                    achieve minimum working loads:
                                                                                                                                                                                                                                                                                                                                                                                      315mm Ø     Vertical load capacity - 21kN
                                                                                                                                                                                                                                                                                                                                                                                                  Horizontal load capacity - 4kN
                                                                                                                                                                                                                                                                       Projected Boundary                                                                                                         Confirm depth with engineer prior to construction
                                                                                                                                                                                                                                                                                                                                                 C1 - 315Ø PILE REINFORCEMENT


  FOR OVERALL DIMENSIONS OF SLAB AND FOOTINGS, REFER ARCHITECTURAL DRAWING
           Issue   Made By    Date          Description                                            PROPOSED NEW JETTY                                                                                                                                                                                                                  Scale : 1:200                                                       NOTES:
           A       WPH        05/09/25      Issue for construction
                                                                                                   at LOT 444 (#18) THE PENINSULA, NOOSAVILLE
REVISION




                                                                                                                                                                                                                                                                                                                                       Job No.: 25-0424                                                    1. Do not scale drawings.
                                                                                                                                                                                                                                                                                                                                                                                                           2. Scale is correct at A3.
                                                                                                   BUILDER: PONTOON WORKS
                                                                                                                                                                                                                                                                                                                                       Dwg No.: S03                                                        3. Check and verify all dimensions
                                                                                                   Designed By : J. SAYERS BEng (Civil) Hons                                                Drawn By : WPH Date : 05/09/25                                                                                                                                                                                   prior to commencement of work.
                                                                                                   Certified By : B.R. CROMAR BEng (Civil) MIEAust CPEng RPEQ NER                                          Date : 05/09/25   Ph: (07) 5444 5578   Email: [email protected]                                                JETTY PILE LAYOUT & DETAILS

Page 5

           FLOOR FRAMING SCHEDULE:

           MARK     SIZE                                               DESCRIPTION
           BR1      2/152x63x6 Channel Section                         Bearer (continuous span)
                    (Alloy & Temper - 6061/T6)

           DJ1      200x50x3.0 Rectangular Hollow Section              Deck Joist (single span)
                    (Alloy & Temper - 6060/T5 or 6106/T6)
                                                                                                                                                                                                                                                                                                                                                       Projected Boundary
           SJ1      200x50x3.0 Rectangular Hollow Section              Structural Joist (single or Cont.)
                    (Alloy & Temper - 6060/T5 or 6106/T6)

           TR1      200x50x3.0 Rectangular Hollow Section              Trimmer (single span)
                    (Alloy & Temper - 6060/T5 or 6106/T6)                                                                                                                                                                                                                                                                                            Water Allocation Boundary


           ST1      80x50x6.0 Rectangular Hollow Section               Strut
                    (Alloy & Temper - 6060/T5 or 6106/T6)

           C1       315Ø Jetted Concrete Piles                         Column

       NOTES:
       1. All floor joists to be at 450mm crs UNO.
                                                                                                                                                                                                                                                                                Existing Jetty
                                                                                                                                                                                                                                                                                to be removed


           NOTE:
           All fixings, connectors, plates and angles
           to be Stainless Steel grade 316 or aluminium


           NOTE:
           All Steel to be protected
           as per AS/NZS 2312.1

                                                                                                                                                                                                                                              Hidden line indicates




                                                                                                                                                                                                                                                                                                                                                                                 Water Allocation Boundary
                                                                                                                                                                                                                                              location of ST1. Typical.
           NOTE:                                                                                                                                                                                                                                                                       (Typical)
           All dissimilar metals to be
                                                                                                                                                                                                                                                SJ1
           isolated to prevent corrosion
                                                                                                                                                                                                      C1                                 C1




                                                                                                                                                                            TR1




                                                                                                                                                                                                                                                                                C1




                                                                                                                                                                                                                                                                                                            1 C1
                                                                                                                                                                                                                                                       DJ1




                                                                                                                                                                                                                                                                                                          BR
                                                                                                                                                                                      BR1




                                                                                                                                                                                                                                  BR1




                                                                                                                                                                                                                                                                          BR1
                                                                                                                                                                                                                                                SJ1
                                                                                                                                                                                                      Cantilevered framing must not
                                                                                                                                                                                                      be fixed to revetment wall.
                                                                                                                                                                                                      Aluminium plate to end of
                                                                                                                                                                                                      framing as specified by builder.
                                                                                                                                                                                                                                                                                                           BR1                       (Typical)




                                                                                                                                                                                                                                                                                                                   C1
                                                                                                                                                                                                                                                                                                    SJ1




                                                                                                                                                                                                                                                                                                                          SJ1
                                                                                                                                                                                                                                                                                                                DJ1                  (Typical)
                                                                                                                                                                                  Property Boundary
                                                                                                                                                           Revetment Wall




                                                                                                                                                                                                                                                                                                          BR1




                                                                                                                                                                                                                                                                                                                   C1
                                                                                                                                                                                                                                                                                                                TR1                steps by others
                                                                                                                                                                                                                                                                                                                                                     Water Allocation Boundary



                                                                                                                                                                                                                                                                                                                                                       Projected Boundary




           Issue   Made By      Date          Description                                                   PROPOSED NEW JETTY                                                                                                                                                                                                                                 Scale : 1:100/1:10                            NOTES:
           A       WPH          05/09/25      Issue for construction
                                                                                                            at LOT 444 (#18) THE PENINSULA, NOOSAVILLE
REVISION




                                                                                                                                                                                                                                                                                                                                                               Job No.: 25-0424                              1. Do not scale drawings.
                                                                                                                                                                                                                                                                                                                                                                                                             2. Scale is correct at A3.
                                                                                                            BUILDER: PONTOON WORKS
                                                                                                                                                                                                                                                                                                                                                               Dwg No.: S04                                  3. Check and verify all dimensions
                                                                                                            Designed By : J. SAYERS BEng (Civil) Hons                                                          Drawn By : WPH Date : 05/09/25                                                                                                                                                                  prior to commencement of work.
                                                                                                            Certified By : B.R. CROMAR BEng (Civil) MIEAust CPEng RPEQ NER                                                    Date : 05/09/25                     Ph: (07) 5444 5578       Email: [email protected]                               JETTY FRAMING LAYOUT & DETAILS

Page 6

                                                                                                                                                                                                                                                                                                                        Provide 50x80x3.0 Fabricated Unequal Angle
                                                                                                                                                                                                                                                                                                                        (Alloy & Temper - 6060/T5 or 6106/T6)
                                                                                                                                                                                                                                                                                                     DJ1                with 2/No.14 x 20mm SS tek screw each way




                                                                                                                                                                                                                                                                                                                         BR1




                                                                                                                                                                                                                                                                                                           80
                                                                                                                           BR1




                                                                                                                                                                                                                                                                                                                Neoprene washers between
                                                                                                                                                                                                                                                                                                                all SS fixings and aluminium.
                                                                                                                                                                                Provide 2/No.14 x 20mm SS tek screw each
                                                                                                                                                                                connection with Neoprene washers between
                                                 400                                                                                                                            all SS fixings and aluminium.
                                                                                                                                                         1                      6mm end plates CFW all round and to BR1
                                                 Typ                           ST
                                                                                  1                                                                    ST




                                                                                                                                                    10mm end plates
                                                                                                                                                    6mm CFW
                                                       1                                                                                            Typical.


                                                              1

                                                                             1/M16 - SS316




                                                                                                                  C1
                                                                             threaded rod through                                      Refer to S03
                                                                             C1                                                        for reinforcement details




                                                                                                                                                                                BR1
                                                                                                                                                                                          125x50x6.0mm UA
                                                                                                                                                                                          4mm CFW to BR1
                                                                                                                                                                                          2/M12 SS Grade 316
                                                                                                                                                                                          chemset anchors.
                                                                                                                                                                                          200mm min embedment.
                                                                                                                                      High strength shrinkage
                                                                                                                                                                                          Epoxy = REO 502
                                                                                                                                      compensated grout pad


                                                                                                                        C1 below



                                                                                                                                                                                                                                                                                                                                           SJ1




                                                                                                                                                                                                                                                                                  BR1
                                                  Stitch weld 'C' Section together                                                                                                                                                                                                      Provide 50x80x3.0 Fabricated Unequal Angle
                                                                                                                                                                                                                                               Neoprene washers between                 (Alloy & Temper - 6060/T5 or 6106/T6)
                                                                                                                                                                                                                                               all SS fixings and aluminum.             with 2/No.14 x 20mm SS tek screw each way
                                                                                                                 BR1




                                                                                                                                                                                                                                                                                                                                                             80
                                                                                                                                                                                                                                                                                                                                                                     BR1
                                                                                                                                                                                                                                                                            SJ1         SJ1
                                                                                                                                                                         C1




                                                                                                                                                                      315mm Ø




           Issue   Made By   Date       Description                                                 PROPOSED NEW JETTY                                                                                                                                                                        Scale : 1:100                                                                NOTES:
           A       WPH       05/09/25   Issue for construction
                                                                                                    at LOT 444 (#18) THE PENINSULA, NOOSAVILLE
REVISION




                                                                                                                                                                                                                                                                                              Job No.: 25-0424                                                             1. Do not scale drawings.
                                                                                                                                                                                                                                                                                                                                                                           2. Scale is correct at A3.
                                                                                                    BUILDER: PONTOON WORKS
                                                                                                                                                                                                                                                                                              Dwg No.: S05                                                                 3. Check and verify all dimensions
                                                                                                    Designed By : J. SAYERS BEng (Civil) Hons                         Drawn By : WPH Date : 05/09/25                                                                                                                                                                         prior to commencement of work.
                                                                                                    Certified By : B.R. CROMAR BEng (Civil) MIEAust CPEng RPEQ NER                   Date : 05/09/25           Ph: (07) 5444 5578   Email: [email protected]                     CONNECTION DETAILS