25-0424 Structural Issue A(1)(1)
SITE CLASSIFICATION:
The site classification for this block, based on the attached soil All footings to be founded on STIFF CLAYS or DENSE SANDS
report, is Class 'N/A' as per AS2870. 'Residential Slabs and Footings'. with an allowable bearing capacity of 100kPa. Engineer to be
on site during excavation to confirm founding material and
bearing capacity.
EARTHWORKS: 65mm
315 outer diameter tube.
1. Prepare the existing foundation below by removal of any top-soil cover
Filled with concrete, N50/20.
containing organic matter which could inhibit compaction Provide 6/N12 bars
2. Proof roll the foundation and remove and reconstruct areas that
and R10 helix with 150mm pitch.
break up or show evidence of movement under proof loading.
3. Sand filling under slabs or footings shall be placed in 200mm
max layers, (Uncompacted), Compacted in accordance with AS1289
315mm Ø
E5.1 (Density to be greater than 65% in accordance with AS1289 E6.1)
4. Fill material other than sand (ie gravel, decomposed rock or
broken rock, free from organic material and lumps of clay) under
slabs or footings to be compacted to achieve an density ratio Projected Boundary
(calculated by AS1289 E4.1) of not less that 95% at maximum
dry density as determined by AS 1289 E1.1
Alternatively fill is to be placed an machine track rolled and piers
drilled/installed as per the layout plan. Compaction testing is then
not required due to the presence of supporting piers. Water Allocation Boundary
5. All Earthworks to be carried out in accordance with AS 3798
FOOTINGS:
1. All footings are to be deepened through any soft spots and bear
a minimum of 300mm into Recommended Founding Material with
a minimum bearing capacity of 100kPa
2. Construct footings under all load bearing walls
SLAB:(UNO)
1. To be a minimum of 100mm thick. Existing Jetty
2. Reinforcement to be a minimum of SL82 Mesh with 30mm cover. to be removed
315 outer diameter tube.
50mm compacted sand bed with 0.2mm Visqueen Moisture barrier Filled with concrete, N50/20.
to AS 3360.1 required under slab. Provide 6/N12 bars
3. Deepen slab to 150mm thick under all bracing walls or position and R10 helix with 150mm pitch.
where Chemical or Mechanical anchor bolts are to be used.
SITE MAINTENANCE:
1. Finished ground surface must be shaped to direct water away
from building area in accordance with the BCA requirements.
Refer to attached CSIRO BTF18: Foundation Maintenance and
Footing Performance and Homeowners Guide for further Guidance
on site Maintenance Approx Broadwater Bottom
GENERAL:
1. These drawings are to be read in conjunction with HR Design Group
Specification FS.01.
Water Allocation Boundary
C1 C1 C1 C1
TBC by specilist contractor
Denotes 315Ø jetted concrete piles
to achieve minimum working loads:
Vertical load capacity - 21kN
Horizontal load capacity - 4kN
C1
Outline of proposed jetty
Property Boundary
Revetment Wall
C1
steps by others Pile depth to be confirmed with
specilist contractor and install piles
Water Allocation Boundary achieve minimum working loads:
315mm Ø Vertical load capacity - 21kN
Horizontal load capacity - 4kN
Projected Boundary Confirm depth with engineer prior to construction
C1 - 315Ø PILE REINFORCEMENT
FOR OVERALL DIMENSIONS OF SLAB AND FOOTINGS, REFER ARCHITECTURAL DRAWING
Issue Made By Date Description PROPOSED NEW JETTY Scale : 1:200 NOTES:
A WPH 05/09/25 Issue for construction
at LOT 444 (#18) THE PENINSULA, NOOSAVILLE
REVISION
Job No.: 25-0424 1. Do not scale drawings.
2. Scale is correct at A3.
BUILDER: PONTOON WORKS
Dwg No.: S03 3. Check and verify all dimensions
Designed By : J. SAYERS BEng (Civil) Hons Drawn By : WPH Date : 05/09/25 prior to commencement of work.
Certified By : B.R. CROMAR BEng (Civil) MIEAust CPEng RPEQ NER Date : 05/09/25 Ph: (07) 5444 5578 Email: [email protected] JETTY PILE LAYOUT & DETAILS