Sam Hopper – Slope Stability Assessment and Geotechnical Report - Proposed Residence, 24 Arakon Crescent, Sunshine Beach
7.2.3 Further Comments Regarding Foundations
Foundation Design
As noted above this site has been classified as ‘P’, however, if the site was classified based on
reactivity alone, under normal moisture conditions, a ground surface movement (ys) of <20mm
(maximum) could be adopted, which relates to a Class ‘S’ (slightly reactive) site (considering
the proposed development, existing subsurface profile as per boreholes records, and taking into
account other relevant geotechnical data held by Soil Surveys Engineering).
It should also be noted that the methodology adopted for determination of the site classification
assumes the structure has performance requirements similar to domestic type construction.
Development of Abnormal Soil Conditions
It is recommended that design works for the proposed development take into account the long
term effect of any design elements on the subsurface moisture conditions under and around the
structure.
These design works should consider aspects of the design that may contribute to the
development of abnormal moisture conditions i.e.:-
Site drainage
Gardens and landscaping
Future planting of trees and shrubs
Services and repair of leaks
The designer is directed to AS 2870-2011 Appendix B and Section 8.2.7 of this report which
outlines measures that should be considered.
7.2.4 High Level Footings
Where high level footings are adopted, our recommendation is that all perimeter footings,
footings under isolated columns and strip footings below internal load bearing walls be founded
at least 300mm below platform level and a minimum of 300mm into the natural sands.
Table 6 outlines minimum allowable bearing capacities for high level foundations on the site.
TABLE 6 ALLOWABLE BEARING CAPACITIES FOR HIGH LEVEL FOOTINGS
Allowable Bearing Capacity (kPa)
Material
Strip Footing Pad Footing
Fill Uncontrolled NR NR
Sand Loose NR NR
Compacted to 70% density index 100 125
Medium Dense 100 125
Dense 200 250
Very Dense 400 450
Note: NR - Not Recommended
The base of all pad and strip footings founding in sand should be individually re-compacted
using a vibrating plate compactor prior to placement of reinforcing steel and concrete as soils
may be loosened during the excavation process by machinery action.
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Attachment C - Soil Survey Report.pdfRelated documentApplication case desk ↗
About this file
- File size
- 4.1 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.