MASONRY SPECIFICATION.
Construction: masonry work to comply with AS3700.
Masonry Unit Strength: f'uc = 15mPa (unconfined strength)
Mortar: cement 1, lime 1/2, sand 41/2 + methyl cellulose water
thickener
Grout: f'c = 20mPa (confined test) with 10mm aggregate with pouring
consistency & a minimum cement content of
300kg/cubic metre
Steelwork cover: as indicated on drawings but not less than 20mm from
the face of the grout to the reinforcement face.
Reinforcement laps: deformed bars - 40 times* bar diameter
Grout placement & compaction, careful placement to avoid segregation & disturbance of
mortar joints and compact with a 25mm rod. Note - all lintels must be fully propped during &
for a minimum of 14 days (or for longer if required) after the construction of upper walls,
slabs, roofs or other structural elements.