Hydrant (H1) and water main performance test. Water was drawn, at the flow rates below, from both
outlets of a standpipe attached to street spring hydrant H1. The pressure was recorded at the outlet of
H1 to determine the hydrant performance. This test is used to determine if the hydrant meets the flow
and pressure requirements of AS2419.1 (if applicable). The water main residual pressure was
measured from a standpipe attached to spring hydrant H2.
Flow - H1 Hydrant Pressure - Water Main Residual
(L/s) H1 Pressure - H2
(kPa) (kPa)
0 465 470
5 430 460
10 390 435
15 325 400
20 260 370
25 130 310
29.1 10 265
Hydrant Condition: H1 and H2 were in good condition with a powder coat exterior.
Test time and date: 09:43 am, 3rd of July, 2019
Technician: Thomas Manning
Notes:
• The test results are correct at the time of the tests
• It is the responsibility of the recipient to determine the effect of changes in domestic/industrial usage, modifications to the
main, differences in RL and extra hydraulic losses between the hydrant and tie in locations
• Flow meters and pressure gauges are calibrated annually
• Flows are accurate to ±0.2L/s. Pressures are accurate to ±10kPa
Thank you for engaging HTC. Please do not hesitate to call on 0423 383 329 should you have any
queries. Regards,
Water Mains Flow and Pressure Testing | Hydrostatic Testing | Boosted Hydrant Certification
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
HTC FLOW AND PRESSURE TEST REPORT.pdfRelated documentApplication case desk ↗
About this file
- File size
- 409 KB (small file)
- File type
No other editions are linked here.