Hydrant (H1) and water main performance test. Water was drawn, at the flow rates below, from both
outlets of a standpipe attached to street spring hydrant H1. The pressure was recorded at the outlet of
H1 to determine the hydrant performance. This test is used to determine if the hydrant meets the flow
and pressure requirements of AS2419.1 (if applicable). The water main residual pressure was
measured from a standpipe attached to spring hydrant H2.

                    Flow - H1                      Hydrant Pressure -             Water Main Residual
                    (L/s)                          H1                             Pressure - H2
                                                   (kPa)                          (kPa)
                    0                              465                            470
                    5                              430                            460
                    10                             390                            435
                    15                             325                            400
                    20                             260                            370
                    25                             130                            310
                    29.1                           10                             265

Hydrant Condition: H1 and H2 were in good condition with a powder coat exterior.

Test time and date: 09:43 am, 3rd of July, 2019
Technician: Thomas Manning

Notes:
• The test results are correct at the time of the tests
• It is the responsibility of the recipient to determine the effect of changes in domestic/industrial usage, modifications to the
main, differences in RL and extra hydraulic losses between the hydrant and tie in locations
• Flow meters and pressure gauges are calibrated annually
• Flows are accurate to ±0.2L/s. Pressures are accurate to ±10kPa


Thank you for engaging HTC. Please do not hesitate to call on 0423 383 329 should you have any
queries. Regards,




           Water Mains Flow and Pressure Testing           |   Hydrostatic Testing     |   Boosted Hydrant Certification

Used in these records

About this file

File size
409 KB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

HTC FLOW AND PRESSURE TEST REPORT.pdf · 409 KB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.